Honeywell C7015A Скачать руководство пользователя страница 13

ADJUSTMENTS AND CHECKOUT 

TROUBLESHOOTING

 CAUTION

FINAL CHECKOUT

Before putting the burner into service, check out the

installation by using 

 Checkout procedures in the instruc-

tions for the appropriate flame safeguard control. After
completing the checkout, run the burner through at least one
complete cycle to verify proper operation.

Do not put the system into operation until all
Checkout tests in the instructions for the appropri-
ate flame safeguard control and any specified in the
burner installation instructions are satisfactorily
completed.

Troubleshooting

 CAUTION

 

 

1. Be extremely careful while troubleshooting the

detector; line voltage is present on some of the
terminals on the wiring 

 or 

terminal strip

when power is on.

2. Open the master switch to disconnect power

before removing or installing the detector, there
may be more than one disconnect involved.

If you cannot obtain a satisfactory flame signal while

adjusting the sighting position of the detector, follow these
procedures. If you encounter other problems in the system,
refer to Troubleshooting in the instructions for the appropri-
ate flame safeguard control.

EQUIPMENT REQUIRED

1. 

300 

 scale.

2. Microammeter (Honeywell 

 or equivalent)

with 0 to 25 microampdc range.

3. 

 196146, or 117053

Meter Connector Plug or equivalent (required for some
meters).

4. A volt-ohm meter with a zero to 5 or 10 Vdc scale and

a sensitivity of 20,000 ohm/volt is suggested for 
control flame signal measurements. If the control has the

Keyboard Display Module option, flame voltage is displayed
on the module.

5. A one 

 meter with a zero to 5 or 10 Vdc

scale is recommended for 7800 SERIES control flame volt-
age measurements. If the control has the Keyboard Display
Module option, flame voltage is displayed on the module.

6. Replacement parts-see Specifications.

TROUBLESHOOTING PROCEDURES

Firstperfonn 

 Inspection. Then follow the

applicable procedures for either a low reading or a zero
reading on the flame signal meter. After reinstalling the
detector, recheck the meter reading. Adjust the position of the
detector to try to obtain the proper 

 signal. If the

procedures are completed and a satisfactory flame signal
cannot be obtained, replace the detector.

PRELIMINARY INSPECTION

1.

 the flame is properly adjusted and is not

too lean.

2. Checkfortheproperlinevoltage. Makesurethemaster

switch is closed, connections are correct, and power supply
is of the correct voltage and frequency.

3. Check the detector wiring for defects including:

. incorrect connections.

wrong type or size of wire.

deteriorated wire.

open circuits.

short circuits.

leakage paths caused by moisture, soot, or dirt.

4. With the burner running, check the temperature at the

detector. If it exceeds 125” F 

 

add additional insulation between the wall of the
combustion chamber and the detector.
add a shield or screen to reflect radiated heat away
from the detector.
add cooling (refer to Sight Pipe Ventilation, see
Installation).

PROCEDURE FOR A LOW METER READING

1. Remove the detector and clean the focusing lens 

a soft, clean cloth.

2. If the focusing lens is broken or damaged, or if it is

coated with a substance that cannot be cleaned off, replace the

 Bushing (which includes the focusing lens).

3. Clean the inside of the sight pipe before reinstalling the

detector.

4. If the meter reading is still too low, replace the lead

sulfide cell (Fig. 8).

5. If the meter reading is still too low, replace the plug-in

amplifier.

6. If you still cannot obtain a proper flame signal, replace

the 

 Infrared Flame Detector.

PROCEDURE FOR A ZERO METER READING

1. Replace the lead sulfide cell (Fig. 8). Then recheck the

flame signal.

2. If there is still no flame signal, replace the plug-in

amplifier.

3. If you still cannot obtain a meter reading, replace the

entire 

 Infrared Flame Detector.

IMPORTANT: 

At the completion of troubleshooting, be

sure to perform the Adjustments and Checkout, page

10.

13 60-2306-5

Содержание C7015A

Страница 1: ...lot W Models are available with leadwire lengths of 30 flame and or the main burner flame 48 and 96 inches 0 76 1 22 2 64 m Mounts easily on a standard 314 inch sight pipe The lead sulfide photocell plugs into an electrical socket in the C OlSA assembly and is field re placeable The lead sulfide photocell s sensitivity to infrared W Flexible metal cable protects and electrically shields the detect...

Страница 2: ...um at the lead sulfide photocell MOUNTING C7015A Mount knurled collar with 3 4 14 NPSM in ternal threads for mounting on a standard 3 4 in pipe see fig 1 104662DLeadSulfidePhotocell twoleadsforinserting into socket in C7015A see Fig 8 TABLE l MODELS AVAILABLE With 0 125 in 3 175 mm diameter hexagonal orifice to reduce the detector field of view insulate the detector from sight pipe temperatures hi...

Страница 3: ...ethedetectorfromsightpipe hot gases from reaching the lead sulfide photocell 390427A Reducer Bushing to mount the detector on a temperatures higher than 125 F 52 C and up to lf2 in sight pipe specijically to replaceFireyeTM lead suljia2 infraredflame detectors Hookup Cable 250 F 121 Cl R1298020 2 wire heat and moisture resistant No 20 AWG Teflon TFE insulated ratedupto400 F 204 C for continuous du...

