19
Vigilon fire system
Power supply
Standard
Designed to EN54-4 : 1997 + A1:2002 and A2:2006
Mains supply voltage and
fuses
230V -15% +10% 50Hz/60Hz
protected by: FS3 T3.15AH250V Ceramic (20 x 5 mm) on PSU
Input current - 1.4A
Nominal supply voltage for
master alarm circuits
24V +1V, -4V
Battery circuit(s)
Terminals to connect to internally or externally housed
batteries. Batteries reach fully charged state in 72Hr for
VIG1-24 and VIG1-72.
Battery current with mains
disconnected
VIG1-24 - 6.2A max.
VIG1-72 - 6.2A max. over two battery sets
Light indications
To show the status of PSU
PSU Fuses Mains
44V supply
Battery charge circuit 1
Battery charge circuit 2
FS6 T3.15A Ceramic
FS2 F3.15A Glass
FS1 F10A Ceramic for VIG1-72 only
FS7 F6.3A Ceramic Quick Blow for VIG1-24 only
FS3 F10A Ceramic for VIG1-72 only
All fuses 20mm x 5mm size
Storage temperature
-10ºC to +55ºC
Operating temperature
-5ºC to +40ºC
Relative Humidity
up to 90% (Non condensing) Tempe5ºC to +45°C
Indicators
LD1 - LD5
indicate RAM, ROM and EPROM status, error,
checksum and communication
Battery Charging current
1 x 2.4A nominal for VIG1-24
2 x 3.6A nominal for VIG1-72
EN54 Part 4 data VIG1-24
VIG1-72
I min
-> 780uA
I max a* -
max quiescent loop current
-> 108mA @ 43.5V
I max b -
max alarm loop current
-> 3.15A @ 46.4V
Ri max -> 0.9R
UVLO -> 20.7V ± 0.4V
I min
-> 780uA
I max a* -
max quiescent loop current
-> 162mA @ 43.5V
I max b -
max alarm loop current
-> 3.15A @ 46.4V
Ri max -> 1.25R
UVLO -> 20.7V ± 0.4V
*max a - Max loop current
27mA x 6 = 162mA quiescent for VIG1-72 panel
27mA x 4 = 108mA quiescent for VIG1-24 panel
Hazardous voltages may still be present even when the indicators
are extinguished.