BCU 370 · Edition 01.19
51
Parameters
4 .5 Monitoring/tightness control
4 .5 .1 Min . gas pressure monitoring
Parameter 23
Determines whether the minimum gas pressure DG
min.
is monitored.
To ensure that there is adequate gas pressure on the
burner, the pressure can be monitored using the gas
pressure monitor DG
min.
.
Monitoring takes place in the start-up position/standby,
during burner start-up or during burner operation. If
the signal is not applied, a locking warning signal is
triggered and the display shows
X
, “Fault DG
min
. in
program step X”. When the signal is applied again, the
BCU 370 attempts to restart the burner, provided the
start-up signal (
ϑ
) is applied.
The requirement for monitoring of the minimum gas
pressure is stipulated in the relevant application stand-
ard.
4 .5 .2 Digital input function
Parameter 24
Defines the function of the input on terminal 11.
Parameter 24 = 0: input has no function.
Parameter 24 = 1: monitoring of the maximum gas
pressure DG
max.
.
To ensure that the permissible gas pressure on the
burner is not exceeded, the pressure can be monitored
using the gas pressure monitor DG
max.
.
Monitoring takes place in the start-up position/standby,
during burner start-up or during burner operation. If
the signal is not applied, a fault lock-out occurs and the
display shows
X
, “Fault DG
max.
in program step X”.
Parameter 24 = 3: monitoring of the pressure switch
between V1 and V2/V3 for tightness control (only on
BCU..D3). See Function – Tightness control.