Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
5.4.2 Delay 1 (Primary Delay
– Alarm acknowledge)
Delay 1
: Maximum time to press
MUTE BUZZER
key in order to acknowledge (accept) the
alarm start Delay 2
.
If the MUTE
BUZZER key is not pressed, sounders will be activated when
delay
1 time is finished. It is possible to configure a period of time from 0 seconds (only delay 2
is performed) to 300 seconds (5 minutes) at 30-second intervals.
Delay 1 configuration:
Press the
MUTE BUZZER
=ON
push-button. Then press
RESET
push-button to change
cyclically the led that has to be on and, consequently, to change the period of time.
No leds on
= OFF=
0s
only Delay 2 if configured (by default)
Led 1 Alarm (Red)
= ON =
30 sec.
Led 2 Disablement (Yellow)
= ON =
60 sec.
Led 3 Test (Yellow)
= ON =
90 sec.
Led 4 Power (Green)
= ON =
120 sec.
Led 5 General Fault (Yellow)
= ON =
150 sec.
Led 6 Earth Fault (Yellow)
= ON =
180 sec.
Led 7 Sounders fault/Disabled (Yellow) = ON =
210 sec.
Led 8 Power Supply (Yellow)
= ON =
240 sec.
Led 9 Auxiliary P.Supply F.(Yellow)
= ON =
270 sec.
Led 10 System Fault (Yellow)
= ON =
300 sec
.
Reset Push-button:
Change Option
(Access level 3 - Configuration)
At level 1 or 2, DELAY
ON/OFF
push-button can be pressed in order to cancel
operating delays.
The sounder and relay cards outputs operation depends on the control matrix.
Configuration