background image

Technical Data

 

MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m 

RANGE: Approx 7m dia at 2.4m ceiling height

OFF DELAY: 1 minute - 96 hours/Disabled plus 10-second Walk-test Mode

PHOTOCELL: Passive/Active/Regulating adjustable 50-5000 lux

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)

PRODUCT RATING AND RECOMMENDED CIRCUIT PROTECTION: 10 Amps

MAXIMUM RECOMMENDED LOAD (VOLT-FREE): 6 Amps

MAXIMUM RECOMMENDED LOAD (ANALOGUE 1-10V): 20 Ballasts

DIMMING OUTPUT: Analogue 1-10V

COLOUR: White

MATERIAL: Flame retardant PC/ABS

WEIGHT: 300g

IP RATING: 2X

Ex-Or 

Novar ED&S Limited
Haydock Lane, Haydock, 
Merseyside WA11 9UJ

Tel: +44 (0)1942 719229 
Fax: +44 (0)1942 508753  
Email: [email protected]
www.ex-or.com

100mm

100mm

Dimensions

62mm

deep

62mm deep

behind ceiling

MS2421AF

MS2421ASM

Flange:

15mm deep

Important Additional Notes

1.

All terminals on this product are provided for final connections.  It is not intended that the product be used as a junction box for looping cables. 

2.

A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.

3.

Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains with regard to wiring practice.  
The 0V line of the dimming output is almost at Neutral potential.

4.

The dimming control output should be connected only to the control input of the ballasts - never to other detectors.

5.

Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on the working plane to remain 
constant when daylight illuminates the ceiling and the working plane to a differing extent.  Therefore, products of this type should be regarded as capable 
of maintaining an APPROXIMATE light level only.

6.    This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of some lighting types (e.g. ‘2D’ 

luminaires) may specify a maximum number of switching cycles in order to achieve a predicted lamp life.   Please check with the manufacturer of the 
luminaires to ensure that they are compatible with automatic controls in this respect. 

7.  The detectors are extremely sensitive to movement; they must be mounted on a solid surface which has no movement whatsoever. 
8.     This equipment should be used to control only those ballasts powered from the same phase as the detector.

W4475D

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Содержание Ex-Or LightSpot Gold Series

Страница 1: ...Installation and Commissioning Instructions Note HP2000 required for commissioning Gold Series LightSpot for use with Analogue 1 10V ballasts MS2421A MS2421ASM MS2421AF ...

Страница 2: ...the PCELL RLY action should be set to DISABLED and the lights will be on continuously during periods of occupancy The Analogue 1 10V output dims the ballast s in the luminaires It always tries to maintain a programmed light level on the working plane It aims for the level stored in the parameter Set point Low Sometimes it is convenient to limit the extent to which the presence detector with photoc...

Страница 3: ...ght level falls below Set point Low during a period of occupancy then the lights are switched on immediately without any delay Programming the Set points 1 Simple PCELLRLYSwitching Control i If PCELL RLY ACTIVE switching action is required it is important that the lights are switched on at least 15 minutes before this procedure is undertaken to allow the tubes to reach full output For PCELL RLY PA...

Страница 4: ...respect as mains with regard to wiring practice The 0V line of the dimming output is almost at Neutral potential 4 The dimming control output should be connected only to the control input of the ballasts never to other detectors 5 Due to the fact that the photocell is on the ceiling looking down it is not possible for measurements made with a lux meter on the working plane to remain constant when ...

Отзывы: