QS7800B NETWORK INTERFACE CONTROLBUS™ MODULE FOR MULTI-DROPPING 7800 SERIES RELAY MODULES

65-0227—2

4

a. Near a phone line.
b. Within 4000 ft (1219 m) of all Relay Modules 

connected to the Network Interface Unit.

c. Within 50 ft (15 m) of the personal computer 

connected to the 25-pin RS-232 port of the Network 
Interface Unit.

4.

Mount the Network Interface Unit and insert the 
ControlBus™ Module into the Network Interface Unit 
slot, see Fig. 2 and 5.

Route the ControlBus™ cable so that all devices are 
connected in a daisy chain configuration. It is 
recommended that the QS7800B ControlBus™ Module be 
at one end of the daisy chain.

5.

Connect L1, L2 and Ground (GND) to the pigtails 
(Q7700A only).

6.

Insert the plug-in cards into the open slots of the 
Network Interface Unit, starting with slot one.

7.

Install the covers, power wiring compartment and 
Network Interface Unit. 

8.

Connect the serial port of the modem to the 9-pin 
RS-232 connector of the Network Interface Unit (see 
Fig 4).

9.

Connect the serial port of the personal computer to the 
25-pin RS-232C port on the Network Interface Unit for 
local personal computer application, see Fig. 3.

10.

Do not exceed 600 mA current draw, six card maximum, 
total capacity of the plug-in cards. Refer to the 
ControlBus™ Module device label and this specification 
for individual loads.

11.

Recheck all wiring with Fig. 6.

12.

Restore power to the Network Interface Unit.

Fig. 1. QS7800B Network Interface ControlBus™ Module 

dimensions in in. (mm).

Fig. 2. ControlBus™ Module mounting.

Fig. 3. RS-232 Interface insertion 

(serial communications).

Fig. 4. Modem insertion, Network Interface Unit.

Fig. 5. ControlBus™ RS-485 interface insertion.

1 (25)

M2093

3-29/32

(99)

4-21/32 (118)

M7437B

ELECTRICAL
CONNECTOR

EDGE
CONNECTOR

CONTROLBUS™
MODULE

NETWORK
INTERFACE
UNIT

25-PIN 
RS-232C
CONNECTOR

NETWORK
INTERFACE
UNIT

M7432B

CONTROLBUS™
PLUG-IN MODULE

9-PIN RS-232
CONNECTOR

RS-232C CONNECTOR
(SERIAL COMMUNICATIONS)

M7433B

NETWORK
INTERFACE UNIT

CONTROLBUS™
MODULE

CONTROLBUS
RS-485 CONNECTOR

NETWORK 
INTERFACE UNIT 

M7436B

Содержание CONTROLBUS QS7800B

Страница 1: ...imum of 222 multi dropped subnetworks per Q7700 Network Interface Unit Up to 31 multi dropped 7800 SERIES subnetworks per QS7800B ControlBus Module without using an RS 485 repeater Up to 61 multi dropped 7800 SERIES subnetworks per QS7800B ControlBus Module using an RS 485 repeater Local and remote annunciation of 7800 SERIES Relay Module faults Personal computer user interface Microsoft Windows b...

Страница 2: ...ederal Communications Commission Part 15 Class A Emis sions Part 68 FCC Registration Number HS92SJ 10735 DT E Canadian Department of Communication CS 03 Certification Number 573 3459A IMPORTANT This equipment complies with the requirements in part 15 of FCC rules for a Class A computing device Operation of this equipment in a residential area can cause unacceptable interference with radio and tele...

Страница 3: ...rface Unit Be sure to allow clearances for servicing installing and removing the wiring compartment cover Network Interface Unit cover electrical connectors and ControlBus Modules a Allow for an additional 2 1 2 inches 64 mm minimum below the Network Interface Unit for electrical connector installation b Allow for an additional 1 1 2 inches 38 mm minimum on each side for electrical housing cover i...

Страница 4: ... 9 pin RS 232 connector of the Network Interface Unit see Fig 4 9 Connect the serial port of the personal computer to the 25 pin RS 232C port on the Network Interface Unit for local personal computer application see Fig 3 10 Do not exceed 600 mA current draw six card maximum total capacity of the plug in cards Refer to the ControlBus Module device label and this specification for individual loads ...

Страница 5: ...SHIELDED CABLE BELDEN 8723 OR EQUIVALENT IS RECOMMENDED CABLE SHIELD MUST BE GROUNDED AT EACH END MULTI DROP COMMUNICATION BUS TERMINATION RESISTORS A WITHOUT RS 485 REPEATER MODULES AT THE CLOSEST AND FARTHEST END OF THE DAISY CHAIN REQUIRE TERMINATION RESISTORS INSTALL A 120 OHM 1 4 WATT RESISTOR BETWEEN TERMINALS a AND b of the QS7800B CONTROLBUS MODULE INSTALL A 120 OHM 1 4 WATT RESISTOR BETWE...

Страница 6: ...ule is required in each subnetwork See Fig 6 for wiring information Subnetworks can be spread evenly balanced across the NIU slots This will help to speed communications It is recommended that the multi drop network be built starting with slot number 1 of the NIU according to the guidelines above Record the serial number and physical location of each S7810B Multi Drop Switch This data will be usef...

Страница 7: ...7 65 0227 2 ...

Страница 8: ...nal Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 ...

Отзывы: