QS7800B NETWORK INTERFACE CONTROLBUS™ MODULE FOR MULTI-DROPPING 7800 SERIES RELAY MODULES

5

65-0227—2

Fig. 6. Multi-drop wiring.

NETWORK INTERFACE UNIT

PLUG-IN

PLUG-IN

POWER
SUPPLY

L1

L2

GND

SYSTEM 2

A

B

C

M11347A

UNIVERSAL
POWER
SUPPLY

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. Q7700A1014, 120V, 50/60 HZ; Q7700B1004, 
UNIVERSAL POWER SUPPLY, 100 TO 250V, 50/60 HZ.

CONNECT PIGTAIL LEADWIRES (Q7700A ONLY):
BLACK—L1
WHITE—L2
GREEN—GROUND

MULTI-DROP RS-485 COMMUNICATION BUS. UP TO 31 S7810B MULTI-DROP SWITCH MODULES (SUBNETWORKS) CAN BE CONNECTED TO A SINGLE 
QS7800B CONTROLBUS™ MODULE WITHOUT AN RS-485 REPEATER. UP TO 61 S7810B MULTI-DROP SWITCH MODULES (SUBNETWORKS) CAN BE 
CONNECTED TO A SINGLE QS7800B CONTROLBUS™ MODULE WITH AN RS-485 REPEATER.
 
INSTALL THE REPEATER BETWEEN THE 30TH AND 31ST SUBNETWORKS.

UP TO SIX QS7800B CONTROLBUS™ MODULES CAN BE INTERFACED WITH THE NETWORK INTERFACE UNIT. MAXIMUM OF 222 MULTI-DROP 
SUBNETWORKS CAN BE INTERFACED WITH A SINGLE Q7700 NETWORK INTERFACE UNIT.

LOCAL SYSTEM (SUBNETWORK). REFER TO S7810B MULTI-DROP SWITCH MODULE INSTRUCTIONS, FORM 65-0228, FOR WIRING INSTRUCTIONS.

THE SUBNETWORKS MUST BE WIRED IN A DAISY CHAIN CONFIGURATION. IT IS RECOMMENDED THAT THE QS7800B CONTROLBUS™ MODULE 
BE AT ONE END OF THE DAISY CHAIN.

22 AWG (OR LARGER) TWISTED PAIR SHIELDED CABLE (BELDEN 8723 OR EQUIVALENT) IS RECOMMENDED. CABLE SHIELD MUST BE GROUNDED 
AT EACH END.

MULTI-DROP COMMUNICATION BUS TERMINATION RESISTORS:
A. WITHOUT RS-485 REPEATER: MODULES AT THE CLOSEST AND FARTHEST END OF THE DAISY CHAIN REQUIRE TERMINATION RESISTORS. INSTALL 
A 120 OHM, 1/4 WATT, RESISTOR BETWEEN TERMINALS a AND b of the QS7800B CONTROLBUS™ MODULE. INSTALL A 120 OHM, 1/4 WATT, RESISTOR 
BETWEEN TERMINALS 7 AND 8 OF THE LAST S7810B MULTI-DROP SWITCH MODULE IN THE DAISY CHAIN.
B. WITH RS-485 REPEATER: WHEN AN RS-485 REPEATER IS USED, TWO DAISY CHAIN CONFIGURATIONS ARE EFFECTIVELY FORMED. MODULES AT 
THE CLOSEST AND FARTHEST END OF EACH DAISY CHAIN REQUIRE TERMINATION RESISTORS. INSTALL A 120 OHM, 1/4 WATT, RESISTOR BETWEEN 
TERMINALS a AND b OF THE QS7800B CONTROLBUS™ MODULE. INSTALL A 120 OHM, 1/4 WATT, RESISTOR BETWEEN INPUT TERMINALS DATA+ AND 
DATA- OF THE RS-485 REPEATER. INSTALL A 120 OHM, 1/4 WATT, RESISTOR BETWEEN OUTPUT TERMINALS DATA+ AND DATA- OF THE RS-485 REPEATER. 
INSTALL A 120 OHM, 1/4  WATT, RESISTOR BETWEEN TERMINALS 7 AND 8 OF THE LAST S7810B MULTI-DROP SWITCH MODULE IN THE SECOND DAISY CHAIN. 

