BCU 370 · Edition 01.19
79
Annex
12 Annex
12 .1 Status and fault messages for PROFIBUS DP
This table can be used to program the master.
Input bytes (BCU
➔
master)
Byte 2
Byte 0, Bit 2 = 0 (Status message)
Byte 0, Bit 2 = 1 (Fault message)
0
0 Start-up position/standby
1
A0 Valve moves to Closed position
01 Flame simulation
2
01 Fan run up time
3
A1 Butterfly valve moves to Open position
4
P1 Pre-purge time
04 Start-up without flame signal
5
A2 Butterfly valve moves to Ignition position
05 Flame failure during 1
st
flame proving period
6
03 Pre-ignition time
06 Flame failure during 2
nd
safety time
7
04 1
st
safety time on start-up
07 Flame failure during 2
nd
flame proving period
8
05 1
st
flame proving period
08 Flame failure during operation
9
06 2
nd
safety time on start-up
10
07 2
nd
flame proving period
d0 Fault Air monitor break contact check
11
08 Controller enable signal
d1 Fault Air monitor make contact check
12
P9 Post-purge time
d2 Fault Air supply while butterfly valve moves to Ignition position
13
d3 Fault Air supply during pre-ignition time
14
d4 Fault Air supply during 1
st
safety time on start-up
15
d5 Fault Air supply during 1
st
flame proving period
16
d6 Fault Air supply during 2
nd
safety time on start-up
17
d7 Fault Air supply during 2
nd
flame proving period
18
d8 Fault Air supply during operation
19
dP Fault Air supply during pre-purge time
▼