Loop loading

(VIG-LPC-EN and COMPACT-LPC-EN)

4188-1075 issue 3_Part 2_08/14

3

This document shows how to determine the loop load and loop cable length for a Post March 2014 Loop Card 

fitted in a Vigilon panel:

 

 

VIG-LPC-EN   (for use in Vigilon 4-6 loop panels only)

 

COMPACT-LPC-EN  (for use in Vigilon Compact panel only)

A precise battery standby calculation result is obtained using the ‘Battery standby and loop load calculator’ 
tool. The tool can be downloaded from www.gentexpert.co.uk website, accessible to registered users.

Distributed alarm device load 

This is where the alarm load is distributed along the entire length of the loop and when using:

 

1.5mm² cable, the loop length can be up to 2Km with up to 200 devices and up to 400mA alarm current for standard 
mode of loop card operation  / 800mA alarm load for enhanced mode of loop card operation. 

 

2.5mm

²

 cable, the loop length can be up to 2.5Km with up to 200 devices and up to 400mA alarm current for 

standard mode of loop card operation  / 800mA alarm load for enhanced mode of loop card operation.

U

se table 1 to calculate the loop alarm load.

Always use the 

‘Battery Standby and loop load calculator tool’

 to determine loop load and panel battery standby.

Lumped alarm devices load

If the alarm devices are lumped together on a loop circuit then there is a trade off between the number of alarm devices and loop 
cable length possible, which must be calculated.
Use the 

‘Battery Standby and loop load calculator tool’

 to determine  the precise loop length, loop load and panel standby. In 

the absence of the tool a rough method to determine

 loop length and loading only

 is shown here. Use table 1 to determine alarm 

load and respective table 2, 3, 4 or 5 to determine loop length and loop load.

What are Lumped and Distributed alarm device loads?

Example of Lumped alarm device load

Vigilon 

Compact panel
shown

S

4

AV

S

3

AV

S

4

S

4

AV

S

4

AV

S

4

AV

S

4

AV

S

3

AV

S

3

AV

S

4

S

4

S

4

Where 35% of the alarm devices            are
lumped together in 1/4 segment     ,     ,     or      of a loop.

S

4

AV

S

3

AV

C

D

S

3

AV

S

4

S

4

S

4

This example
shows lumped devices
along cable length      .
    

Vigilon 

Compact panel
shown

S

4

AV

S

3

AV

S

4

S

4

AV

S

4

AV

S

3

AV

S

3

AV

S

4

S

4

S

4

Distributed alarm devices            are evenly 
spaced along the entire length of the loop cable
from end to end. 

S

3

AV

S

4

S

4

S

4

S

3

AV

S

4

AV

S

4

AV

S

3

AV

S

4

AV

S

4

AV

S

4

S

4

AV

S

3

AV

Example of Distributed alarm device load

S

4

AV

S

3

AV

- Audio Visual S4 and S3 devices

S

4

- S4 Sensor only devices

- Other system devices

key:

B

A

C

D

B

A

D

System with VAD only devices, S4 Sensors and S4 Sensor Sounders is capable of up to 0.8A alarm load.

Содержание GENT COMPACT-LPC-EN

Страница 1: ...arios 2 1 2 1 Loop card MCC MCB and PSU combinations VAD is a Visual Alarm Device The Loop card VIG LPC EN or COMPACT LPC EN must never be used in a Vigilon panel based System having device mix with 3400 sensors T 3 Post March 2014 build of EN Compact Loop card COMPACT LPC EN V4 48 or higher MCB 1 2 V4 52 or higher Post March 2014 build of EN Vigilon Loop card VIG LPC EN V4 48 or higher Pre or Pos...

Страница 2: ... EN or COMPACT LPC EN can only be used as a replacement card for Older Build Loop card VIG LPC or COMPACT LPC where S4 and S3 Mark 1 2 devices or 34000 devices are installed on the loop circuit Up to 2Km loop length is possible with 1 5mm cable with S4 and S3 Mark 1 2 devices installed on a loop circuit In this case a rough method for calculating the loop load and loop cable length is shown in par...

Страница 3: ...by Lumped alarm devices load If the alarm devices are lumped together on a loop circuit then there is a trade off between the number of alarm devices and loop cable length possible which must be calculated Use the Battery Standby and loop load calculator tool to determine the precise loop length loop load and panel standby In the absence of the tool a rough method to determine loop length and load...

Страница 4: ...ent Device part number Description VAD POWER Maximum limit per loop No of Devices on loop Alarm current mA per device Alarm current x VIG RPT 72 Repeat panel 4 ______ x 1 20 VIG MIM A3 A3 Zonal Mimic panel 4 ______ x 1 20 S4 720 Heat Sensor 200 ______ x 0 20 S4 710 Optical Heat Sensor 200 ______ x 0 20 S4 711 Dual Optical Heat Sensor 200 ______ x 0 20 S4 770 S Optical Heat Turbo Sounder 177 ______...

Страница 5: ...45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 VAD HPR Dual Optical Heat CO Turbo Voice Red VAD L M H 76 50 39 ______ x ______ x ______ x 10 5 15 8 20 28 Dual Optical Heat CO Non Turbo Voice Red VAD L M H 100 60 45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 replaced with S4 901 Dual Optical Heat Sensor CO 200 ______ x 0 20 S4 34760 Venturi Air Duct Kit 200 ______ x 0 20 S4 34740 Beam sensor...

Страница 6: ...150 75 ______ x ______ x 2 60 5 30 S4 711 ST VO Dual Optical Heat Sensor Speech Strobe 55 40 ______ x ______ x 7 00 10 0 S4 911 ST VO Dual Optical Heat Sensor CO Strobe Sounder Speech 55 40 ______ x ______ x 7 00 10 0 A Total Alarm Current Distributed Alarm load Ensure the Total Alarm Current value calculated does not exceed the maximum total alarm current value shown below to achieve 2Km loop len...

Страница 7: ... 1 2 2 2 3 2 4 2 5 200 mA 275 mA 300 mA 190 170 150 325 mA 180 170 150 120 100 350 mA 180 150 120 110 100 80 60 375 mA 190 170 150 120 100 80 60 n a n a 400 mA 190 170 150 130 110 90 70 n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop wh...

Страница 8: ... 190 170 160 150 140 600 mA 190 180 170 150 140 100 90 80 60 n a 700 mA 190 170 160 150 130 120 110 100 60 n a n a n a n a 800m A 190 180 160 150 130 120 110 100 80 70 60 n a n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop where there i...

Страница 9: ... an earth fault present before allocation Note An Earth fault post allocation is indicated as Earth fault Use the Loop Diagnostic Tool to diagnose the earth fault condition and rectify it Technical Data Loop Cards VIG LPC EN and COMPACT LPC EN Dimensions VIG LPC EN COMPACT LPC EN 130mm x 100mm x 15mm 120mm x 100mm x 15mm Weight 74g approximately Devices 200 device loop circuit Voltage and Current ...

Страница 10: ...ware To enable the new loop card to supply the full alarm load in a system having Vigilon 4 6 loop panel we need the new power supply backplane and loop card The following photos show where to look to identify old and new parts 2211 187 V4 xx Older build of Vigilon PSU VS PSU 24 or VS PSU 72 Post July 2013 build of Vigilon PSU Older build of build of Vigilon LPC Post March 2014 build of Vigilon LP...

Отзывы: