User Overrides

The end-user can configure a number of lighting scenes that can be recalled 
using a hand-held override. With an HC5 hand-held controller lighting can be 
overridden OFF or ON, or a set level can be chosen. Regulating and switched 
loads  can  be  adjusted  independently  through  a  combination  of  OneSwitch 
Dimming and the HC5 Hand-held Controller. 

W4475D

Output

1-10V

+

-

MS2421A

Using OneSwitch, Switched and 

Analogue Outputs

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

LIVE

NEUTRAL

EARTH

Analogue Ballast

(MAX 6 AMPS)

ONESWITCH
DIMMING

Analogue output

Momentary
push-to-make
switch

Wiring Examples

1-10V

Output

+

-

MS2421A

Using Switched Output only

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

LIVE

NEUTRAL

EARTH

LOAD

(MAX 6 AMPS)

ONESWITCH
DIMMING

NC

LOAD

(Max 6 Amps)

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

VOLT-
FREE 
OUTPUT

LIVE IN

LIVE IN

NEUTRAL

NEUTRAL

EARTH

EARTH

Any connection not shown is NO CONNECTION

ONE

SWITCH

NC

NC

ONE

SWITCH

Relay outputs may be connected together in parallel to cover larger areas, 
however the total load on all combined relay outputs must not exceed 6 Amps. 

Momentary
push-to-make
switch

DO NOT CONNECT DIMMING OUTPUTS TOGETHER .

photocell reading has been stored in the Set-point Low parameter. This is the 
control  set-point  for  the  regulating  process  which  tries  to  maintain  this 
photocell reading at all times by dimming or brightening the lights.

Switching the Lighting Load:

In addition to dimming the lighting load via the 1-10V output, the load can also 
be controlled by the relay according to natuiral light level.This form of control is 
governed by the setting of the parameter PCELL RLY. There are three options 
for this parameter:-

 

DISABLED:

 In his mode the photocell has no effect upon the operation of the 

relay - it will switch only according to detected occupancy.

PASSIVE:

 In this mode the relay will be inhibited from closing if the area is 

entered  when  the  ambient  light  level  is  above  Set-point  Low.  If  during  the 
period of occupancy, the light level falls below Set-point Low, then the lights will 
switch  on.  In  this  mode  the  lights  will  never  switch  off  during  a  period  of 
occupancy - no matter how bright it becomes.

ACTIVE: 

This is the same as PASSIVE mode except that, additionally, the 

lights will switch off if the light level exceeds Set-point High even if the area is 
occupied. For the switch-off to occur, the light level must persist at this high 
level for the full duration of what is called a "Passing Cloud Timer" (PCT). The 
PCT is usually of the same duration as the Off-delay used by the Presence 
Detection logic; however when an unusually long Off-delay is configured the 
PCT is automatically capped at 20 minutes. If the light level falls below Set-
point  Low  during  a  period  of  occupancy,  then  the  lights  are  switched  on 
immediately without any delay.

 

Programming the Set-points:
 
1) Simple PCELL RLY Switching Control:

i) If PCELL RLY-ACTIVE switching action is required it is important that the 
lights are switched on at least 15 minutes before this procedure is undertaken 
to allow the tubes to reach full output. For PCELL RLY-PASSIVE   switching 
action this is not necessary.

ii)  Download  the  settings  already  established  within  the  Detector  for  non-
Photocell related features to the HP2000. Edit the Photocell setting to ACTIVE 
or PASSIVE as required. Upload the whole configuration to Detector.

iii)Wait until the appropriate time of day for, or use blinds to create, the natural 
light level, as measured with a light meter, below which you 

would 

want the 

lights to be on and above which you 

would not

 want the lights to be on.

iv) Start the internal self-programming operation by selecting UTILITIES/SET 
LIGHT LEVEL on the HP2000 and pressing and holding the "OK" button. The 
Detector  takes  a  Photocell  reading,  adds  a  small  margin  and  stores  the 
resulting value as Set-point High. It then switches off the controlled lights and 
takes another Photocell reading which it stores as Set-point Low. The lights 
are now switched on again, completing the acknowledgement "blink". The OK 
button can now be released. Note that the difference between the two Set-
point values, the Switching Hysteresis, is equal to the contribution to total light 
made by the controlled luminaires. This is the ideal amount of hysteresis to 
prevent oscillation without compromising control accuracy.

NC

NC

 

2) Regulating Control overlaid by PCELL RLY Switching Control

First carry out the commissioning procedure described for 

Regulating Only

 

control  (under  Photocell  Commissioning).  When  the 

Regulating  Only

 

commissioning procedure has been carried out the HP2000 parameter Set-
point Low within the Detector has acquired a new, non-default value. This value 
should be read in a full download from the Detector to the HP2000 and retained. 

The Set-point High value should now be manually edited on the HP2000 screen 
to be about 25% higher in the same units, e.g. if a download from the Detector 
to the HP2000 shows that 429 has been automatically stored into the Set-point 
Low parameter, then the Set-point High value should be manually edited to 535 
or 536. The PCELL RLY action should be set to “ACTIVE” or “PASSIVE”, as 
required, and the whole configuration then uploaded to the Detector.

2 x MS2421A

In Parallel, using Switched 

Output only

Please note that the Earth terminal 
has no internal connection and is 
used for termination only. 

Please note that the Earth terminal 
has no internal connection and is 
used for termination only. 

Lights ON =

Lights OFF =

Set-point High

Set-point Low

Natural
Light 
Level

Duration of 

PCT

Active Mode

Passive Mode

Occupancy

Area Occupied =

Area Unoccupied =

Содержание Ex-Or LightSpot Gold Series

Страница 1: ...Installation and Commissioning Instructions Note HP2000 required for commissioning Gold Series LightSpot for use with Analogue 1 10V ballasts MS2421A MS2421ASM MS2421AF ...

Страница 2: ...the PCELL RLY action should be set to DISABLED and the lights will be on continuously during periods of occupancy The Analogue 1 10V output dims the ballast s in the luminaires It always tries to maintain a programmed light level on the working plane It aims for the level stored in the parameter Set point Low Sometimes it is convenient to limit the extent to which the presence detector with photoc...

Страница 3: ...ght level falls below Set point Low during a period of occupancy then the lights are switched on immediately without any delay Programming the Set points 1 Simple PCELLRLYSwitching Control i If PCELL RLY ACTIVE switching action is required it is important that the lights are switched on at least 15 minutes before this procedure is undertaken to allow the tubes to reach full output For PCELL RLY PA...

Страница 4: ...respect as mains with regard to wiring practice The 0V line of the dimming output is almost at Neutral potential 4 The dimming control output should be connected only to the control input of the ballasts never to other detectors 5 Due to the fact that the photocell is on the ceiling looking down it is not possible for measurements made with a lux meter on the working plane to remain constant when ...

Отзывы: