14
Typical Vigilon System
Typical Vigilon System
The loop allows wiring of addressable devices like
fi
re sensors, alarm sounders, call
points, interface units, mimic and repeat panels
, a combined maximum of up to
200
devices are allowed per loop circuit, a further limit on a loop circuit is determined by
device loading.
Vigilon Fire System
GENT 2015
Panel healthy
15:45
Active
Fault/Dis
Fire Routing O/P
Vigilon Fire System
GENT 2015
Designed to EN54 Pt 2 & 4
Healthy
15:45
Fault
System Fault
Test
Fire
Power
Power Fault
Fault/Dis
Disablement
Sounder
Previous
Next
Delay
Verify
Active
Fire Routing O/P
Repeat Panel
Conventional 2-wire
system equipment
(eg 7800 detectors)
Conventional 2-wire
system equipment
230V ac / 24V dc
Magnetic door
release
230V ac
230V ac
Output to control plant
Input output signals
may be used to control
and monitor:
Plant equipment
Building management system
Tx
Rx
Loop circuit 1
T
S
3
Mimic Panel
Spur
T
S
3
S
4
S
4
230V ac
Addressable System Devices
- Manual Call Point
- T Breaker
T
- End of Line Unit
- Magnetic door release
Conventional Products off
interface inputs
- Alarm sounder
- Conventional Fire Detector
- Manual Call Point
- Beam sensor
Transmitter and receiver
Tx
Rx
S
3
- S-Cubed
Voice enhanced Speech,
Sounder, Strobe Unit
S
4
- S-Quad
Sensor Speech Sounder &
VAD/Strobe
- S4 1-Input
loop powered interface
S4
i
- S4 1- Confirmation
input loop powered interface
S4
o
- S4 Mains switching output
loop powered interface
S4
o~
- S4 4-Input/Output
loop powered interface
S4
i/o
- Remote LED
L
LED off S sensor
4
S
4
S
4
S
4
S4
i/o
S4
i
S4
o~
S
4
Optional Loop circuits 2 to 4/6
Fire /Fault
Two auxiliary relays
contacts
rated 1A @ 24Vdc
Battery box
(needed for
VIG1-72 only)
Conventional
Sounders on
(Two master
alarm circuits)
400mA per circuit
Clean
contacts rated
1A @ 24Vdc
230V ac
EN Vigilon
Control Panel
Port 1 (RS485)
Port 0 (RS232)
S4
MP
- S4 - Input/Output
mains powered interface unit
S4
MP
S
4
L
- S4 - Input/Output
ASD interface unit
S4
ASD
S4
ASD
FAAST