Honeywell
• 31
Communications
6.2
Control word bits
Table 15. Control Word bits
6.3
Status word bits
Table 16. Status Word bits
Bit
Name
Value = 1
Value = 0
Description
B0
Start/Stop
Start request
Stop request
Start/Stop command to
application
B2
Fault reset
Reset faults
No action
Command to reset fault
B3-B15 Not used
Bit
Name
Value = 1
Value = 0
Description
B0
Ready
Ready
Not ready
Indicates whether the drive is
ready or not
B1
Run
Running
Stop
Indicates whether the drive is
running or stopped
B2
Direction
Counterclockwise Clockwise
Indicates the rotation direc-
tion of the motor
B3
Fault
Faulted
Not faulted Indicates if a fault is active
B4
Alarm
Alarm
No alarm
Indicates if an alarm is active
B5
AtReference True
False
Reference frequency reached
B6
ZeroSpeed True
False
Motor running at zero speed
B7-B15 Not used