ACCESSORIES
MAN0987_Iss 2_09/16
31
FSL100 Series Flame Detectors
Technical Handbook
10 FSL100-TL Test Lamp Non-EX
The FSL100-TL (test lamp) is a rechargeable, hand-held IR and UV radiation source that is specifically designed to test
Honeywell FSL100 series flame detectors used in
safe areas only
. The detection range is approximately 4 meters (13 ft).
It is supplied in a custom carry case with a dedicated charging unit suitable for mains connection.
10.1 Safety Instructions
Read this manual carefully and study the warnings and cautions before using this equipment.
1. This test lamp is only suitable for testing Honeywell FSL100 series flame detectors in safe areas.
2. Do not use the test lamp in wet conditions.
3. Ensure testing of the flame detectors does not activate unwanted alarm signals.
4. Press the trigger to switch on, release it to switch off.
5. Batteries may be damaged if you use the test lamp continuously for longer than 10 minutes.
6. The grid may become hot during use. Be careful not to allow contact with skin or flammable objects.
7. Do not touch or remove the protective grid or stick fingers or objects through it.
8. Do not point directly at eyes from a short distance. Do not look directly into the light.
9. Store the test lamp in its box in a clean and dry location. A dirty reflector will reduce the test range.
10. Do not incinerate or mistreat the lamp or battery as the battery could leak or explode.
11. The test lamp should not be used when damaged. If a fault does occur, do not open the lamp other than to change the
battery. Return faulty lamps to Honeywell Analytics for repair.
12. Keep the test lamp and batteries away from children. Dispose of items in accordance with the WEEE directive.
Figure 18.
FSL100-TL Test Lamp Kit
Warning
– Safe Areas Only
The FSL100-TL test lamp is only compatible with the Honeywell Analytics FSL100 series flame detectors used
in safe areas. The test lamp is not approved for use with any other types of detector or location.
Always ensure that relay operated systems (drenchers, alarms, etc.) are inhibited or disabled before operating
this test lamp in the vicinity of any flame detector.
Always ensure that Alarm Systems are returned to Normal Operation when work is completed.