9.2 Possible causes / Elimination

A  B  C  D  E  F  G  H  I  J  K  L  M  N  Possible cause 

Elimination 

refer to

x x

x

x

The pump or pipelines are not completely 
ventilated of not filled 

Fill or ventilate them 

Instructions for the 
pump

x x x x x

x

Shut-off valves are only opened partially 
or not at all 

check and open if necesary 

------------------------

x

x x

x

The dirt trap is clogged 

clean 

Chapter 8.3.2

x x x x

The shut-off valve of the input is closed or 
defective 

check and open if necesary 

------------------------

x

x

The shut-off valveof the output is closed 
or defective 

check and open if necesary 

------------------------

x x

x x x

x

x

Pressure switch is set wrong 

Check the set value 

Instructions for the 
pressure switch

x

Switch-on pressure is too high 

Check the set value 

Chapter  4.

x

x

Membrane pressure vessel is not 
precharged enough 

Set the precharge pressure

Chapter 8.3.1

Renew the pressure pad 

Instructions for the 
membrane pressure 
vessel

x

x

The membrane pressure vessel is defec-
tive 

check the seal, replace if necessary  Instructions for the 

membrane pressure 
vessel

x

The floating ring seal is defective 

replace 

Instructions for the 
pump

x

Buffer tank is not full 

Check the water level in the buffer 
tank 

------------------------

x x x

x x x

The system check valve is defective 

check and replace if necessary 

Instructions for the 
check valves

x

x

x x x

More water is removed than stated in the 
ordering data 

Consult the manufacturer 

------------------------

x

The motor protection switch is activated, 
it is set wrong or the pump is stuck 

Compare the values with those stated 
on the type label 

Type label/Pump in-
structions

x

The set delay is too short 

Check the set value 

Chapter 7.3.1.3

x

The main power supply is interrupted 

check or eliminate the defect, check 
the fuse 

------------------------

x

x

The main fuse in the distributor of the sy-
stem is loose or burned, perhaps too 
small or too fast-acting fuses were used 

Check the fuses, renew if necessary, 
measure the motor current 

------------------------

x

Phase failure 

check individual phases, replace if 
necessary 

------------------------

x

Magnetic valve for the minimum pumping 
amount does not switch 

check or eliminate the defect 

Instructions for ma-
gnetic valves

x

Leak on the output side 

check 

------------------------

x

Electrical connection between the buffer 
tank control unit and the switch cabinet is 
interrupted 

check or renew the electrical connec-
tion 

------------------------

x

The refilling is too large, odour trap is 
clogged 

Check the refilling, check if the odour 
trap is clogged, clean if necessary 

------------------------

Содержание CBU145

Страница 1: ...CBU145 Compact Booster Unit double pump To ensure the quality of potable water according to EN1717 Instructions 32303722 001 ...

Страница 2: ... separation of potable water 9 3 5 9 Mode of operation in the event of power loss 9 3 6 Options 9 4 Technical data 10 4 1 Construction dimensions 11 4 2 Noise expectancy values 11 4 3 Authorised environmental conditions 11 5 Shipping 12 5 1 Check condition upon delivery 12 5 2 Transportation 12 6 Assembly 12 6 1 General safety instructions 12 6 2 Installation according to DIN 14462 12 6 3 Installa...

Страница 3: ...ocess must be ensured The operator is responsible for complying with local regulations that are not covered by the manual 1 4 Further safety regulations Besides the safety instructions presented in this manual and its intended use the following safety regulations are valid Accident prevention regulations safety and operating regulations Safety regulations for handling hazardous substances Applicab...

Страница 4: ... Type of hazard Reduction of hazard Injury from cables Danger to life Electric shock of 230 400V from electric voltage Connect up protective earth system Always switch off power supply and secure against swit ching on again during maintenance and servicing work Comply with the valid accident prevention and safety re gulations for electrical devices Electrostatically endangered components subassemb...

Страница 5: ... protection against contact during operation of the pump Eliminate hazards caused by electrical energy for details refer to the country specific regulations and or local power supply companies 1 10Safety instructions for maintenance inspections and assembly work Alterations or modifications of the system are only permitted with the consent of the manufacturer Use only original parts or parts autho...

