background image

4188-1075 issue 3_Part 2_08/14

7

Loop Loading

Loop length and quantities for Standard mode with non VAD devices

Use either Table 2 or Table 3 to determine the maximum number of devices on a loop and loop cable length possible for lumped 
alarm load. The examples 1 and 2 below show how to use the tables to determine loading and loop cable length.

Table 2  Lumped load using 1.5mm²  loop cable

Assuming S-Quad with older sounder including strobe and S-Cube Mark 1/2 devices, ie non compliant Part 23 devices.

A

Total 

Alarm 

Current

Loop cable length in Km including spurs using 1.5mm² cable 

B

    

C

 Maximum allowed devices of any type on a loop for a

           

Lumped alarm load

 only.

            

 blank cell = 200 devices

            n/a = not applicable (condition not allowed)

0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

225 mA
250 mA

190 160 130

275 mA

190 150 130 100 70

300 mA

170 130 100 70 n/a n/a

325 mA

180 150 120 90 n/a n/a n/a n/a

350 mA

170 140 110 70 n/a n/a n/a n/a n/a

375 mA

160 130 100 70 n/a n/a n/a n/a n/a n/a

400 mA

170 140 110 70 n/a n/a n/a n/a n/a n/a n/a

Table 3  Lumped load using 2.5mm²  loop cable 

Assuming S-Quad with sounder including strobe and S-Cube Mk 1/2 devices, ie non compliant Part 23 devices.

A

 

Total 

Alarm 

Current

Loop cable length in Km including spurs using 2.5mm² cable 

B

    

C

 Maximum allowed devices of any type 

           on a loop for a 

Lumped alarm load

 

           only.

        

 blank cell = 200 devices

        n/a = not applicable (condition not 
        allowed)

0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5

200 mA
275 mA
300 mA

190 170 150

325 mA

180 170 150 120 100

350 mA

180 150 120 110 100 80 60

375 mA

190 170 150 120 100 80 60 n/a n/a

400 mA

190 170 150 130 110 90 70 n/a n/a n/a n/a

Example 1 

Devices allowed on a known loop cable length for Lumped alarm load

If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop where 
there is lumped alarm devices. 
a.  First calculate the 

total alarm current

 value 

A

, use 

Table 1

b.  Use the calculated 

total alarm current 

A

 and the known loop cable length 

B

 to look up in 

Table 2

 or 

3

 the maximum number 

of devices 

C

 that can be connected to the loop. 

For example if the 

total alarm current

  

A

  is 350mA when using 1.5mm² loop cable that is 

B

 1.5Km in length, then 

Table 2

 tells 

you for 

lumped alarm devices

 the maximum number of devices allowed on the loop must be limited to 

C

 

70

 devices.

Example 2 

Loop cable length allowed for known Lumped alarm device load

If the number of devices on a loop is known then you can determine the maximum cable length that can be used on the loop circuit. 
a.  First calculate the 

total alarm current

 value 

A

, use 

Table 1. 

b. Use the 

total alarm current 

A

 and the known number of devices on the loop to look up in 

Table 2

 or 

3

 and work out the 

maximum length of loop cable allowed 

B

 for the connection lumped alarm devices. 

For example if the 

total alarm current

 

A

 is 225mA and if 200 devices 

C

 are required on the loop, then 

Table 2

 tells you the 

maximum loop cable length  

B

 can be 2Km for lumped alarm load, when using 1.5mm² loop cable.  However Table 2 tells you if 

2.5mm² loop cable is used then the cable length can be up to 2.5Km.

Содержание GENT COMPACT-LPC-EN

Страница 1: ...arios 2 1 2 1 Loop card MCC MCB and PSU combinations VAD is a Visual Alarm Device The Loop card VIG LPC EN or COMPACT LPC EN must never be used in a Vigilon panel based System having device mix with 3400 sensors T 3 Post March 2014 build of EN Compact Loop card COMPACT LPC EN V4 48 or higher MCB 1 2 V4 52 or higher Post March 2014 build of EN Vigilon Loop card VIG LPC EN V4 48 or higher Pre or Pos...

Страница 2: ... EN or COMPACT LPC EN can only be used as a replacement card for Older Build Loop card VIG LPC or COMPACT LPC where S4 and S3 Mark 1 2 devices or 34000 devices are installed on the loop circuit Up to 2Km loop length is possible with 1 5mm cable with S4 and S3 Mark 1 2 devices installed on a loop circuit In this case a rough method for calculating the loop load and loop cable length is shown in par...

Страница 3: ...by Lumped alarm devices load If the alarm devices are lumped together on a loop circuit then there is a trade off between the number of alarm devices and loop cable length possible which must be calculated Use the Battery Standby and loop load calculator tool to determine the precise loop length loop load and panel standby In the absence of the tool a rough method to determine loop length and load...

Страница 4: ...ent Device part number Description VAD POWER Maximum limit per loop No of Devices on loop Alarm current mA per device Alarm current x VIG RPT 72 Repeat panel 4 ______ x 1 20 VIG MIM A3 A3 Zonal Mimic panel 4 ______ x 1 20 S4 720 Heat Sensor 200 ______ x 0 20 S4 710 Optical Heat Sensor 200 ______ x 0 20 S4 711 Dual Optical Heat Sensor 200 ______ x 0 20 S4 770 S Optical Heat Turbo Sounder 177 ______...

Страница 5: ...45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 VAD HPR Dual Optical Heat CO Turbo Voice Red VAD L M H 76 50 39 ______ x ______ x ______ x 10 5 15 8 20 28 Dual Optical Heat CO Non Turbo Voice Red VAD L M H 100 60 45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 replaced with S4 901 Dual Optical Heat Sensor CO 200 ______ x 0 20 S4 34760 Venturi Air Duct Kit 200 ______ x 0 20 S4 34740 Beam sensor...

Страница 6: ...150 75 ______ x ______ x 2 60 5 30 S4 711 ST VO Dual Optical Heat Sensor Speech Strobe 55 40 ______ x ______ x 7 00 10 0 S4 911 ST VO Dual Optical Heat Sensor CO Strobe Sounder Speech 55 40 ______ x ______ x 7 00 10 0 A Total Alarm Current Distributed Alarm load Ensure the Total Alarm Current value calculated does not exceed the maximum total alarm current value shown below to achieve 2Km loop len...

Страница 7: ... 1 2 2 2 3 2 4 2 5 200 mA 275 mA 300 mA 190 170 150 325 mA 180 170 150 120 100 350 mA 180 150 120 110 100 80 60 375 mA 190 170 150 120 100 80 60 n a n a 400 mA 190 170 150 130 110 90 70 n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop wh...

Страница 8: ... 190 170 160 150 140 600 mA 190 180 170 150 140 100 90 80 60 n a 700 mA 190 170 160 150 130 120 110 100 60 n a n a n a n a 800m A 190 180 160 150 130 120 110 100 80 70 60 n a n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop where there i...

Страница 9: ... an earth fault present before allocation Note An Earth fault post allocation is indicated as Earth fault Use the Loop Diagnostic Tool to diagnose the earth fault condition and rectify it Technical Data Loop Cards VIG LPC EN and COMPACT LPC EN Dimensions VIG LPC EN COMPACT LPC EN 130mm x 100mm x 15mm 120mm x 100mm x 15mm Weight 74g approximately Devices 200 device loop circuit Voltage and Current ...

Страница 10: ...ware To enable the new loop card to supply the full alarm load in a system having Vigilon 4 6 loop panel we need the new power supply backplane and loop card The following photos show where to look to identify old and new parts 2211 187 V4 xx Older build of Vigilon PSU VS PSU 24 or VS PSU 72 Post July 2013 build of Vigilon PSU Older build of build of Vigilon LPC Post March 2014 build of Vigilon LP...

Отзывы: