Outstation Wiring 

The compact unit requires programming to determine the outstation configuration; 

Four types of handset are allowed on the system, type A (fixed phone) type B (hands-free refuge points), disabled toilet alarms and 
jack plates. 

For jack points a 10K EOL resistor is required at the OUT of the last plate on the line.  

 

Cable Guidance for Compact Unit and Outstations 

Following the publication of BS5839pt9:2011, the guidance on cables for the Compact unit has changed, following a 
relaxation in the requirements of the standard. 
 

Type A Outstations 

Any system with fire fighting telephones (Type A outstations) must have all wiring to these outstations and any necessary network 
cables interconnecting parts of the system in Enhanced fire rated cables. 
 

Type B Outstations 

In buildings under 30 metres in height, or any building with sprinklers fitted, the wiring of Type B (hands-free) disabled refuge points 
may be in standard fire rated cable as long as the planned evacuation will be completed within 30 minutes.  If the building is over 
30metres in height without sprinklers, or where the evacuation will take place over multiple stages exceeding 30 minutes, enhanced 
fire rated cables must be used. 
 

Disabled toilet call points 

The revised BS5839pt9:2011 now recognises the addition of disabled toilet call systems to the Compact unit, however 
gives no guidance on their use, as this is in Building Regulations Approved Document M. 

There is no requirement for these systems to be monitored or battery backed.  However with the EVCS-TA toilet extension we 
have included these features as standard. The only cable requirement may come from the building design statement, and typically 
this will require low smoke and fume cables (LSF), although they can also be wired in standard fire rated cable for ease of 
identification. 
 

Combined Systems 

When a system consists of a mix of Type A and Type B outstations, the wiring must be enhanced fire rated for any shared resource 
such as network cables, but individual spurs to type B outstations can be wired in standard fire rated cable as long as the distance 
covered by that cable does not exceed 30 metres vertically in non-sprinklered buildings, or the evacuation plan for this segment of 
the building will not exceed 30 minutes. 
 

General Guidance 

In complex buildings or where systems are being quoted without access to the fire evacuation plan we recommend all wiring to be 
enhanced, or suitable caveats and detailed assumptions are placed on the design certificate required by BS5839pt9:2011.  

 
 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание EVCS-CMPT9

Страница 1: ...EVCS CMPT9 Compact Master EVCS XC10 Slave Exchange Installation Commissioning and Maintenance Manual www acornfiresecurity com www acornfiresecurity com ...

Страница 2: ...oved Document B for all non domestic dwellings Building Regulations Approved Document B also requires all buildings where the public or disabled staff gain access to any floor other than the ground floor using lifts or stairs are required to exit Product Overview A Compact 9 unit comprises of two functional blocks the master handset and outstations type A type B duo jack points or disabled toilet ...

Страница 3: ...l all units are on the same mains phase as they are classified TEN 230V powering from different phases can mean a 440V potential can be present in a unit during a major fault incident Anti static handling guidelines Make sure that electro static handling precautions are taken immediately before handling PCBs and other static sensitive components Before handling any static sensitive items operators...

Страница 4: ...ins fuse b 2 5mm AF ALN key Using the ALN key supplied open the right hand front cover Verify the following items are present 1 9 off outstation line connectors 2 1 off 2 way fault connector 3 1 off 2 way in use connector 4 1 off 2 way access connector 5 1 off 4 way network connector If there are any Items missing please contact Honeywell quoting the unit serial number and the name on the packing ...

Страница 5: ...cessory pack with the following contents a Spare mains fuse b 2 5mm AF ALN key Using the ALN key supplied open the front cover Verify the following items are present 1 10 off outstation line connectors 2 1 off 4 way network connector If there are any items missing please contact Honeywell quoting the unit serial number and the name on the packing list enclosed so we can rectify the situation www a...

Страница 6: ...g will be brought into the panel and remove the required knockouts for cable entry If a knockout is removed fill the hole with a good quality cable gland On the bottom face a single knockout is for the incoming mains Mains SHOULD NOT enter the box by any other hole If additional holes are required then the can be drilled as shown below taking care not to obscure the battery or PCB locations Unused...

Страница 7: ... should be installed to meet the appropriate parts of BS5839 9 2011 and BS 7671 Wiring Regulations Other national standards of installation should be adhered to where applicable Do not test wiring with an insulation tester Megger with any equipment or outstations connected as the 500 Volt test voltage will destroy these devices totally You must observe local wiring regulations Do not run SELV and ...

Страница 8: ...afety Information Sealed Lead acid batteries contain sulphuric acid which can cause burns if exposed to the skin The low internal resistance of these batteries means large currents will flow if they are accidentally short circuited causing burns and a risk of fire exercise caution when handling batteries Power up Procedure Always apply mains power before connecting batteries Do not commission the ...

Страница 9: ...st be used Disabled toilet call points The revised BS5839pt9 2011 now recognises the addition of disabled toilet call systems to the Compact unit however gives no guidance on their use as this is in Building Regulations Approved Document M There is no requirement for these systems to be monitored or battery backed However with the EVCS TA toilet extension we have included these features as standar...

Страница 10: ...9 Handsets Type A Hands Free Refuge Point Type B Disabled Toilet Alarm Master to Slave Connection www acornfiresecurity com www acornfiresecurity com ...

Страница 11: ...ls 2ND Fix Replace the front panel door plate by attaching the ribbon cable lead and fixing with the door hinges Attach all plugs ensuring they fit squarely into the connectors Do not connect battery until the master has been powered up on mains Powering UP Carefully check the outstation wiring then apply AC power to each Compact master unit DO NOT commission on batteries as the power supply has a...

Страница 12: ...vels of accessibility User Manager and Engineer User level is accessible to all Manager level is accessible to those who log in as Manager or Engineer Engineer level is accessible to those who log in as Engineer To access the menus from the Status Screen Menu press the TICK button Note If panel is installed in a public area then all operations will be restricted to Manager or Engineer only except ...

Страница 13: ... EVCS CMPT9 press the TICK button to show the log in screen Compact M9 Back Login View current fault The log in screen will prompt the user to enter a PIN The default Engineer PIN is 0000 Use the navigation keys to choose the correct number and then press TICK to move to the next number Repeat until the PIN is entered Enter PIN to LOG IN 0 A list of possible menu options is presented Log out will ...

Страница 14: ...ing outstation 4 10 56 02 01 01 11 Scroll through the root menu using the navigation keys until View fault log is selected Press TICK to enter the View fault log menu Use the navigation keys to scroll through the faults pressing exits View Event Log This menu is an information only menu It displays the last 99 events that have occurred recording the type of event and the date and time the event oc...

Страница 15: ...r Minute Second The cursor will be on the first option Day Use the navigation keys to select the correct day then press TICK to move to the Month option Repeat until the current date and time are set and the next option is selected Most configuration menus will have the same options located in the bottom right of the LCD screen Next Save and Quit Pressing the TICK button selects the option chosen ...

Страница 16: ...sired then press TICK Both Save and Quit will go back to the root menu Change Engineer PIN The default Engineer PIN to access the configuration menus is 0000 but this can be changed Scroll through the root menu using the navigation keys until Change engineer PIN is selected Press TICK to show the Change engineer PIN menu There are 2 lines New PIN and Repeat PIN The cursor will be on the first digi...

Страница 17: ...ICK Next Moves cursor back to show log option Exec Executes command to clear log if clear log option is set to yes and moves back to root menu Quit Moves back to root menu Panel Settings Depending upon location of install the buzzer can operate in different modes and the access level used to operate the panel can be set Panel settings Next Buzzer mode Faulty User flt accept No User access No The b...

Страница 18: ...desired then press TICK Both Save and Quit will go back to the root menu Relay Settings The In use relay has multiple settings None In use Connected or Ignored None the relay is ignored In Use the relay closes when any outstation is activated This is the default setting Connected the relay closes when the master handset establishes a conversation with an outstation Ignored the relay closes if the ...

Страница 19: ... batteries have just been added or changed Battery test Mains OK Batt OK Action Quit Press up or down to toggle between Quit and Retest Press TICK to select that action Define Outstation This menu option will set all outstations to present This does not permanently save all outstations as present This is used for testing purposes only Define all handsets Master No Slave No Next Outstation Ring Thi...

Страница 20: ...outstation type None no outstation Phone Type A handset Refuge Type B handsfree handset Pullcord disabled toilet alarm If an outstation is defined as a Pullcord the master will emit a continuous tone if the toilet alarm is activated This tone will cease when the master handset goes off hook No call can be established with the toilet alarm Set Name M9 outstation 1 Name Extension 1 Next Use the navi...

Страница 21: ...ation keys to select the node ID for this master unit and press TICK to move to the next option We must now tell the system how many M9 s should be present on the system Network Settings Supervisor present Master present Scroll to the supervisor addresses option and press TICK Supervisor present 1 Y 2 N 3 N 4 N Next Using the up and down keys to toggle yes or no and the TICK key to move to the nex...

Страница 22: ...ssing the TICK key The tone will remain silent for 4 minutes whereupon it will recommence This tone signifies that the toilet alarm has been activated and it can occur simultaneously with the Master Handset ringing due to an incoming call from a Type A or Type B handset Making a Call Lift the handset on the master handset then press the key to scroll the display to the directory page If user acces...

Страница 23: ... until all points are tested Record results in the site log Monthly Test one outstation by lifting the handset followed by the master calling that outstation Record results in the site log Quarterly Engineer call to check system operation Yearly Engineer call to check system operation and check battery health 5 Yearly Engineer call to check system operation and replace the batteries www acornfires...

Страница 24: ...23 Technical Specification www acornfiresecurity com www acornfiresecurity com ...

Страница 25: ...PR211 183 510 01 PINSTEVCSCMPT9 www acornfiresecurity com www acornfiresecurity com ...