Programming
Honeywell
• 16
5.
Programming
Basic information on how to use the control keypad you will find in the Application Manual.
The navigation path to the fieldbus parameters may differ from application to application. The
exemplary paths below apply to the Honeywell SmartDrive.
1. First ensure that the right fieldbus protocol is selected.
2. Select
‘Fieldbus control’
as the
Remote Control Place
.
3. Choose source of reference.
4. Set fieldbus parameters (M5.7 and M5.8). See below.
5.1
BACnet MS/TP parameters and monitoring values (M5.7.3)
Code
Parameter
Min
Max
Unit
Default
ID
Description
PARAMETERS
P5.7.3.1.1
Baud rate
1
4
bd
1
Communication speed
1 = 9600
2 = 19200
3 = 38400
4 = 76800
P5.7.3.1.2
Autobauding
0
1
1
Automatic baudrate
detection
0 = Off
1 = On; The automati-
cally detected baud rate
is then shown as value
of parameter P5.7.3.1.1
P5.7.3.1.3
MAC address
1
127
1
P5.7.3.1.4
Instance number
0
65535
0
Device Object's instance
number.
0 = Automatically
gegerated
P5.7.3.1.5
Communication
time-out
0
65535
s
10
0 = Not used
Navigate: Main Menu > I/O and Hardware (M5) > RS-485 (M5.7)
OR
Ethernet
(M5.8) > Common settings (M5.7.1) > Protocol (P5.7.1.1) > Edit >
(Choose protocol)
Navigate: Main Menu > Quick Setup (M1) > Rem. Ctrl. Place (P1.15)
OR
Navigate: Main Menu > Parameters (M3) > Start/Stop Setup (M3.2) > Rem.
Ctrl. Place (P3.2.1)
Navigate: Main Menu > Parameters (M3) > References (M3.3)
Содержание BacNet protocol
Страница 1: ...Honeywell Installation and User Manual BacNet protocol for Variable Frequency Drives ...
Страница 3: ...Honeywell 1 ...
Страница 7: ...Honeywell 5 Safety ...
Страница 9: ...Honeywell 7 BACnet general info ...
Страница 11: ...Honeywell 9 BACnet technical data ...
Страница 24: ...Programming Honeywell 22 P5 7 3 2 6 STATUS WORD Shows the current Status Word that is sent to the bus ...
Страница 37: ...Honeywell 35 Fault tracing ...