Honeywell EC7823A Скачать руководство пользователя страница 2

EC7823A;RM7823A 7800 SERIES RELAY MODULES

66-1086—2

2

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condition.

2.

Check the ratings given in the instructions and marked 

on the product to make sure the product is suitable for 

the application.

3.

Installer must be a trained, experienced, flame 

safeguard service technician.

4.

After installation is complete, check out the product 

operation as provided in these instructions.

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury or 

death.

To prevent possible hazardous burner operation, verify 

safety requirements each time a control is installed on 

a burner. 

WARNING

Electrical Shock Hazard/Equipment Damage 

Hazard.

Can cause severe injury, death or property 

damage.

 Disconnect the power supply before beginning 

installation. More than one power supply disconnect 

may be required.

IMPORTANT

1. Wiring connections for the relay modules are unique; 

refer to Fig. 2 or the correct Specifications for proper 

subbase wiring. 

2. Wiring must comply with all applicable codes, 

ordinances and regulations.

3. Wiring must comply with NEC Class 1 (Line Voltage) 

wiring.

4. Loads connected to the EC/RM7823A must not 

exceed those listed on the EC/RM7823A label or the 

Specifications; see Table 3 or 4.

5. All external timers must be listed or 

component-recognized by authorities who have 

proper jurisdiction.

6. For on-off gas-fired systems, some authorities who 

have jurisdiction prohibit the wiring of any limit or 

operating contacts in series between the flame 

safeguard control and the main fuel valve(s).

7. Two flame detectors can be connected in parallel 

with the exception of Infrared Flame Detectors 

(C7015).

8. This equipment generates, uses and can radiate 

radio frequency energy and, if not installed and used 

in accordance with the instructions, can cause 

interference with radio communications. It has been 

tested and found to comply with the limits for a Class 

B computing device of Part 15 of FCC rules which 

are designed to provide reasonable protection 

against such interference when operated in a 

commercial environment. Operation of this 

equipment in a residential area may cause 

interference; in which case, the users at their own 

expense may be required to take whatever 

measures are required to correct this interference. 

9. This digital apparatus does not exceed the Class B 

limits for radio noise for digital apparatus set out in 

the Radio Interference Regulations of the Canadian 

Department of Communications. 

Location

Humidity

Install the relay module where the relative humidity never 

reaches the saturation point. The relay module is designed to 

operate in a maximum 85% relative humidity continuous, 

noncondensing, moisture environment. Condensing moisture 

can cause a safety shutdown. 

Vibration

Do not install the relay module where it could be subjected to 

vibration in excess of 0.5G continuous maximum vibration.

Weather

The relay module is not designed to be weather tight. When 

installed outdoors, the relay module must be protected by an 

approved weather-tight enclosure.

Mounting Q7800 Wiring Subbase

1.

Mount the Q7800 Subbase in any position except 

horizontally with the bifurcated contacts pointing down. 

The standard vertical position or with the bifurcated 

contacts point up is recommended. Any other position 

decreases the maximum ambient temperature rating. 

2.

Select a location on a wall, burner or electrical panel. 

The wiring subbase can be mounted directly in the 

control cabinet. Be sure to allow adequate clearance 

for servicing, installation, access or removal of the 

EC/RM7823A, dust cover, flame amplifier, flame 

amplifier voltage probes, electrical signal voltage probes 

and electrical field connections. 

3.

For surface mounting, use the back of the subbase as a 

template to mark the four screw locations. Drill the pilot 

holes. 

4.

Securely mount the subbase using four no. 6 screws 

(not provided).

Wiring Subbase

WARNING

Electrical Shock Hazard.

Can cause serious injury, death or equipment/

control damage.

Disconnect the power supply before beginning 

installation. More than one power supply disconnect 

may be required.

1.

For proper subbase wiring, refer to Figs. 2, 3, 4 or 5.

2.

For proper remote wiring of the Keyboard Display 

Module, refer to the Specifications for the Keyboard 

Display Module (65-0090), Network Interface Unit 

(63-2278), Data ControlBus Module™ (65-0091) or 

Extension Cable Assembly (65-0131).

3.

Disconnect the power supply from the main disconnect 

before beginning installation to prevent electrical shock 

and equipment damage. More than one disconnect may 

be required. 

4.

All wiring must comply with all applicable electrical 

codes, ordinances and regulations. Wiring must comply 

with NEC, Class 1 (Line Voltage) wiring.

5.

For recommended wire size and type, see Table 1.

6.

For recommended grounding practices, see Table 2.

Содержание EC7823A

Страница 1: ...Ratings see Table 3 Voltage and Frequency EC7823A 220 240 Vac 10 15 50 60 Hz 10 RM7823A 120 Vac 10 15 50 60 Hz 10 Power Dissipation 10W maximum Maximum Total Connected Load 2000 VA Fusing Total Connected Load 15A type SC Fast Blow or equivalent Environmental Ratings Ambient Temperature Operating 40 F to 140 F 40 C to 60 C Storage 40 F to 150 F 40 C to 66 C Humidity 85 relative humidity continuous ...

Страница 2: ...ired to correct this interference 9 This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications Location Humidity Install the relay module where the relative humidity never reaches the saturation point The relay module is designed to operate in a maximum 85 relative humidi...

Страница 3: ...ures for given application TTW60C THW75C THHN90C Ground Type Recommended Practice Earth ground subbase and relay module 1 Use to provide a connection between the subbase and the control panel of the equipment Earth ground must be capable of conducting enough current to blow the 15A fast acting fuse or breaker in the event of an internal short circuit 2 Use wide straps or brackets to provide minimu...

Страница 4: ... Wiring Check 1 Check the power supply circuit The voltage and frequency tolerance must match those of the EC RM7823A A separate power supply circuit may be required for the EC RM7823A Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout in Table 5 before installing the EC RM7823A on the subbase 3 Install all electrical connectors 4...

Страница 5: ... 10 9KA2 N C 1A Pilot Duty at 120 Vac F 11 Flame Sensor 60 to 220 Vac current limited 12 Unused 13 9KB Common 14 9KB1 N C 1A Pilot Duty at 120 Vac also rated for 5V control circuits 15 9KB2 N O 1A Pilot Duty at 120 Vac also rated for 5V control circuits 16 21 Unused 22 Shutter 120 Vac 0 5A Terminal Number Description Ratingsa G Flame Sensor Grounda Earth G Earth Grounda L2 N Line Voltage Common 3 ...

Страница 6: ... signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts IMPORTANT The EC RM7823A must be installed with a plug in motion rather than a hinge action 4 Mount the EC RM7823A by aligning the four L shaped corner guides and knife blade termi...

Страница 7: ...use serious injury death or equipment damage 1 Close all manual fuel shutoff valve s before starting these tests 2 Use extreme care while testing the system Line voltage is present on most terminal connections when power is on 3 Open the master switch before installing or removing a jumper on the subbase 4 Before continuing to the next test be sure to remove test jumper s used in the previous test...

Страница 8: ...damaged or incorrectly sized wires and tighten any loose terminal screws 10 Replace faulty controllers limits interlocks actuators valves transformers motors and other devices as required 11 Make sure normal operation is obtained for each required test before continuing the checkout 12 After completing each test be sure to remove the test jumper s WARNING Explosion hazard Can cause serious injury ...

Отзывы: