Honeywell C7015A Скачать руководство пользователя страница 8

INSTALLATION

CLEARANCE

Make sure there will be enough mom to easily mount the

sight pipe, flame detector, and all required accessories, and to
remove th e 

flame 

detecto r for troubleshooting and servicing.

INSTALLING THE SIGHT PIPE

Thelocationofthesightpipeisthemostcriticalpartofthe

installation. A 

 in. black iron sight pipe is recommended.

Do 

 

 a stainless steel or galvanized pipe because its

internal surface blackens with use as deposits from the
combustion chamber accumulate on it. Initially, its shiny
intemalsurfacereflectsinharedradiation, whichcouldresult
in a satisfactory flame signal even though the pipe may be
improperly located. As it blackens, less 

 radiation is

reflected and the 

 signal becomes marginal.

Because no two situations 

 the same, the length and

sighting angle of the pipe must be determined at the time and

placeofinstallation.Generally,itisdesirabletohavethesight
pipe tilting downward to prevent soot or dirt buildup.

PREPARE HOLE IN WALL OF COMBUSTION
CHAMBER

Form a hole of the proper diameter for the sight pipe in the

the 

hole (Fig. 9) to leave room for small adjustments of the

sighting angle. The taper of the hole should be about 1 in. for
every 3 in. 

 mm for every 76.2 mm] of wall thickness.

INSTALLING ACCESSORIES

It may be necessary or desirable to install accessories

between the sight pipe and the detector. This section 
scribes the installation of these accessories.

SIGHT PIPE VENTILATION

 may be necessary to ventilate the sight pipe to cool the

detector.

For a negative pressure combustion chamber, drilling a

few holes in 

 section of the sight pipe outside of the

combustion chamber allows air at atmospheric pressure to
flow through the sight pipe into the chamber. A perforated
pipe nipple between the sight pipe and the flame detector can
also be used. See Fig. 7.

For a positive pressure combustion chamber, connect a

supply of pressurized air from the burner blower to flow
throughthesightpipeintothechamber.Theairpressuremust
be greater than the chamber pressure.

Fig. 

 air 

cooling.

mounting details, refer to form 60-0361 for the 118367A
Swivel Mount)

REDUCER BUSHING

To mount the detector on a 

 in. sight pipe, 

if replacing a 

 lead 

 detector, 

install a

 Reducer Bushing (Fig. 1).

 PLATE

To reduce the detector field-of-view, and restrict it to the

intersection of the pilot and main flame, or to a small area of
hotrefractory (see Fig.   install a 105 134 Orifice Plate. The

 plate can be inserted into a standard 

 in. pipe

coupling (Fig. 1) or into the seal-off adapter, if used.

MOUNTING SIGHT PIPE

Thmadoneendofthepipetofitthemountingcollaronthe

detector (or an accessory, if used, see Fig. 1). Cut the pipe to
the desired length (as 

 

 practical). T o 

avoid conducting

excessive heat back to the lead 

 photocell, the sight

pipeshould not extendmore than halfway 

into 

the refractory.

Tack weld 

 pipe to the wall in a trial position (Fig. 9)

Do

 permanently weld the sight pipe in place until ajter

completing the Adjustments and Checkout, page 10.

NOTE: If you use a Swivel Mount (part no. 

 and

yo u 

arepositive 

about the location and sighting angle, you

can permanently weld the pipe.

PIPE NIPPLE

A   in. pipe nipple, 6 to 8 in.   152 to 203 mm] long, can

be inserted between the sight pipe and the 

 Mount

(Fig.   to help cool the lead 

 cell. Usin g 

the 

pip e 

nipple

will also reduce the viewing area of the detector, see Table 2

or 3).

SEAL-OFF ADAPTER

To protect 

 detector from hot gases, install a 105 172A

Seal-Off Adapter (Fig. 1). The adapter has a glass window
that prevents hot gases from reaching the lead sulfide 
cell.

HEAT BLOCK

To insulate the detector from sight pipe temperatures

above 125” F 

 

 install a 105061 Heat Block (Fig. 1).

The device is made of nonheat-conductive, laminated plastic
that prevents heat 

 being conducted from the sight pipe

to the detector. It can withstand temperatures up to 250” F

 

DETECTOR PIPE NIPPLE

PIPE TEE

SIGHT
PIPE 

MOUNTING THE DETECTOR

Before mounting the 

 install the lead sulfide

photocell (if not installed already).

COOLING AIR
APPLIED UNDER

Unscrew the bushing from the cap, plu

the photocel l into

the 

cell mount, and screw the bushing back into the cap (Fig.

8). The bushing also includes a 

 lens to 

available radiation on the photocell face.

Mount the 

 Detector onto the sight pipe, heat

block, orotheraccessory (Figs. 1 and 9). Screw the mounting
collar onto the sight pipe or accessory.

SWIVEL MOUNT

To facilitate flame sighting, a Swivel Mount (part no.

 is available. The Swivel Mount requires a reducer

of the proper size to mount it onto the sight pipe. (For

8

Содержание C7015A

Страница 1: ...lot W Models are available with leadwire lengths of 30 flame and or the main burner flame 48 and 96 inches 0 76 1 22 2 64 m Mounts easily on a standard 314 inch sight pipe The lead sulfide photocell plugs into an electrical socket in the C OlSA assembly and is field re placeable The lead sulfide photocell s sensitivity to infrared W Flexible metal cable protects and electrically shields the detect...

Страница 2: ...um at the lead sulfide photocell MOUNTING C7015A Mount knurled collar with 3 4 14 NPSM in ternal threads for mounting on a standard 3 4 in pipe see fig 1 104662DLeadSulfidePhotocell twoleadsforinserting into socket in C7015A see Fig 8 TABLE l MODELS AVAILABLE With 0 125 in 3 175 mm diameter hexagonal orifice to reduce the detector field of view insulate the detector from sight pipe temperatures hi...

Страница 3: ...ethedetectorfromsightpipe hot gases from reaching the lead sulfide photocell 390427A Reducer Bushing to mount the detector on a temperatures higher than 125 F 52 C and up to lf2 in sight pipe specijically to replaceFireyeTM lead suljia2 infraredflame detectors Hookup Cable 250 F 121 Cl R1298020 2 wire heat and moisture resistant No 20 AWG Teflon TFE insulated ratedupto400 F 204 C for continuous du...

Страница 4: ...n is the basis of a reliable flame safeguard installation Refer to the burner manufac turer instructions and instructions below Carefully follow instructions for the best possible flame detector application BASIC REQUIREMENTS Because all flames produce infrared radiation a C7015A Infrared lead sulfide Flame Detector can be used to prove the presence of a flame in a combustion chamber The detector ...

Страница 5: ... length ening the sight pipe 2 reducing the diameter of the sight pipe and 3 installing an orifice plate in front of the photo cell Combinations of these methods can be used Fig P Methods of reducing C7015A Detector field of view AREA M 0 g j___ UNRESTRICTED VIEW 3 BY LENGTHENING THE SIGHT PIPE CHANGING PIPE LENGTH OR SIZE DIAMETER Theeffectorchangingthelengthofthesightpipeisshown in Tables 2 and ...

Страница 6: ...75 mm diameterorifice is4in 101 6mm andfromtheorificetotheflamejunction or refractory is 36 in 914 4 mm the dieter of the sighted area is 2 4 in 70 mm Fig 3 shows how a typical orifice plate restricts the view of a small area around the flame junction TABLE ADIAMEXER OF AREA SIGHTED THROUGH ORIFICE IN IN 6 1 1 1 6 I 2 1 2 6 3 2 TABLE 5 DIAMETER OF AREA SIGHTED THROUGH ORIFICE IN MM Fig 3 4sing ori...

Страница 7: ...efractory Fig 5 or at the floor of the combustion chamber Fig 6 SIGHTING SUMMARY When sighting the detector two important factors to consider are 1 proper sighting of the flame being detected normally the pilot main Rame junction and 2 avoiding hot refractory sighting A typical sighting arrangement is shown in Fig 4 The detector is aimed at the intersection of the pilot and main flames and at a re...

Страница 8: ...cing a FireyeW lead sulfuie detector install a 390427 AReducer Bushing Fig 1 ORIFICE PLATE To reduce the detector field of view and restrict it to the intersection of the pilot and main flame or to a small area of hotrefractory see Fig 3 install a 105 134 Orifice Plate The or e plate can be inserted into a standard 3 4 in pipe coupling Fig 1 or into the seal off adapter if used MOUNTING SIGHT PIPE...

Страница 9: ...feguardprimarycontrol oratleast 194 F 90 C if used with a flame safeguard programming control 6 For splicing in high temperature installations use Honeywell specification no R1298020 or equivalent for the F leadwire This wire is rated up to 400 F 204 Cl for continuous duty It is tested for operation up to 600 volts and breakdown up to 7500 volts For the other leadwire use moisture resistant no 14 ...

Страница 10: ...ufacturer instructions or flame safeguatd control instructions Refer to Table 6 for the minimum acceptable flame currents for the amplifiers and associated flame safeguard controls With the flame detector installed and the burner running adjust the sighting position of the detector for optimum flame signal The R7748B AMRLI CHECKTM R7848A and R7848B AMPLI CHECKTM amplifiersusedwiththeBCS7700and 780...

Страница 11: ...ng section Fig 12 Measuring microamp flame Signal PLUG IN FLAME SIGNAL AMPLIFIER I W136A SELECTOR TEST METER SWITCH 196146 METER CONNECTOR RED CONNECTOR CK CONNECTOR M E T E R LEAD El 208 Fig K Measuring BCS 7700 Flame Safeguard Control flame signal voltage PROBES ECS 7700 CHASSIS MODULE FOOTMOUNT E2512A Fig 14 Measuring 7800 SERIES Flame Safeguard Control flame signal voltage TABLE 6 FLAME SIGNAL...

Страница 12: ...ractory reaches its maximum temperature If the installation has a multifuel burner burn the fuel most likely to reflect bend or obscure the hot refractory s steady infrared radiation burn 12 solids instead of liquids or liquids instead of gases When the maximum refractory temperature is reached close all manual fuel shutoff valves or open theelectricalcircuit of all automatic fuel valves Visually ...

Страница 13: ...BLESHOOTING PROCEDURES Firstperfonn thePreliminary Inspection Then follow the applicable procedures for either a low reading or a zero reading on the flame signal meter After reinstalling the detector recheck the meter reading Adjust the position of the detector to try to obtain the proper fIame signal If the procedures are completed and a satisfactory flame signal cannot be obtained replace the d...

Страница 14: ...d Checkout page 11 PERIODIC MAINTENANCE 1 Clean the focusing lens andsightpipe when necessary Remove the detector and use a soft clean cloth lhe lens does not require removal to clean it If it is broken or damaged or itiscoatedwithasubstancethatcannotbecleanedoff replace the 110634A Bushing which includes the focusing lens 2 Keep the flame detection system adjusted for the smoothest most reliable ...

Страница 15: ...Flame Detector and accessories in in mm 3 Fig 2 Methods of reducing C7015A Infrared Flame Detector field of view 5 Fig 3 Using orifice plate to restrict detector field of view to intersection of pilot and main flame or to small area of hot refractory 6 Fig 4 C7015A Infrared Flame Detector aimed at side wall of combustion chamber 7 Fig 5 C7015A Infrared Flame Detector aimed at a point above refract...

Отзывы: