Advanced Features

Photocell

The MLSM2000A incorporates a photocell which can be configured to operate in three different modes, selectable from within 
the product’s menus on the QuickSet Pro Programmer. These modes are ‘regulating’, passive’ and ‘none’. Note that in 

any

 

mode of operation, the photocell affects the light output only when the Entry Scene is set to Scene 1. 

Setting the regulating photocell

The MLSM2000A is set by default to operate in ‘regulating’ mode. Using the QuickSet Pro, enter the Utilities menu and select 
‘LightSpot/MLS/LCM’ then ‘Set Light Level’. Use the ‘up’ and ‘down’ buttons to manually adjust the light output from the 
luminaire(s) and when at the required level press and hold ‘OK’ to store. The luminaire(s) will blink to acknowledge a successful 
store operation. 

Setting the passive photocell

Use Passive mode in applications where light level regulation is not required (eg, when controlling non-dimmable ballasts) but 
it is desirable to hold off the controlled lighting when natural light is sufficient. 

The parameter 

‘Threshold’ 

on the QuickSet Pro menu is used to program the MLSM2000A’s passive photocell set point, 

which determines whether the lights will be allowed to turn on as an unoccupied area is entered. The threshold is programmed 
as a number between 1 (darkest) and 254 (brightest). This number is not scaled to correlate with ‘lux’ measurements made 
using a light meter, but nevertheless is a true representation of the light level perceived by the MLSM2000A. 

In order to assist with selection of the appropriate threshold setting, the light level currently perceived by the detector (in terms 
of a number between 1 and 254) can be viewed on the QuickSet screen briefly following a download operation. The number 
represents the light level immediately before the download operation took place. 

Tip: turn the lights off first using the 

IR 

Remote

  menu  found  in 

Utilities

  if  you  want  to  measure  the  perceived  ambient  light  level  with  no  contribution  from  the 

controlled lighting. 

Note: When setting the regulating light level as described in the previous section, the Threshold is also set to the current 
measured level. 

Commissioning

Detectors are supplied factory pre-set which ensures the lighting will switch on automatically as soon as power is 
applied.  Final commissioning of the detectors requires the use of the QuickSet Pro Programmer.  

Commissioning Detectors using the QuickSet Pro Programmer

It is important that the Programmer be held perpendicular between 0.5m and 2m from the sensor.

1.  Switch on by pressing any button (and unlock with top left rectangular button).

2.   Point the programmer at detector and press the  DOWNLOAD button.   The programmer will confirm the 

product’s identity and call up the correct menu of parameters and their current settings.

3.  Use a combination of UP, DOWN, FORWARD and BACK buttons to navigate the parameter menu, selecting 

options for each shown. 

4.  When options for all parameters have been selected, point the programmer at the detector and press the 

UPLOAD button.  The luminaire(s) will switch off briefly during the programming process.

5.  After a short period of inactivity (default 5 minutes), the programmer hibernates retaining the most recent 

settings.

  

OneSwitch Dimming

OneSwitch dimming affords local control to the end-user whereby a simple, momentary, push-to-make wallswitch 
can be used to raise or lower the lighting level or to toggle the output ON/OFF. A press of less than 1 second will 
toggle the output status while a longer press will raise or lower the output. Each time the switch is pressed, the 
direction of dimming reverses. If the switch has not been pressed for 5 seconds, the direction will be up (brighter) - 
unless the output is already above 90% in which case the direction is down.  A wiring diagram is shown left.

To Test with HC5A Hand-held Controller

Once the MLS Luminaire Controllers have been installed within the luminaires, the HC5A may be used to dim and 
brighten luminaires and to switch them ON and OFF.  One of 6 different lighting scenes can also be recalled.

Содержание Ex-Or MLSM2000A

Страница 1: ...rollers MLSM2000A Control Module DHW DHS Mini Detector Head for use with Analogue 1 10V and Fixed Output Electronic High frequency Ballasts Installation and Commissioning Instructions Note QuickSet Pro required for commissioning ...

Страница 2: ...ust be no direct illumination 4 In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from neighbouring luminaires not under its control This is particularly important when planning the installed layout of linear luminaires that have an integral detector positioned...

Страница 3: ...eived ambient light level with no contribution from the controlled lighting Note When setting the regulating light level as described in the previous section the Threshold is also set to the current measured level Commissioning Detectors are supplied factory pre set which ensures the lighting will switch on automatically as soon as power is applied Final commissioning of the detectors requires the...

Страница 4: ...perative that the MLS bus is wired with the correct type of cable normally it should be 1 5mm unscreened twisted pair Please read ApplicationNoteAN4001 for more details 6 Due to the fact that the photocell is on the ceiling looking down it is not possible for measurementsmade with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a d...

Отзывы: