EC7823A;RM7823A 7800 SERIES RELAY MODULES

66-1086—2

4

Fig. 2. Wiring subbase for EC/RM7823A.

7.

Recommended wire routing of leadwires:

a. Do not run high voltage ignition transformer wires 

in the same conduit with the flame detector.

b. Do not route flame detector leadwires in conduit 

with line voltage circuits.

c. Enclose flame detector leadwires without armor 

cable in metal cable or conduit. 

d. Follow directions in flame detector instructions.

8.

 Maximum wire lengths:

a. EC/RM7823A leadwires: The maximum leadwire 

length is 300 feet to terminal inputs. 

b. Flame Detector leadwires: The maximum flame 

sensor leadwire length is limited by the flame 

signal strength.

9.

Make sure loads do not exceed the terminal ratings. 

Refer to the label on the EC/RM7823A or to the ratings 

in Tables 3 and 4.

Final Wiring Check

1.

Check the power supply circuit. The voltage and 

frequency tolerance must match those of the 

EC/RM7823A. A separate power supply circuit may 

be required for the EC/RM7823A. Add the required 

disconnect means and overload protection. 

2.

Check all wiring circuits and complete the Static 

Checkout in Table 5 before installing the EC/RM7823A 

on the subbase. 

3.

Install all electrical connectors. 

4.

Restore panel power. 

M15080GR 

G

L2

3

4

5

6

7

8

9

10

F

(L1)

13

14

15

16

17

18

19

20

21

22

12

MASTER

SWITCH

NORMALLY 

CLOSED

NORMALLY 

OPEN

COMMON

FLAME DETECTOR

120V, 50/60 Hz (RM7823); 220-240V, 50/60 Hz (EC7823) POWER SUPPLY.  PROVIDE 

 DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS

OUTPUTS SHOWN ARE WHEN THE DEVICE DOES NOT SEE FLAME.

SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS FOR CORRECT WIRING.

NOTE: FOR EC7823, A 220/240V TO 120V, 10VA, STEP-DOWN TRANSFORMER IS REQUIRED.

L1 

(HOT)
L2

1

1

Q7800

2

2

NORMALLY 

CLOSED

NORMALLY 

OPEN

COMMON

4

4

3

3

3

Содержание EC7823A

Страница 1: ...Ratings see Table 3 Voltage and Frequency EC7823A 220 240 Vac 10 15 50 60 Hz 10 RM7823A 120 Vac 10 15 50 60 Hz 10 Power Dissipation 10W maximum Maximum Total Connected Load 2000 VA Fusing Total Connected Load 15A type SC Fast Blow or equivalent Environmental Ratings Ambient Temperature Operating 40 F to 140 F 40 C to 60 C Storage 40 F to 150 F 40 C to 66 C Humidity 85 relative humidity continuous ...

Страница 2: ...ired to correct this interference 9 This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications Location Humidity Install the relay module where the relative humidity never reaches the saturation point The relay module is designed to operate in a maximum 85 relative humidi...

Страница 3: ...ures for given application TTW60C THW75C THHN90C Ground Type Recommended Practice Earth ground subbase and relay module 1 Use to provide a connection between the subbase and the control panel of the equipment Earth ground must be capable of conducting enough current to blow the 15A fast acting fuse or breaker in the event of an internal short circuit 2 Use wide straps or brackets to provide minimu...

Страница 4: ... Wiring Check 1 Check the power supply circuit The voltage and frequency tolerance must match those of the EC RM7823A A separate power supply circuit may be required for the EC RM7823A Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout in Table 5 before installing the EC RM7823A on the subbase 3 Install all electrical connectors 4...

Страница 5: ... 10 9KA2 N C 1A Pilot Duty at 120 Vac F 11 Flame Sensor 60 to 220 Vac current limited 12 Unused 13 9KB Common 14 9KB1 N C 1A Pilot Duty at 120 Vac also rated for 5V control circuits 15 9KB2 N O 1A Pilot Duty at 120 Vac also rated for 5V control circuits 16 21 Unused 22 Shutter 120 Vac 0 5A Terminal Number Description Ratingsa G Flame Sensor Grounda Earth G Earth Grounda L2 N Line Voltage Common 3 ...

Страница 6: ... signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts IMPORTANT The EC RM7823A must be installed with a plug in motion rather than a hinge action 4 Mount the EC RM7823A by aligning the four L shaped corner guides and knife blade termi...

Страница 7: ...use serious injury death or equipment damage 1 Close all manual fuel shutoff valve s before starting these tests 2 Use extreme care while testing the system Line voltage is present on most terminal connections when power is on 3 Open the master switch before installing or removing a jumper on the subbase 4 Before continuing to the next test be sure to remove test jumper s used in the previous test...

Страница 8: ...damaged or incorrectly sized wires and tighten any loose terminal screws 10 Replace faulty controllers limits interlocks actuators valves transformers motors and other devices as required 11 Make sure normal operation is obtained for each required test before continuing the checkout 12 After completing each test be sure to remove the test jumper s WARNING Explosion hazard Can cause serious injury ...