Honeywell C7015A Скачать руководство пользователя страница 11

ADJUSTMENTS AND CHECKOUT

and associated flame safeguard controls.

Move the detector and 

sight 

pipe around to sight the flame

at various positions and angles. Try to get a maximum steady
meter reading. The signal must be above the minimum
acceptable current/voltage listed in Table 6.

Measure the 

 signal for the pilot alone, the main

burner flame alone, and both together (unless monitoring
only the pilot 

 when using an intermittent pilot, or only

 burner 

flame 

when using direct spark ignition). Also

measure the flame signal at high and low firing rates and
while modulating in between (as applicable). With the detec-

tor in its final position, all required 

 signals must be

steady and as specified in Table 

6. If you 

cannot obtain the

proper signals, refer to the Troubleshooting section.

Fig. 

 

 flame Signal.

PLUG-IN FLAME

SIGNAL AMPLIFIER

I

SELECTOR

TEST 

SWITCH,

196146 METER

CONNECTOR

RED CONNECTOR

CK CONNECTOR

M E T E R ‘

LEAD

El 208

Fig. 

 BCS 7700 Flame Safeguard

Control flame signal voltage.

PROBES

 7700 

CHASSIS MODULE 

Fig. 

 7800 SERIES Flame

Safeguard Control flame signal voltage.

TABLE 6-FLAME SIGNAL

 Minimum   Maximum   Minimum   Maximum

Flame 

Acceptable Expected Acceptable

Expected

Signal Steady Current Current Steady Voltage

Voltage

Amplifier Flame Safeguard Control (microamp) (microamp)

 

2.25 5.0

 

 

3.5 5.0

 

 

4.0 5.5

BCS 7700 2.2

4.98

 

1.25 5.0

 

 

 

1.25 5.0

 

 

 

60-2306-5

Содержание C7015A

Страница 1: ...lot W Models are available with leadwire lengths of 30 flame and or the main burner flame 48 and 96 inches 0 76 1 22 2 64 m Mounts easily on a standard 314 inch sight pipe The lead sulfide photocell plugs into an electrical socket in the C OlSA assembly and is field re placeable The lead sulfide photocell s sensitivity to infrared W Flexible metal cable protects and electrically shields the detect...

Страница 2: ...um at the lead sulfide photocell MOUNTING C7015A Mount knurled collar with 3 4 14 NPSM in ternal threads for mounting on a standard 3 4 in pipe see fig 1 104662DLeadSulfidePhotocell twoleadsforinserting into socket in C7015A see Fig 8 TABLE l MODELS AVAILABLE With 0 125 in 3 175 mm diameter hexagonal orifice to reduce the detector field of view insulate the detector from sight pipe temperatures hi...

Страница 3: ...ethedetectorfromsightpipe hot gases from reaching the lead sulfide photocell 390427A Reducer Bushing to mount the detector on a temperatures higher than 125 F 52 C and up to lf2 in sight pipe specijically to replaceFireyeTM lead suljia2 infraredflame detectors Hookup Cable 250 F 121 Cl R1298020 2 wire heat and moisture resistant No 20 AWG Teflon TFE insulated ratedupto400 F 204 C for continuous du...

Страница 4: ...n is the basis of a reliable flame safeguard installation Refer to the burner manufac turer instructions and instructions below Carefully follow instructions for the best possible flame detector application BASIC REQUIREMENTS Because all flames produce infrared radiation a C7015A Infrared lead sulfide Flame Detector can be used to prove the presence of a flame in a combustion chamber The detector ...

Страница 5: ... length ening the sight pipe 2 reducing the diameter of the sight pipe and 3 installing an orifice plate in front of the photo cell Combinations of these methods can be used Fig P Methods of reducing C7015A Detector field of view AREA M 0 g j___ UNRESTRICTED VIEW 3 BY LENGTHENING THE SIGHT PIPE CHANGING PIPE LENGTH OR SIZE DIAMETER Theeffectorchangingthelengthofthesightpipeisshown in Tables 2 and ...

