BACnet installation
Figure 3.
You can use the BACnet communication protocol through Ethernet and RS485.
4.1
Prepare for use through Ethernet
Figure 4.
3
Connect the Ethernet cable (see specification on page 8) to its terminal and run
the cable through the conduit as shown in Figure 4.
NOTE:
Pay attention that the non-bending part of the connector does not exceed
40 mm in length.
Ethernet
connector
Ethernet
cable run
conduit
I/O terminal
(see larger
picture)
Grounding
bar
DIP
switches
32 33
12 13 14 15 16 17 18 19 30
B
A
RS485
terminals
21 22 23
24 25 26
1 2 3 4 5 6 7 8 9 10 11
max. 40 mm
Ethernet
cable