BCU 460, BCU 465 · Edition 11.19
64
Parameters
11 Parameters
Any changes to parameters will be saved to the parameter chip card.
11 .1 Application parameters
Name
Parameter
Value range Description
Factory default
settings
Burner 1 FS1 flame signal switch-off
A001
2 – 20
Burner 1 flame signal switch-off threshold in
µ
A
(depending on I004)
2 – 20
µ
A where
I004 = 0,
5 – 20
µ
A where
I004 = 1,
5
µ
A where
I004 = 2
Burner 2 flame signal switch-off threshold FS2
A002
2 – 20
Burner 2 flame signal switch-off threshold in
µ
A
(depending on I004)
2 – 20
µ
A where
I004 = 0, 5 or 7,
5 – 20
µ
A where
I004 = 1, 3 or 8,
5
µ
A where
I004 = 2, 4 or 6
Flame simulation check in standby position
A003
0
1
Off
On
0
A006
0
3
6
Off
Continuous operation
Burner 1 UVS Burner 2 ionization
0
A007
1
2
3
1 start-up attempt
2 start-up attempts
3 start-up attempts
1
A009
0
1
4
Off
Burner 1
Burner 1 max. 5 x in 15 min.
0
Delayed low air pressure protection
A016
0
1
Off
On
1
A019
0; 1; 2; 3; 4 Time in seconds
1
A028
0 – 250
Time in seconds
0
A034
0 – 6000
Time in seconds
6000
A036
0 – 250
Time in seconds
0
A039
0 – 60
Time in seconds
0