Страница 6: ...75 mm diameterorifice is4in 101 6mm andfromtheorificetotheflamejunction or refractory is 36 in 914 4 mm the dieter of the sighted area is 2 4 in 70 mm Fig 3 shows how a typical orifice plate restricts the view of a small area around the flame junction TABLE ADIAMEXER OF AREA SIGHTED THROUGH ORIFICE IN IN 6 1 1 1 6 I 2 1 2 6 3 2 TABLE 5 DIAMETER OF AREA SIGHTED THROUGH ORIFICE IN MM Fig 3 4sing ori...

Страница 7: ...efractory Fig 5 or at the floor of the combustion chamber Fig 6 SIGHTING SUMMARY When sighting the detector two important factors to consider are 1 proper sighting of the flame being detected normally the pilot main Rame junction and 2 avoiding hot refractory sighting A typical sighting arrangement is shown in Fig 4 The detector is aimed at the intersection of the pilot and main flames and at a re...

Страница 8: ...cing a FireyeW lead sulfuie detector install a 390427 AReducer Bushing Fig 1 ORIFICE PLATE To reduce the detector field of view and restrict it to the intersection of the pilot and main flame or to a small area of hotrefractory see Fig 3 install a 105 134 Orifice Plate The or e plate can be inserted into a standard 3 4 in pipe coupling Fig 1 or into the seal off adapter if used MOUNTING SIGHT PIPE...

Страница 9: ...feguardprimarycontrol oratleast 194 F 90 C if used with a flame safeguard programming control 6 For splicing in high temperature installations use Honeywell specification no R1298020 or equivalent for the F leadwire This wire is rated up to 400 F 204 Cl for continuous duty It is tested for operation up to 600 volts and breakdown up to 7500 volts For the other leadwire use moisture resistant no 14 ...

Страница 10: ...ufacturer instructions or flame safeguatd control instructions Refer to Table 6 for the minimum acceptable flame currents for the amplifiers and associated flame safeguard controls With the flame detector installed and the burner running adjust the sighting position of the detector for optimum flame signal The R7748B AMRLI CHECKTM R7848A and R7848B AMPLI CHECKTM amplifiersusedwiththeBCS7700and 780...

Страница 11: ...ng section Fig 12 Measuring microamp flame Signal PLUG IN FLAME SIGNAL AMPLIFIER I W136A SELECTOR TEST METER SWITCH 196146 METER CONNECTOR RED CONNECTOR CK CONNECTOR M E T E R LEAD El 208 Fig K Measuring BCS 7700 Flame Safeguard Control flame signal voltage PROBES ECS 7700 CHASSIS MODULE FOOTMOUNT E2512A Fig 14 Measuring 7800 SERIES Flame Safeguard Control flame signal voltage TABLE 6 FLAME SIGNAL...

Страница 12: ...ractory reaches its maximum temperature If the installation has a multifuel burner burn the fuel most likely to reflect bend or obscure the hot refractory s steady infrared radiation burn 12 solids instead of liquids or liquids instead of gases When the maximum refractory temperature is reached close all manual fuel shutoff valves or open theelectricalcircuit of all automatic fuel valves Visually ...

Страница 13: ...BLESHOOTING PROCEDURES Firstperfonn thePreliminary Inspection Then follow the applicable procedures for either a low reading or a zero reading on the flame signal meter After reinstalling the detector recheck the meter reading Adjust the position of the detector to try to obtain the proper fIame signal If the procedures are completed and a satisfactory flame signal cannot be obtained replace the d...

Страница 14: ...d Checkout page 11 PERIODIC MAINTENANCE 1 Clean the focusing lens andsightpipe when necessary Remove the detector and use a soft clean cloth lhe lens does not require removal to clean it If it is broken or damaged or itiscoatedwithasubstancethatcannotbecleanedoff replace the 110634A Bushing which includes the focusing lens 2 Keep the flame detection system adjusted for the smoothest most reliable ...

Страница 15: ...Flame Detector and accessories in in mm 3 Fig 2 Methods of reducing C7015A Infrared Flame Detector field of view 5 Fig 3 Using orifice plate to restrict detector field of view to intersection of pilot and main flame or to small area of hot refractory 6 Fig 4 C7015A Infrared Flame Detector aimed at side wall of combustion chamber 7 Fig 5 C7015A Infrared Flame Detector aimed at a point above refract...

Отзывы: