NFS Supra
Page 41
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
5.4.5 Digital Input
The digital input of the control panel activates by close contact (by default) or open contact
(Configurable option). When the contact is closed/opened between digital input terminals
(DIGITAL IN), the following functions are supported by the control panel:
Digital input configuration:
Select by pressing
KEYPAD ACCESS
=ON
The cyclic change of the function is made by pressing the
RESET
key.
Led 1 Alarm (Red)
= ON
Reset
(By default)
Led 2 Disablement (Yellow)
= ON
Evacuate
Led 3 Test (Yellow)
= ON
Sounders and Buzzer mute
Led 4 Power (Green)
= ON
Delays on/off
Led 5 General Fault (Yellow) = ON
Buzzer Mute
Digital input activates by close contact (by default) (when closes activates)
Digital input activation selection NO/NC:
Select by pressing keys
(
KEYPAD ACCESS
=ON +
SILENCE/RESOUND
=ON
)
The cyclic change of the function is made by pressing the
RESET
key.
Led 1 Alarm (Red)
= ON; activates by
NC
contact
Led 2 Disablement (Yellow)
= ON; Activates by
NO contact
(By default)
Reset push-button:
Change Option
(Access level 3 - Configuration)
Digital input
function
change
Reset push-button:
Change Option
(Access level 3 - Configuration)
Change
option
Configuration