WEB-300E, WEB-600E/U, CP-300E, CP-600E/U SERIES CONTROLLERS
31-00010—01
8
If desired, you can use the wall mount NPB-WPM-US/U in
your office (to initially commission the controller), and then
install the controller at the job using either a NPB-PWR-H/
U or NPB-PWR-UN-H/U module. The following sections
provide more details:
• “NPB-PWR-H/U” on page 8 (24 Vac/dc-powered in-line
module)
• “NPB-PWR-UN-H/U” on page 8 (Universal 120V–
240Vac-powered in-line module)
• “NPB-WPM-US/U (Wall Mount AC Adapter)” on page 9
NPB-PWR-H/U
Use the NPB-PWR-H/U module to power the controller
(and if installed, IO-16-H/U modules) from a dedicated
Class 2, 24Vac transformer, or from a 24Vdc power
supply.
NOTE: If there is no optional NiMH backup battery,
using the NPB-PWR-H/U allows a higher
operating temperature. See “Environmental
NOTE: If powering from a 24V transformer, do not
power any other equipment with it. Other-
wise, conducted noise problems may result.
Also, do not ground either side of the trans-
former’s 24V secondary.
Fig. 4. NPB-PWR-H/U module wiring connections.
Located at the bottom of the NPB-PWR-H/U module is a
2-position power connector, and an earth ground spade
lug, as shown in Fig. 4.
Connect the supplied earth ground wire to a nearby earth
ground point. Unplug the power connector plug from the
module and make connections to it as shown.
CAUTION
Do not plug 24V power into the NPB-PWR-H/U
(reinsert connector plug) until all other
mounting and wiring is completed. See “Initial
power up and checkout.” on page 12.
NPB-PWR-UN-H/U
The NPB-PWR-UN-H/U module lets you power the
controller (and if installed, connected I/O modules) from
AC line power, with a universal input range from 120–
240Vac. If installing IO-16-H/U modules, the NPB-PWR-
UN-H/U module mounts as the last (end) module in the
chain. (See Fig. 1 on page 4).
WARNING
• A 120Vac or 240Vac circuit powers the NPB-
PWR-UN-H/U. Disconnect power to this circuit
before installation to prevent electrical shock
or equipment damage.
• Make all connections in accordance with
national and local electrical codes. Use copper
conductors only.
• Do not exceed the 30W capacity of NPB-
PWR-UN-H/U by the powered devices.
+
–
M34991
CONTROLLER
NPB-PWR-H/U (COVER REMOVED)
EARTH GROUND
SUPPLIED EARTH
GROUNDING WIRE
DEDICATED 24VAC TRANSFORMER
NEITHER SIDE OF SECONDARY
TIED TO EARTH GROUND
24VAC
OR
24VDC
24VDC POWER SUPPLY
(POLARITY NOT CRITICAL)
NEITHER SIDE TIED TO EARTH