Honeywell EC7823A Скачать руководство пользователя страница 1

INSTALLATION INSTRUCTIONS

66-1086-2

® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc.
All Rights Reserved 

EC7823A;RM7823A

7800 SERIES Relay Modules

APPLICATION

The Honeywell EC/RM7823A Relay Module is a 

microprocessor based flame detector relay that can be fitted 

with any 7800 SERIES Flame Amplifier to provide relay action 

from one dpdt relay when flame is or is not present. The 

EC/RM7823A system consists of a relay module, wiring 

subbase and flame amplifier. Options include keyboard 

display module (KDM), personal computer interface, Data 

ControlBus Module™, remote display mounting and 

Combustion System Manager™ Software. 

Functions provided by the EC/RM7823A include flame 

monitoring, self-diagnostics and troubleshooting.The 

EC/RM7823A is a solid state replacement for the R7023B,C 

Flame Detector Relays.

The EC7823/RM7823 is a flame detector relay only. A 

switchable primary control must be used to provide safe-start 

check, safety lockout, load switching and other functions 

required in Flame Safeguard systems.

This document provides installation and static checkout 

instructions. Other applicable publications are:

SPECIFICATIONS

Electrical Ratings, see Table 3:

Voltage and Frequency:

EC7823A: 220-240 Vac +10%/-15%, 50/60 Hz ±10%.

RM7823A: 120 Vac, +10%/-15%, 50/60 Hz, ± 10%.

Power Dissipation:

10W maximum.

Maximum Total Connected Load: 2000 VA.

Fusing: Total Connected Load: 15A, type SC, Fast Blow, or 

equivalent.

Environmental Ratings:

Ambient Temperature:

Operating: -40°F to 140°F (-40°C to +60°C).

Storage: -40°F to 150°F (-40°C to +66°C).

Humidity: 85% relative humidity continuous, noncondensing.

Vibration: 0.5G environment.

Approvals:

RM7823A:

Underwriters Laboratories Inc. Listed: File No. MP268, 

Guide No. MCCZ.

Canadian Standards Association Certified: LR9S329-3.

Factory Mutual Approved: Report No. J.I.1V9A0.AF. 

IRI Acceptable.

Federal Communications Commission: 

Part 15, Class B, Emissions.

EC7823A:

Factory Mutual Approved: Report No. J.I.1V9A0.AF. 

IRI Acceptable.

Federal Communications Commission: 

Part 15, Class B, Emissions.

Form 

Number

Description

63-2278 Q7700A Network Interface Unit Product Data
65-0084 Q7800A,B 22-Terminal Wiring Subbase Product 

Data

65-0090 S7800A Keyboard Display Module Product Data.
65-0091 S7810A Data ControlBus Module™ Product Data
65-0095 S7820 Remote Reset Module Product Data
65-0097 221729C Dust Cover Packing Sheet
65-0109 R7824, R7847, R7848, R7849, R7851, R7861, 

R7886 Flame Amplifiers for the 7800 SERIES 

Product Data

65-0131 221818A Extension Cable Assembly Product Data
65-0229 7800 SERIES Relay Modules Checkout and Test

Содержание EC7823A

Страница 1: ...Ratings see Table 3 Voltage and Frequency EC7823A 220 240 Vac 10 15 50 60 Hz 10 RM7823A 120 Vac 10 15 50 60 Hz 10 Power Dissipation 10W maximum Maximum Total Connected Load 2000 VA Fusing Total Connected Load 15A type SC Fast Blow or equivalent Environmental Ratings Ambient Temperature Operating 40 F to 140 F 40 C to 60 C Storage 40 F to 150 F 40 C to 66 C Humidity 85 relative humidity continuous ...

Страница 2: ...ired to correct this interference 9 This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications Location Humidity Install the relay module where the relative humidity never reaches the saturation point The relay module is designed to operate in a maximum 85 relative humidi...

Страница 3: ...ures for given application TTW60C THW75C THHN90C Ground Type Recommended Practice Earth ground subbase and relay module 1 Use to provide a connection between the subbase and the control panel of the equipment Earth ground must be capable of conducting enough current to blow the 15A fast acting fuse or breaker in the event of an internal short circuit 2 Use wide straps or brackets to provide minimu...

Страница 4: ... Wiring Check 1 Check the power supply circuit The voltage and frequency tolerance must match those of the EC RM7823A A separate power supply circuit may be required for the EC RM7823A Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout in Table 5 before installing the EC RM7823A on the subbase 3 Install all electrical connectors 4...

Страница 5: ... 10 9KA2 N C 1A Pilot Duty at 120 Vac F 11 Flame Sensor 60 to 220 Vac current limited 12 Unused 13 9KB Common 14 9KB1 N C 1A Pilot Duty at 120 Vac also rated for 5V control circuits 15 9KB2 N O 1A Pilot Duty at 120 Vac also rated for 5V control circuits 16 21 Unused 22 Shutter 120 Vac 0 5A Terminal Number Description Ratingsa G Flame Sensor Grounda Earth G Earth Grounda L2 N Line Voltage Common 3 ...

Страница 6: ... signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts IMPORTANT The EC RM7823A must be installed with a plug in motion rather than a hinge action 4 Mount the EC RM7823A by aligning the four L shaped corner guides and knife blade termi...

Страница 7: ...use serious injury death or equipment damage 1 Close all manual fuel shutoff valve s before starting these tests 2 Use extreme care while testing the system Line voltage is present on most terminal connections when power is on 3 Open the master switch before installing or removing a jumper on the subbase 4 Before continuing to the next test be sure to remove test jumper s used in the previous test...

Страница 8: ...damaged or incorrectly sized wires and tighten any loose terminal screws 10 Replace faulty controllers limits interlocks actuators valves transformers motors and other devices as required 11 Make sure normal operation is obtained for each required test before continuing the checkout 12 After completing each test be sure to remove the test jumper s WARNING Explosion hazard Can cause serious injury ...