SDC / DHC
Operation
EN2H-0220GE51 R0308
55
Undoing deactivation
Deactivation is undone when the averaged
and
current outside
temperature exceeds the set value by 1 K.
The summer deactivation function is undone:
•
In case of an outside sensor defect
•
In case frost protection is active
During deactivation phases (standby mode, manual summer
operation, summer deactivation) lasting longer than 24 hours all
pumps are switched on for approx. 20 s and the mixers are
temporarily opened during this time to protect against blocking by
corrosion.
In connection with a second outside sensor, the current averaged
outside temperature is accepted for summer deactivation if the
average value of both sensors is specified during outside sensor
assignment.
Active summer deactivation is represented by a beach umbrella
symbol in the basic display.
Only active in the AUTOMATIC operating mode.
20 °C
OFF, set value of system frost protection to 40 °C
Pos: 51 /156-Honeywell/Bedienung/Parameter-Reset @ 1\mod_1207647099619_6.doc @ 9915
4.2.3.5 Parameter
reset
With the reset parameter, it is possible to reset any inadvertently
made changes in the parameter menu to the factory setting.
ATTENTION
A reset should only be carried out if all individually entered
values are to be replaced by the values specified at the
factory.
►
When the PARAM. RESET
display flashes, press the input
button
î
.
SET flashes in the display.
►
Press and hold the input button
î
for 5 s.
NOTE
Factory setting
Setting range
Setting
Содержание DHC
Страница 1: ...EN2H 0220GE51 R0308 Heating Controller SDC Remote Heating Controller DHC OPERATING INSTRUCTIONS ...
Страница 2: ...EN2H 0220GE51 R0308 ...
Страница 5: ...SDC DHC Contents EN2H 0220GE51 R0308 5 ...
Страница 6: ......
Страница 61: ...SDC DHC Log EN2H 0220GE51 R0308 61 ...
Страница 62: ...Log SDC DHC 62 EN2H 0220GE51 R0308 ...
Страница 63: ......