DISTRIBUTED I/O
11
EN0B-0090
Digital Output Module XFL524B
•
Six isolated change-over contacts
•
Max. voltage U
max
= 230 Vac per output
•
Max. current I
max
= 2 A per output
•
LED per channel
OFF: LED off
ON: LED illuminated (yellow)
•
Green power LED (L1) and red L
ON
W
ORKS
status LED
(L2)
•
Cycle time 1 sec with CPU
•
Dimensions (WxLxH): 47x97x70 mm
The digital output module has six isolated change-over con-
tacts which can be connected to actuators or other switch-
able devices.
The unit plugs into the XSL514 Terminal Block and can be
inserted and removed without disturbing other units on the
bus. Terminals 1 through 18 are switched according to the
adjacent figure. Six LEDs are located on top of the module.
The module address is set using the rotary HEX switch.
Beginning with V2.04.00 Excel 500 controller firmware, the
online point attribute Normally Open / Normally Closed
(NO/NC) defines the relation between the physical state
(relay on/off) and its logical status. See Table 9.
NOTE:
The digital outputs can be used as status contacts
or as alarm contacts, depending upon how they are
defined in CARE. All outputs from a single module
must be used for the same purpose.
Table 9. Physical state and logical status as defined by
the point attribute NO/NC for the XFL524B.
Relay
On/Off
NO/NC
attribute
Logical
Status
Output
Voltage
LED
Status
On
NO
1
24V
On
Off
NO
0
0V
Off
On
NC
0
0V
Off
Off
NC
1
24V
On
Open Loop Actuator
Object Type #3
Mandatory
Network
Variables
input
NV 1
nviRequest
SNVT_obj_request
nv1
nviValue
SNVT_switch
Optional
Network
Variables
input
NV 1
nviRequest
SNVT_obj_request
nv1
nvoDiagnose
SNVT_count
1
1
input
NV 1
nviRequest
SNVT_obj_request
nv3
nvoFeedback
SNVT_switch
input
NV 1
nviRequest
SNVT_obj_request
nv1
nvoManCnt
SNVT_count
User-Defined
Network
Variables
input
NV 1
nviRequest
SNVT_obj_request
nc1
UCPTSensorConfig
Optional
Configuration
Properties
This output NV appears only once for the node.
Figure 7. L
ON
M
ARK
Object for each digital output.