DIAGNOSTIC INFORMATIONS
Detailed diagnostic information for an easy troubleshooting of your muting application is available using the following indicators:
•
internal indicators: LED "RUN1" and "RUN2" located on the module front panel,
•
external indicators: muting lamp connected to terminals 48.
In the case of a failure the indicators are indicating a flashing code. There exist two types of errors:
•
FATAL ERRORS are only indicated by flashing internal LED's "RUN1" and /or "RUN2". The muting lamp connected to terminal
48 remains permanently off.
The normally open safety contacts (13/14, 23/24, 33/34) are de-energised and the module needs to be reset by taking the
power off and on after resolving the error cause.
•
APPLICATION AND INSTALLATION ERRORS are indicated by flashing internal LED "RUN1" and the muting lamp connected
to terminal 48. LED "RUN2" is permanently on.
The normally open safety contacts (13/14, 23/24, 33/34) are de-energised, but the module can be restarted pushing the start
push-button after resolving the error cause.
FATAL ERRORS
Error
code
LED
RUN
1
LED
RUN
2
Muting
lamp
(48)
Error
type
Possible causes
Corrective actions
0
Internal
module
error
Missing supply voltage
Internal module fault
Apply voltage to A1(+) and A2(-).
If the error is not resetable, contact
your nearest sales office for
assistance.
5
(1)
5
6
6
7
7
8
9-13
8
5
(1)
Mode
selector
error
Different modes selected
for channel 1 and
channel 2.
Not valid mode selection
Select identical modes for channel
1 and channel 2
Select valid mode (see mode
selection table)
Under-
voltage
error
Supply voltage is too low
(< -15% of nominal
voltage = 20,4 Vdc )
6
Over-
voltage
error
Supply voltage is too
high (> +15% of nominal
voltage = 27,6 Vdc )
Apply supply voltage within
specifications: 24 Vdc +/- 15% at
A1(+) and A2(-)
7
(1)
(1)
Input
error
Signals between
redundant safety device
inputs (S11-S14 or S21-
S24) are NOT applied
within 2,5 s.
Check correct functioning of safety device outputs.
Check for broken wires and short circuits
Check safety switches are actuated
within the time frame.
8
(1)
(1)
Relay
contact
error
Contacts of internal
safety relays K1 or K2
are damaged or welded
Ensure safety contacts 13/23 to 33/34 are properly
connected and not welded.
Ensure switched current is within specifications.
If the error is not resetable, contact your next sales
office for assistance.
9
10
11
12
13
9-13
(1)
(1)
Internal
module
error
Note the sequence leading to this error.
If the error is not resetable, contact your nearest
sales office for assistance.
Note (1): It is possible that
- LED "RUN1" and "RUN2" are indicating different error codes or,
- only one LED "RUN1" or "RUN2" is indicating an error code and the second LED "RUN1" or "RUN2" is switched off.
: switched off
: n-times flashing
n
: switched on