FOR Q7700B NETWORK INTERFACE UNIT.

1

2

3

4

5

6

7

8

9

10

1

2

3

5

10

9

9

9

9

8

8

7

7

7

6

6

6

4

8 7 6 5 4 3 2 1

S7810B MULTI-DROP
SWITCH MODULE

7800 SERIES
RELAY MODULE

8 7 6 5 4 3 2 1

S7810B MULTI-DROP
SWITCH MODULE

7800 SERIES
RELAY MODULE

TO LOCAL
SYSTEM

8 7 6 5 4 3 2 1

S7810B MULTI-DROP
SWITCH MODULE

7800 SERIES
RELAY MODULE

TO LOCAL
SYSTEM

TO LOCAL
SYSTEM

INPUT

OUTPUT

+ –

GND

+ –

GND

RS-485
REPEATER

Содержание CONTROLBUS QS7800B

Страница 1: ...imum of 222 multi dropped subnetworks per Q7700 Network Interface Unit Up to 31 multi dropped 7800 SERIES subnetworks per QS7800B ControlBus Module without using an RS 485 repeater Up to 61 multi dropped 7800 SERIES subnetworks per QS7800B ControlBus Module using an RS 485 repeater Local and remote annunciation of 7800 SERIES Relay Module faults Personal computer user interface Microsoft Windows b...

Страница 2: ...ederal Communications Commission Part 15 Class A Emis sions Part 68 FCC Registration Number HS92SJ 10735 DT E Canadian Department of Communication CS 03 Certification Number 573 3459A IMPORTANT This equipment complies with the requirements in part 15 of FCC rules for a Class A computing device Operation of this equipment in a residential area can cause unacceptable interference with radio and tele...

Страница 3: ...rface Unit Be sure to allow clearances for servicing installing and removing the wiring compartment cover Network Interface Unit cover electrical connectors and ControlBus Modules a Allow for an additional 2 1 2 inches 64 mm minimum below the Network Interface Unit for electrical connector installation b Allow for an additional 1 1 2 inches 38 mm minimum on each side for electrical housing cover i...

Страница 4: ... 9 pin RS 232 connector of the Network Interface Unit see Fig 4 9 Connect the serial port of the personal computer to the 25 pin RS 232C port on the Network Interface Unit for local personal computer application see Fig 3 10 Do not exceed 600 mA current draw six card maximum total capacity of the plug in cards Refer to the ControlBus Module device label and this specification for individual loads ...

Страница 5: ...SHIELDED CABLE BELDEN 8723 OR EQUIVALENT IS RECOMMENDED CABLE SHIELD MUST BE GROUNDED AT EACH END MULTI DROP COMMUNICATION BUS TERMINATION RESISTORS A WITHOUT RS 485 REPEATER MODULES AT THE CLOSEST AND FARTHEST END OF THE DAISY CHAIN REQUIRE TERMINATION RESISTORS INSTALL A 120 OHM 1 4 WATT RESISTOR BETWEEN TERMINALS a AND b of the QS7800B CONTROLBUS MODULE INSTALL A 120 OHM 1 4 WATT RESISTOR BETWE...

Страница 6: ...ule is required in each subnetwork See Fig 6 for wiring information Subnetworks can be spread evenly balanced across the NIU slots This will help to speed communications It is recommended that the multi drop network be built starting with slot number 1 of the NIU according to the guidelines above Record the serial number and physical location of each S7810B Multi Drop Switch This data will be usef...

Страница 7: ...7 65 0227 2 ...

Страница 8: ...nal Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 ...

Отзывы: