SDC / DHC
Operation
EN2H-0220GE51 R0308
25
At outside temperatures below the frost-protection limit (see
4.2.3 "System Parameters" menu, pg. 51) the
heating circuits are
controlled as follows:
•
Without wall devices: Based on a lowered room temperature
specification of 3 °C.
•
With wall devices: Based on the room frost-protection limit of
the respective heating circuit of 10 °C (see "Direct Heating
Circuit" or "Mixed Heating Circuit 1", "Mixed heating circuit 2"
menu, parameter 08 = room frost-protection limit).
An active holiday program can be cancelled in case of early
return.
►
Press
button.
►
Turn input button
î
and switch to automatic mode.
The active holiday program has been cancelled.
Current date
Current date... (current date + 250 days)
An active holiday program appears in the basic display with
information on the return date.
Pos: 21 /156-Honeywell/Bedienung/Taste_Anlageninformation @ 1\mod_1207644494728_6.doc @ 9450
Control during
holidays
Cancellation
Factory setting
Setting range
Display