Technical Data 

2

MLS CABLE: 1.5mm  unscreened twisted-pair: see Application Note AN4001

MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m

RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)

o

ta = 0 - 50 C

CAPACITY: 

Total load must not exceed

 

2 AMPS, up to 4 Ballasts MAX

                    

Electronic, high-frequency ballasts ONLY

o

INTERCONNECT CABLE TEMPERATURE RATING: 60 C 

  

COLOUR: White RAL9010 or silver bezel (DHW = White, DHS = Silver) 

MATERIAL: UV stabilised polycarbonate (DHW/DHS)

                   Flame retardant PC/ABS (MLSM2000A)

IP RATING: 20

OVERALL DIMENSIONS: 32 (l) x 21.5 (w) x 21.3 (h) mm (DHW/DHS)

 

          

 

147.5 (l) x 30 (w) x 22 (h) mm (MLSM2000A)

WEIGHT: 32g (DHW/DHS)

                48g (MSM2000A)

W4205

I

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

6.0m

2.5m

Important Additional Notes

1. 

A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.

2. 

The dimming control output should be connected only to the control input of the ballasts - never to other detectors.

3. 

This equipment should be used to control only those ballasts powered from the same phase as the detector.

4. 

Do not connect mains to the MLS bus.

2

5. 

It is imperative that the MLS bus is wired with the correct type of cable; normally it should be 1.5mm  unscreened twisted pair.   Please read 
Application Note AN4001 for more details.

6. 

Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on the working plane 
to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.  Therefore, products of this type should be 
regarded as capable of maintaining an APPROXIMATE light level only.

7.     This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of some lighting types 

(e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve a predicted lamp life.   Please check with the 
manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect. 

8. 

Some devices in this product range feature a silvered surface finish; this is intended for decorative purposes only

.   Care should be taken to 

avoid accidental separation of the silvered coating from the product.  If   the unit is built into a luminaire that is subsequently wrapped in film 
having adhesive properties, it is recommended that a layer of suitable packaging material be used to protect the silvered area.

Honeywell Ex-Or

St. Marks Court, North Street, 
Horsham, West Sussex, RH12 1BW, UK 
Tel: +44 (0)1942 719229 
Fax: +44 (0)1942 508753
Email: [email protected]
www.ex-or.com

Содержание Ex-Or MLSM2000A

Страница 1: ...rollers MLSM2000A Control Module DHW DHS Mini Detector Head for use with Analogue 1 10V and Fixed Output Electronic High frequency Ballasts Installation and Commissioning Instructions Note QuickSet Pro required for commissioning ...

Страница 2: ...ust be no direct illumination 4 In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from neighbouring luminaires not under its control This is particularly important when planning the installed layout of linear luminaires that have an integral detector positioned...

Страница 3: ...eived ambient light level with no contribution from the controlled lighting Note When setting the regulating light level as described in the previous section the Threshold is also set to the current measured level Commissioning Detectors are supplied factory pre set which ensures the lighting will switch on automatically as soon as power is applied Final commissioning of the detectors requires the...

Страница 4: ...perative that the MLS bus is wired with the correct type of cable normally it should be 1 5mm unscreened twisted pair Please read ApplicationNoteAN4001 for more details 6 Due to the fact that the photocell is on the ceiling looking down it is not possible for measurementsmade with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a d...

Отзывы: