DISTRIBUTED I/O
EN0B-0090
12
Table 10. L
ON
M
ARK
Object NVs for the XFL524B.
NV Name
Type
Range
Description
nviValue
SNVT_switch
Receives the value for the output channel.
nvoFeedback
SNVT_switch
Transmits the feedback value of the Actuator Object. If
the manual override switch is set to auto, or if the
manual override module is not plugged in, the
feedback output reflects the value of nviValue. As
soon as the manual override switch is set to either
manual position, the Actuator Object adopts this
manual value. In this case, the nvoFeedback state
field will be 0xFF (invalid) and the value field will
contain the actuator position.
If the manual override switch is in the automatic posi-
tion, data is transmitted whenever nviValue is written.
If the manual override switch is in the manual position,
data is transmitted whenever the manual position is
changed.
nvoManCnt
SNVT_count
0 to 65535
Transmits the number of manual switching operations.
Each transition from the state auto/manual on/manual
off to any other statue is counted by incrementing this
NV.
nvoDiagnose
SNVT_count
0 to 65535
Counts the number of times the internal filter for
smoothing the signal from the manual override switch
board has been active.
UCPTSensorConfig
0 = not used
1 = binary (default)
Specifies whether an Actuator Object is processed or
not. If set to 0, the value is not updated.