Страница 6: ... in individual cases from the actual compact booster unit version 2 1 4 Symbols 1 Start of a task description 2 Next work step Result of an action List of several options Reference to other documents 2 2 Other applicable documents Data sheet CBU145 Operating instructions of the operating company Data sheets Documentation for the switch cabinet circuit diagram Wiring scheme for the external remote ...

Страница 7: ...temperature sensor are installed wired and preset with standard default values in the factory Buffer tank with inlet and flushing apparatus as well as level overflow and dry running monitor The components are assembled and preset in the factory The electrical components are connected to the control unit of the booster station with plug connections Thus if required an electric separa tion can be ma...

Страница 8: ...rame and completely wired with the Compact Booster Unit Power supply for water level measure ment and solenoid valve is made possible via a plug connection to the switch cabinet 3 4 4 1 Automation Electro mechanical control unit Timer for 24 hour functional operation and weekly flushing cycle Manual automatic switch Phase monitor relays with rotation monitoring and phase failure protection Protect...

Страница 9: ...ted in the automatic and manual modes 3 5 6 Mode of operation for refilling Refilling is done automatically via a float valve Water shortage and overflow are indicated as an error by the switch cabinet 3 5 7 Mode of operation for flushing Flushing of the potable water pipeline connected upstream can be activated by setting the digital timer in the switching cabinet via the solenoid valve The flush...

Страница 10: ...8 4 5 5 10 07 CBU145 50A 074 18 74 G2 DN50 7 4 2 4 9 8 7 5 13 6 CBU145 50A 085 18 85 G2 DN50 8 5 2 7 11 2 7 5 13 6 CBU145 50A 095 18 95 G2 DN50 9 5 3 2 12 7 11 19 47 CBU145 50A 105 18 105 G2 DN50 10 5 3 6 14 1 11 19 47 CBU145 65A 128 18 125 G2 DN65 12 5 1 5 14 15 26 7 CBU145 80B 052 36 51 G2 1 2 DN80 5 1 1 6 1 11 19 47 CBU145 80B 063 36 62 G2 1 2 DN80 6 2 1 1 7 3 11 19 47 CBU145 80B 073 36 72 G2 1...

Страница 11: ...5 G2 DN50 1372 208 1720 2000 691 CBU145 50A 105 G2 DN50 1372 208 1720 2000 693 CBU145 65A 128 G2 DN65 1372 223 1860 2000 773 CBU145 80B 052 G2 1 2 DN80 1425 257 1885 2095 665 CBU145 80B 063 G2 1 2 DN80 1425 257 1885 2135 666 CBU145 80B 073 G2 1 2 DN80 1425 257 1885 2135 675 CBU145 80B 084 G2 1 2 DN80 1425 257 1885 2135 703 CBU145 80B 094 G2 1 2 DN80 1425 257 1885 2135 748 CBU145 80B 104 G2 1 2 DN8...

Страница 12: ...ht information The compact booster unit is attached to wooden rails and wrapped in foil for transport and temporary storage All connection interfaces have protective lids Figure 6 Transporting the entire system Figure 7 Dividing the entire system for transportation Danger Danger for persons near by systems and the the environment that arises from the non intented use of the compact booster unit Op...

Страница 13: ...ways install pipelines so that they are free of tension The use of compensators with tie bars refer to the accessories section is recommended Caution Overflow not connected ª Danger of flooding the installation room Lead the overflow line to a drain with adequate dewatering capacity connection DN150 If kompensators are used to damper vibrations their durability has to be ascertained Compensators h...

Страница 14: ...on protection IEC 60079 DIN VDE 0165 Faulty mains connection ª Damage to the electricity network short circuit Observe the conditions for technical connections of the local power supply companies Wrongly wired connections ª Destruction of electrical electronic components Work on electrical equipment may only be performed by specia list electric technicians Improperly connected wiring and lines e g...

Страница 15: ...fer to Chapter 4 If the switch on pressure is set to the wrong value it has to be changed as described in the pressure switch manual 11 Slowly close the shut off valve of the output and use the pressure guage to check if the system shuts off when the switch off pressure is reached refer to Chapter 4 If the switch off pressure is set to the wrong value it has to be changed as described in the instr...

Страница 16: ...m3 h and 14 l 50 m3 h with each further second Figure 12 Determining the flushing time 7 3 1 5 Check if the water shortage dry running protection is functioning 7 4 Switching the system on 1 Secure the shut off valves of the in and output against being closed 2 Operate the main switch to supply the system with voltage The green light goes on to signal standby mode 7 5 Start up checklist Refer to t...

Страница 17: ...e pump from the power supply Warning Hot surfaces of the pump housing ª Danger of burning The pump housing has to be at ambient temperature Warning Inappropriate lifting moving of heavy modules or components ª Personal and property damage When moving heavy modules or components use suitable transport devices lifting devices and lifting accessories Warning Unqualified persons working on the compact...

Страница 18: ...ogen Caution Dry running causes increased wear ª Damage to the pump unit Never operate the pump unit when it is empty Never close the shut off valve in the suction line and or supply line during operation Caution Exceeding the permissible temperature for the pumped medium ª Damage to the pumps Operation is not permitted with closed shut off valves over longer periods of time overheating of pump me...

Страница 19: ...y may cause Reinstall safety equipment and protective devices and activate them again immediately after work on the system has been completed Before starting up again observe the start up checklist Observe the instructions for the membrane pressure vessel Danger Filling wrong gas in expansion vessel ª Danger of poisoning Only fill the pressure pad with nitrogen Caution Precharge pressure too high ...

Страница 20: ...fective replace Instructions for the pump x Buffer tank is not full Check the water level in the buffer tank x x x x x x The system check valve is defective check and replace if necessary Instructions for the check valves x x x x x More water is removed than stated in the ordering data Consult the manufacturer x The motor protection switch is activated it is set wrong or the pump is stuck Compare ...

Страница 21: ...ster unit ª Danger to life The compact booster unit has to be voltage free during disas sembly Turning off the system with the motor protection switch does not securely shut off the motor inlet lines Only perform maintenance work on the compact booster unit if you are sure that the compact booster unit is free of power Secure the compact booster unit against being switched on unintentionally Dange...

Страница 22: ...07B DN50 0904091 Motitec 1508B DN50 0904092 Motitec 1509B DN50 0904093 Motitec 1510B DN50 0904094 Motitec 2507 DN65 0904095 Motitec 4003 2 DN80 0904130 Motitec 4003 DN80 0904131 Motitec 4004 2 DN80 0904132 Motitec 4004 DN80 0904133 Motitec 4005 2 DN80 0904134 Motitec 4005 DN80 0904135 Motitec 4006 2 DN80 0904136 Motitec 4006 DN80 0904137 2 Pressure switch MCS 22 alle 0904106 3 Solenoid valve 1 2 a...

Страница 23: ...ls then the TÜV has to be informed also The operating company or their customer herewith certifies to be fully trained in operation and maintenance of the compact booster unit The circuit diagrams and instructions were also delivered 1 Compact booster unit Series Size Serial number Order number 2 Customer Operating site Customer Operating site Name Address 3 operating data refer to circuit diagram...

Страница 24: ... handling The following safety precautions regarding rinsing medium residual fluids and their disposal are required We ensure that the above information is correct and complete and delivery will be made according to statutory requirements Type Order number Order item number3 Delivery date Range of application Pumped medium3 radioactive explosive corrosive poisonous hazardous to health biohazard fl...

Страница 25: ...le water this central booster unit requires frequent maintenace contucted by enabled personal which needs to be documented after compleshion This compact booster unit is subject to the standards for drinking water and guidelines for maintenance therein and have to be maintained regularly by qua lified personnel and the results have to be documented Date Operating company Name Signature ...

Страница 26: ...1 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland by its Authorised Representative Honeywell GmbH MU1H 1375GE23 R1014 Subject to change without notice 2014 Honeywell GmbH ...

Отзывы: