Fieldbus communication
Inputs/Outputs
The digital input and output signals from the burner
control unit BCU are included in this module.
Input bytes (BCU
➔
PLC)
The input bytes describe the digital signals which are
transferred from the BCU to the digital inputs of the
PLC. The digital signals take up 3 bytes (24 bits).
Bit Byte n
Byte n+1
Byte n+2
Format
0
Burner 1 operating
signal
Free
Flameless
operation
BOOL
1
Burner 2 operating
signal
Free
Free
BOOL
2
BCU system fault
Air ON
Free
BOOL
3
Fault lock-out
Pre-purge ON
Free
BOOL
4
Safety shut-down
HT ON
Free
BOOL
5
Warning
Ready for
operation
Free
BOOL
6
ON
Burner 1 flame
signal
Free
BOOL
7
Manual mode
Burner 2 flame
signal
Free
BOOL
Output bytes (PLC
➔
BCU)
The output bytes describe the digital signals which
are output by the PLC to the BCU. The digital signals
to control the burner control unit BCU occupy 2 bytes
(16 bits).
Terminals 1 to 41 (dependent on parameters I061 to
I074) can be wired parallel to the bus communication.
This allows the BCU to be controlled using the digital
signals of the bus communication or the inputs at the
terminals.
Bit Byte n
Byte n+1
Format
0
Reset
1)
Auxiliary gas
BOOL
1
Burner 1 start
1)
Optional output
BOOL
2
External air ON
1)
Cooling air valve
BOOL
3
Pre-purge ON
Free
BOOL
4
Burner 2 start
1)
Free
BOOL
5
Flameless mode ON
2)
Free
BOOL
6
Free
Free
BOOL
7
Free
Free
BOOL
1) Terminals 1 to 41 (dependent on parameters I061 to I074) can
be wired parallel to the bus communication.
2) Only with BCU 465 depending on the parameter settings.
▼