Страница 4: ...n is the basis of a reliable flame safeguard installation Refer to the burner manufac turer instructions and instructions below Carefully follow instructions for the best possible flame detector application BASIC REQUIREMENTS Because all flames produce infrared radiation a C7015A Infrared lead sulfide Flame Detector can be used to prove the presence of a flame in a combustion chamber The detector ...

Страница 5: ... length ening the sight pipe 2 reducing the diameter of the sight pipe and 3 installing an orifice plate in front of the photo cell Combinations of these methods can be used Fig P Methods of reducing C7015A Detector field of view AREA M 0 g j___ UNRESTRICTED VIEW 3 BY LENGTHENING THE SIGHT PIPE CHANGING PIPE LENGTH OR SIZE DIAMETER Theeffectorchangingthelengthofthesightpipeisshown in Tables 2 and ...

Страница 6: ...75 mm diameterorifice is4in 101 6mm andfromtheorificetotheflamejunction or refractory is 36 in 914 4 mm the dieter of the sighted area is 2 4 in 70 mm Fig 3 shows how a typical orifice plate restricts the view of a small area around the flame junction TABLE ADIAMEXER OF AREA SIGHTED THROUGH ORIFICE IN IN 6 1 1 1 6 I 2 1 2 6 3 2 TABLE 5 DIAMETER OF AREA SIGHTED THROUGH ORIFICE IN MM Fig 3 4sing ori...

Страница 7: ...efractory Fig 5 or at the floor of the combustion chamber Fig 6 SIGHTING SUMMARY When sighting the detector two important factors to consider are 1 proper sighting of the flame being detected normally the pilot main Rame junction and 2 avoiding hot refractory sighting A typical sighting arrangement is shown in Fig 4 The detector is aimed at the intersection of the pilot and main flames and at a re...

Страница 8: ...cing a FireyeW lead sulfuie detector install a 390427 AReducer Bushing Fig 1 ORIFICE PLATE To reduce the detector field of view and restrict it to the intersection of the pilot and main flame or to a small area of hotrefractory see Fig 3 install a 105 134 Orifice Plate The or e plate can be inserted into a standard 3 4 in pipe coupling Fig 1 or into the seal off adapter if used MOUNTING SIGHT PIPE...

Страница 9: ...feguardprimarycontrol oratleast 194 F 90 C if used with a flame safeguard programming control 6 For splicing in high temperature installations use Honeywell specification no R1298020 or equivalent for the F leadwire This wire is rated up to 400 F 204 Cl for continuous duty It is tested for operation up to 600 volts and breakdown up to 7500 volts For the other leadwire use moisture resistant no 14 ...

Страница 10: ...ufacturer instructions or flame safeguatd control instructions Refer to Table 6 for the minimum acceptable flame currents for the amplifiers and associated flame safeguard controls With the flame detector installed and the burner running adjust the sighting position of the detector for optimum flame signal The R7748B AMRLI CHECKTM R7848A and R7848B AMPLI CHECKTM amplifiersusedwiththeBCS7700and 780...

Страница 11: ...ng section Fig 12 Measuring microamp flame Signal PLUG IN FLAME SIGNAL AMPLIFIER I W136A SELECTOR TEST METER SWITCH 196146 METER CONNECTOR RED CONNECTOR CK CONNECTOR M E T E R LEAD El 208 Fig K Measuring BCS 7700 Flame Safeguard Control flame signal voltage PROBES ECS 7700 CHASSIS MODULE FOOTMOUNT E2512A Fig 14 Measuring 7800 SERIES Flame Safeguard Control flame signal voltage TABLE 6 FLAME SIGNAL...

Страница 12: ...ractory reaches its maximum temperature If the installation has a multifuel burner burn the fuel most likely to reflect bend or obscure the hot refractory s steady infrared radiation burn 12 solids instead of liquids or liquids instead of gases When the maximum refractory temperature is reached close all manual fuel shutoff valves or open theelectricalcircuit of all automatic fuel valves Visually ...

Страница 13: ...BLESHOOTING PROCEDURES Firstperfonn thePreliminary Inspection Then follow the applicable procedures for either a low reading or a zero reading on the flame signal meter After reinstalling the detector recheck the meter reading Adjust the position of the detector to try to obtain the proper fIame signal If the procedures are completed and a satisfactory flame signal cannot be obtained replace the d...

Страница 14: ...d Checkout page 11 PERIODIC MAINTENANCE 1 Clean the focusing lens andsightpipe when necessary Remove the detector and use a soft clean cloth lhe lens does not require removal to clean it If it is broken or damaged or itiscoatedwithasubstancethatcannotbecleanedoff replace the 110634A Bushing which includes the focusing lens 2 Keep the flame detection system adjusted for the smoothest most reliable ...

Страница 15: ...Flame Detector and accessories in in mm 3 Fig 2 Methods of reducing C7015A Infrared Flame Detector field of view 5 Fig 3 Using orifice plate to restrict detector field of view to intersection of pilot and main flame or to small area of hot refractory 6 Fig 4 C7015A Infrared Flame Detector aimed at side wall of combustion chamber 7 Fig 5 C7015A Infrared Flame Detector aimed at a point above refract...

Отзывы: