background image

69-1088B

7

D896 AUTOMATIC VENT DAMPER

EXHIBIT B

Procedure for Installing Electrically Operated Automatic Vent Damper Devices

on Existing Appliances

This procedure is intended as a guide to aid in safely installing an electrically operated or mechanically actuated

automatic vent damper device on an existing appliance.

This procedure is based on the assumption that the history of the specific appliance has been one of safe and

satisfactory operation.

This procedure is predicated on central furnace, boiler and water heater installations, and it should be recognized that

generalized procedures cannot anticipate all situations. Accordingly, in some cases deviation from this procedure may
be necessary to determine safe operation of the equipment.

The following steps are to be followed in making the modifications:

1. Perform a safety inspection of the existing appliance installation. See Exhibit A for the recommended procedure

for such a safety inspection.

2. Shut off all gas and electricity to the appliance. 

To shut off gas use the shutoff valve in the supply line to the

appliance.

3. Install the automatic vent damper device in strict accordance with the manufacturer’s installation instructions.

Make certain the device is not located in that portion of the venting system which serves any appliance other than the
one for which the damper is installed.

4. Make certain wiring connections are tight and wires are positioned and secured so they will not be able to contact

high temperature locations.

5. When an additional automatic valve has been incorporated or an existing gas control replaced, conduct a gas

leakage test of the appliance piping and control system downstream of the shutoff valve in the supply line to the
appliance.

6. Visually inspect the modified venting system for proper horizontal pitch.
7. Check that the damper and gas valve(s) are in the correct operating sequence.

(a)The damper must be in the full open position before the gas valve(s) opens.
(b)The damper must remain in the full open position while the gas valve(s) is open.
(c) The gas valve(s) must be closed before the damper 

begins

 its return to the closed position.

(d)The damper shall remain in the closed position during the off cycle of the appliance.

8. Determine the amperage draw of the gas control circuit and damper device.

(a)Check appliance transformer for adequate capacity.
(b)Check heat anticipator in comfort thermostat to determine it is properly adjusted.

9. Sequence the appliance through at least three normal operating cycles.

10. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliance

is located and other spaces of the building. Turn on clothes dryers. Turn on any exhaust fans, such as range hoods and
bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace
dampers.

11. Place appliance in operation. 

Follow the lighting instructions.

  Adjust thermostat so appliance will operate

continuously.

12. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match

or candle, or smoke from a cigarette, cigar or pipe.

13. (a) Visually determine that main burner gas is burning properly; i.e., no floating, lifting or flashback. Adjust the

primary air shutter(s) as required.

(b) If the appliance is equipped with high and low flame controlling or flame modulation, check for proper main

burner operation at low flame.

14. Determine that the pilot(s), when provided, is burning properly and that main burner ignition is satisfactory by

interrupting and reestablishing the electrical supply to the appliance in any convenient manner.

If the appliance is equipped with a continuous pilot(s), test the pilot safety device(s) to determine if it is operating

properly by extinguishing the pilot(s) when the main burner(s) is off and determining, after 3 minutes, that the main burner
gas does not flow upon a call for heat.

If the appliance is not provided with a pilot(s), test for proper operation of the ignition system in accordance with the

appliance manufacturer’s lighting and operating instructions.

15.

Applicable only to furnaces

—Check both the limit control and the fan control for proper operation. Limit control

operation can be checked by blocking the circulating air inlet or temporarily disconnecting the electrical supply to the
blower motor and determining that the limit control acts to shut off the main burner gas.

16.

Applicable only to boilers

(a) Determine that the water pumps are in operating condition.
(b) Test low water cutoffs, automatic feed controls, pressure and temperature limit controls, and relief valves in

accordance with the manufacturer’s recommendations to determine they are in operating condition.

17. Label the damper device (see 1.7.5) with information as to:

(a) Name of qualified agency responsible for damper installation.
(b) Date of installation.

Exhibit B of ANSI Standard Z21.66-1994 for Electrically Operated Automatic Vent Damper Devices

for use with Gas-Fired Appliances.

Содержание D896

Страница 1: ... damper is fully open the IGNITION GAS PWR LED lights and the furnace or boiler burner ignites When the heating cycle ends both LEDs are truned off the burner turns off and the damper automatically closes Heating system efficiency is increased because the closed damper reduces the loss of residual appliance heat and heated room air through the draft diverter INSTALLATION When Installing this Produ...

Страница 2: ... sure the D896 is used to control only one appliance CAUTION Do not force damper open Damage to device can result Manually open damper using a screwdriver Place screwdriver in slotted knob see Fig 4 and rotate counterclockwise until arrow is pointing in the direction of the stack and both LEDs turn on Mounting The damper must be mounted as close as possible to the draft hood without modifying the ...

Страница 3: ...nt explosion or carbon monoxide poisoning 2 Do not use the D896 with an L8148 or L8124 with a manual automatic switch because the switch can override the safety interlocks in the system wiring causing carbon monoxide buildup CAUTION 1 Remove the shorting plug on the S8600 S8610 or L8148E before attaching the wiring harness 2 Do not permit device wiring to contact high temperature surfaces 3 Label ...

Страница 4: ...6 OPERATES ONLY WHEN VENT DAMPER IS CONNECTED LED 1 LIGHTS WHEN DAMPER IS OPEN LED 2 LIGHTS WITH CALL FOR HEAT SERVICE SWITCH THE NORMAL SWITCH SETTING IS NORM IF THE SWITCH IS MOVED TO THE SERV POSITION THE DAMPER REMAINS OPEN NO W Z TERMINALS ON L7148 M11382 D896 1 2 4 WIRING HARNESS 24 Vac THERMOSTAT 1K L8148E1166 L7148 1K1 L1 HOT L2 CIRCULATOR 3 4 1 3 2 6 PRONG FEMALE MOLEX RECEPTACLE IN L8148...

Страница 5: ... using the thermostat or controller to ensure the system is operating safely THE AIR DUCT IS CLOSED WHEN THE INDICATOR POINTS PERPENDICULAR TO THE DIRECTION OF THE AIR DUCT THE AIR DUCT IS OPEN WHEN THE INDICATOR POINTS IN THE DIRECTION OF THE AIR DUCT M3431 Fig 8 Determining damper position Cooling CAUTION Damage to air condtioner condenser possible Do not operate cooling if outdoor temperature i...

Страница 6: ...the absence of local codes to the National Fuel Gas Code ANSI Z223 1 1988 NFPA 54 for guidance 9 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 10 Determine that the pilot s when provided is burning properly and that main burner ignition is satisfactory by interrupting and reestablishing the electrical supp...

Страница 7: ... thermostat to determine it is properly adjusted 9 Sequence the appliance through at least three normal operating cycles 10 Insofarasispractical closeallbuildingdoorsandwindowsandalldoorsbetweenthespaceinwhichtheappliance is located and other spaces of the building Turn on clothes dryers Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not...

Страница 8: ...ng Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Helping You Control Your World 69 1088B J S 3 97 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 ...

Страница 9: ...ment et le générateur d air chaud ou la chaudière se met en marche Lorsque le cycle de chauffage prend fin le générateur ou la chaudière s éteint et le registre se referme L efficacité du système de chauffage s accroît car la fermeture du registre réduit la perte de chaleur résiduelle et de chaleur ambiante par l ouverture du coupe tirage INSTALLATION Avant D installer ce Produit 1 Lire les instru...

Страница 10: ...VERTISSEMENT Ne pas forcer l ouverture du registre à la main au risque de l endommager Pour ouvrir le registre à la main utiliser un tournevis Insérer le tournevis dans le bouton fendu voir la Fig 4 et tourner dans le sens antihoraire jusqu à ce que la flèche pointe dans le sens de la cheminée et que les deux voyants soient allumés Montage Le registre doit être installé aussi près que possible du ...

Страница 11: ...HON EN PLACE RETENIR LA PALETTE ET APPUYER SUR LE BOUCHON MF3429 DISPOSITIF DE COMMANDE DU MOTEUR BOUCHON DE PALETTE PALETTE DU REGISTRE Câblage MISE EN GARDE Peut causer des maladies graves et entraîner la mort Empêcher les explosions et l empoisonnement au monoxyde de carbone 1 L utilisation d un registre d aération D896 requiert l installation d un bloc combiné gaz à deux vannes ou de deux vann...

Страница 12: ...ORM SI L INTERRUPTEUR EST À LA POSITION SERV LE REGISTRE RESTE OUVERT MF11374 D896 1 2 4 FAISCEAU DE FILS THERMOSTAT 24 V c a 1K L8148E1166 1K1 L1 SOUS TENSION L2 CIRCULATEUR 3 4 1 3 2 RÉCEPTACLE DE PRISE MOLEX FEMELLE À 6 BROCHES DANS LE L8148E ET PRISE MOLEX MÂLE À 5 BROCHES SUR LE CÂBLE 24V MISE 24V À LA TERRE PRISE MOLEX MÂLE À 4 BROCHES POLARISÉES ET PRISE MOLEX FEMELLE À 4 BROCHES CORRESPOND...

Страница 13: ...on normal et la position service Voir la Fig 4 NORMAL Le D896 s ouvre lors d une demande de chaleur et se referme à la fin du cycle de chauffage SERVICE Le D896 reste ouvert à la fin de la demande de chaleur L interrupteur doit être à la position SERVICE avant que le registre ne soit ouvert à la main VÉRIFICATION Chauffage 1 Rétablir l alimentation électrique 2 Si on utilise un thermostat régler l...

Страница 14: ...Cela pourrait forcer le registre D896 à rester en position de fermeture REMARQUE En cas de panne de courant le registre restera exactement à la position où il se trouve au moment de la panne ouvert fermé ou entre les deux Lorsque le courant sera rétabli le registre ouvrira si le thermostat demande de la chaleur ou se refermera si le thermostat ne demande pas de chaleur Régler le thermostat ou le r...

Страница 15: ...ence de tels codes ou règlements se reporter au National Fuel Gas Code norme ANSI Z223 1 1988 NFPA 54 pour obtenir des conseils 9 Mettre en marche l appareil faisant l objet de l inspection Suivre les instructions d allumage Ajuster le thermostat de façon à ce que l appareil fonctionne de façon continue 10 Déterminer si la ou les veilleuses le cas échéant brûlent correctement et que l allumage du ...

Страница 16: ... de déterminer si elle est correctement réglée 9 Faire fonctionner l appareil pendant au moins trois cycles de fonctionnement normal 10 Dans la mesure du possible fermer toutes les portes et fenêtres du bâtiment et toutes les portes entre la pièce où l appareil est situé et les autres pièces du bâtiment Faire fonctionner les sécheuses à linge Faire fonctionner les ventilateurs d extraction tels qu...

Отзывы: