BCU 370 · Edition 01.19
40
Parameters
4 Parameters
Description
Parameter
Value range
Default
Adjustable
1
)
01
0 – 25
µ
A
02
1 – 20
µ
A
1
µ
A
v
03
XX
Air monitoring during pre-purge
04
0 = Off; 1 = On
1
Air monitoring during operation
05
0 = Off; 1 = On
1
06
0 = Quick start;
1 = On each start-up
1
07
1 – 4
1
Restart after flame failure during operation
08
0 = Fault lock-out;
1 = Restart
0
Safety time during operation t
09
1; 2 s
1 s
10
0 – 250 s
0 s
11
0 – 250 s
0 s
safety time on start-up, burner/pilot burner t
12
2; 3; 5; 10 s
5 s
flame proving period, burner/pilot burner t
13
0; 2; 5; 10; 20 s
2 s
safety time on start-up, main burner t
14
0; 2; 3; 5; 10 s
3 s
flame proving period, main burner t
15
0; 2; 5; 10; 20 s
2 s
16
0 = Unlimited;
1 = Limited to 5 minutes
1
17
0 = Off; 1 = On
0
18
0 – 250 s
30 s
19
0 – 250 s
0 s
20
0 – 25 s
2 s
▼