4188-1075 issue 3_Part 2_08/14

9

Loop Loading

Panel messages associated with Loop cards V4.48 and possible actions

Message..

Indications 
given..

associated 
with..

meaning..

possible action

Loop n: High 
resistance on 
negative line

FAULT LED - On
Buzzer - On

LPC

(2Km Loop 
Processor 
Card)

High resistance on 0v 
lines.

Use the Loop Diagnostic 
Tool to diagnose the cause 
of high resistance on the 
negative line and rectify it.

Loop n: High 
resistance

FAULT LED - On
Buzzer - On

LPC

(2Km Loop 
Processor 
Card)

High resistance on 
both lines.

Use the Loop Diagnostic 
Tool to diagnose the cause 
of high resistance on the 
loop and rectify it.

Earth Fault at 
Card n
Loop n: 0v 
resistance is 
xxR, L is y
Loop n: Earth is 
aaa, bbb (99)

LPC

(2Km Loop 
Processor 
Card)

Th

  ere is an earth 

fault present before 
allocation. 
Note: An Earth fault 
post allocation is 
indicated as Earth 
fault.

Use the Loop Diagnostic 
Tool to diagnose the earth 
fault condition and rectify 
it.

Technical Data - Loop Cards (VIG-LPC-EN and COMPACT-LPC-EN) 

Dimensions

VIG-LPC-EN

COMPACT-LPC-EN

130mm x 100mm x 15mm

120mm x 100mm x 15mm 

Weight

74g approximately

Devices            

200 device / loop circuit

Voltage and Current

46.4V in alarm @ 0.8A maximum load #

Terminations and cables

The wiring terminals are located on the Iconic panel Baseboard, each can accept up 

to 2.5mm² cable

Cables: 

U

se only the EMC compliant 2-core 

fi

 re cables recommended in the panel Installation manual.

Loop cable length can be: up to 1.5Km with 1.5mm²  cable #

up to 2.5Km  with 2.5mm² cable #

Operating temperature

0°C to +45°C

Storage temperature

-10°C to +55°C

Relative humidity 

(non condensing)

up to 90%

# - refer to battery standby and loop load calculator to determine the loop cable length.

Содержание GENT COMPACT-LPC-EN

Страница 1: ...arios 2 1 2 1 Loop card MCC MCB and PSU combinations VAD is a Visual Alarm Device The Loop card VIG LPC EN or COMPACT LPC EN must never be used in a Vigilon panel based System having device mix with 3400 sensors T 3 Post March 2014 build of EN Compact Loop card COMPACT LPC EN V4 48 or higher MCB 1 2 V4 52 or higher Post March 2014 build of EN Vigilon Loop card VIG LPC EN V4 48 or higher Pre or Pos...

Страница 2: ... EN or COMPACT LPC EN can only be used as a replacement card for Older Build Loop card VIG LPC or COMPACT LPC where S4 and S3 Mark 1 2 devices or 34000 devices are installed on the loop circuit Up to 2Km loop length is possible with 1 5mm cable with S4 and S3 Mark 1 2 devices installed on a loop circuit In this case a rough method for calculating the loop load and loop cable length is shown in par...

Страница 3: ...by Lumped alarm devices load If the alarm devices are lumped together on a loop circuit then there is a trade off between the number of alarm devices and loop cable length possible which must be calculated Use the Battery Standby and loop load calculator tool to determine the precise loop length loop load and panel standby In the absence of the tool a rough method to determine loop length and load...

Страница 4: ...ent Device part number Description VAD POWER Maximum limit per loop No of Devices on loop Alarm current mA per device Alarm current x VIG RPT 72 Repeat panel 4 ______ x 1 20 VIG MIM A3 A3 Zonal Mimic panel 4 ______ x 1 20 S4 720 Heat Sensor 200 ______ x 0 20 S4 710 Optical Heat Sensor 200 ______ x 0 20 S4 711 Dual Optical Heat Sensor 200 ______ x 0 20 S4 770 S Optical Heat Turbo Sounder 177 ______...

Страница 5: ...45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 VAD HPR Dual Optical Heat CO Turbo Voice Red VAD L M H 76 50 39 ______ x ______ x ______ x 10 5 15 8 20 28 Dual Optical Heat CO Non Turbo Voice Red VAD L M H 100 60 45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 replaced with S4 901 Dual Optical Heat Sensor CO 200 ______ x 0 20 S4 34760 Venturi Air Duct Kit 200 ______ x 0 20 S4 34740 Beam sensor...

Страница 6: ...150 75 ______ x ______ x 2 60 5 30 S4 711 ST VO Dual Optical Heat Sensor Speech Strobe 55 40 ______ x ______ x 7 00 10 0 S4 911 ST VO Dual Optical Heat Sensor CO Strobe Sounder Speech 55 40 ______ x ______ x 7 00 10 0 A Total Alarm Current Distributed Alarm load Ensure the Total Alarm Current value calculated does not exceed the maximum total alarm current value shown below to achieve 2Km loop len...

Страница 7: ... 1 2 2 2 3 2 4 2 5 200 mA 275 mA 300 mA 190 170 150 325 mA 180 170 150 120 100 350 mA 180 150 120 110 100 80 60 375 mA 190 170 150 120 100 80 60 n a n a 400 mA 190 170 150 130 110 90 70 n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop wh...

Страница 8: ... 190 170 160 150 140 600 mA 190 180 170 150 140 100 90 80 60 n a 700 mA 190 170 160 150 130 120 110 100 60 n a n a n a n a 800m A 190 180 160 150 130 120 110 100 80 70 60 n a n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop where there i...

Страница 9: ... an earth fault present before allocation Note An Earth fault post allocation is indicated as Earth fault Use the Loop Diagnostic Tool to diagnose the earth fault condition and rectify it Technical Data Loop Cards VIG LPC EN and COMPACT LPC EN Dimensions VIG LPC EN COMPACT LPC EN 130mm x 100mm x 15mm 120mm x 100mm x 15mm Weight 74g approximately Devices 200 device loop circuit Voltage and Current ...

Страница 10: ...ware To enable the new loop card to supply the full alarm load in a system having Vigilon 4 6 loop panel we need the new power supply backplane and loop card The following photos show where to look to identify old and new parts 2211 187 V4 xx Older build of Vigilon PSU VS PSU 24 or VS PSU 72 Post July 2013 build of Vigilon PSU Older build of build of Vigilon LPC Post March 2014 build of Vigilon LP...

Отзывы: