QS7800B NETWORK INTERFACE CONTROLBUS™ MODULE FOR MULTI-DROPPING 7800 SERIES RELAY MODULES

65-0227—2

6

BUILDING A MULTI-DROP NETWORK

Guidelines

The subnetwork addressing in the Q7700 Network Interface 
Unit (NIU) is not contiguous. It is divided into two blocks, 
containing 198 and 24 addresses, respectively. A maximum 
multi-drop configuration would include 222 subnetworks (198 
plus 24) on a single Q7700 NIU. Because the 24 subnetworks 
are not contiguous, connect them to a separate Q7700 NIU 
slot.

One QS7800B ControlBus™ Module card  supports up to 31 
multi-drop subnetworks without using an RS-485 repeater. If 
an RS-485 repeater is used, up to 61 multi-drop subnetworks 
can be supported by one QS7800B card. The RS-485 
repeater must be installed between the 30th and 31st 
subnetwork.

Each subnetwork includes one 7800 SERIES controller with 
or without an S7800 Keyboard Display Module and/or an 
S7830 Expanded Annunciator. An S7810B1007 Multi-Drop 
Switch Module is required in each subnetwork. See Fig. 6 for 
wiring information. 

Subnetworks can be spread evenly (balanced) across the NIU 
slots. This will help to speed communications.

It is recommended that the multi-drop network be built starting 
with slot number 1 of the NIU, according to the guidelines 
above.

Record the serial number and physical location of each 
S7810B Multi-Drop Switch. This data will be useful when 
commissioning the ZM7850 Combustion System Manager 
(CSM) software. (Reference CSM manual, form 65-0102, for 
CSM commissioning.)

Examples

Network with  Maximum of 198 Subnetworks:

The open NIU slots can be used for other QS7800 ControlBus™ Module Cards.

Network with  Maximum of 222 Subnetworks:

NOTE:

For networks that have more than 198 subnetworks, 
the last NIU card slot must have the 199th through 
222nd subnetwork attached to it.

The open NIU slot can be used for other QS7800 ControlBus™ Module Cards.

NIU Slot Numbers

1

2

3

4

5

6

Total

Number of Subnetworks

61

61

61

15

Open

Open

198

Subnetworks Balanced

33

33

33

33

33

33

198

NIU Slot Numbers

1

2

3

4

5

6

Total

Number of Subnetworks

61

61

61

15

24

Open

222

Subnetworks Balanced

40

40

40

39

39

24

222

Содержание CONTROLBUS QS7800B

Страница 1: ...imum of 222 multi dropped subnetworks per Q7700 Network Interface Unit Up to 31 multi dropped 7800 SERIES subnetworks per QS7800B ControlBus Module without using an RS 485 repeater Up to 61 multi dropped 7800 SERIES subnetworks per QS7800B ControlBus Module using an RS 485 repeater Local and remote annunciation of 7800 SERIES Relay Module faults Personal computer user interface Microsoft Windows b...

Страница 2: ...ederal Communications Commission Part 15 Class A Emis sions Part 68 FCC Registration Number HS92SJ 10735 DT E Canadian Department of Communication CS 03 Certification Number 573 3459A IMPORTANT This equipment complies with the requirements in part 15 of FCC rules for a Class A computing device Operation of this equipment in a residential area can cause unacceptable interference with radio and tele...

Страница 3: ...rface Unit Be sure to allow clearances for servicing installing and removing the wiring compartment cover Network Interface Unit cover electrical connectors and ControlBus Modules a Allow for an additional 2 1 2 inches 64 mm minimum below the Network Interface Unit for electrical connector installation b Allow for an additional 1 1 2 inches 38 mm minimum on each side for electrical housing cover i...

Страница 4: ... 9 pin RS 232 connector of the Network Interface Unit see Fig 4 9 Connect the serial port of the personal computer to the 25 pin RS 232C port on the Network Interface Unit for local personal computer application see Fig 3 10 Do not exceed 600 mA current draw six card maximum total capacity of the plug in cards Refer to the ControlBus Module device label and this specification for individual loads ...

Страница 5: ...SHIELDED CABLE BELDEN 8723 OR EQUIVALENT IS RECOMMENDED CABLE SHIELD MUST BE GROUNDED AT EACH END MULTI DROP COMMUNICATION BUS TERMINATION RESISTORS A WITHOUT RS 485 REPEATER MODULES AT THE CLOSEST AND FARTHEST END OF THE DAISY CHAIN REQUIRE TERMINATION RESISTORS INSTALL A 120 OHM 1 4 WATT RESISTOR BETWEEN TERMINALS a AND b of the QS7800B CONTROLBUS MODULE INSTALL A 120 OHM 1 4 WATT RESISTOR BETWE...

Страница 6: ...ule is required in each subnetwork See Fig 6 for wiring information Subnetworks can be spread evenly balanced across the NIU slots This will help to speed communications It is recommended that the multi drop network be built starting with slot number 1 of the NIU according to the guidelines above Record the serial number and physical location of each S7810B Multi Drop Switch This data will be usef...

Страница 7: ...7 65 0227 2 ...

Страница 8: ...nal Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 ...

Отзывы: