AQS 51/61 CO2 / TEMPERATURE SENSOR WITH BUILT-IN CONTROLLER

EN1B-0189GE51 R0102

7

Bit #

Error code

Error description

Suggested action

0

N/A

Fatal error: The yellow LED flashes con-

tinuously. The push buttons do not function.

Try to restart the sensor by turning the power off and

on again. Contact local distributor.

1

2

Reserved

2

4

Âlgorithm error: An incorrect EEPROM

configuration is indicated.

Try to restart the sensor by turning the power off and

on again. Check detailed settings and configuration

with AQS-USP software version 4.0 and higher.

Contact local distributor.

3

8

Output error: Detected errors during output

signal calculation and generation.

Check connections and output loads. Check detailed

status of outputs with AQS-USP software version 4.0

and higher.

4

16

Self diagnosis error: May indicate the need of

zero-point calibration or sensor replacement.

Check detailed self-diagnostic status with AQS-USP

software version 4.0 and higher. Contact local

distributor.

6

64

Memory error: Non-fatal error during memory

operations.

Check detailed settings and configuration with AQS-

USP software version 4.0 and higher.

7

128

Warm-up state: Is always set after power-up or

power failure. Resets after restart sequence.

If it doesn't disappear within 30 seconds, check power

stability.

NOTE:

One of the probes is out of range. Occurs, for instance, during over-exposure of the CO

2

 sensor, in which case the

error code will automatically reset when the measurement values return to normal. Could also indicate the need of

zero-point calibration. A background calibration using push button function ”bCAL” will remedy this error (a more exact

zero-point calibration using ”CAL” may be performed later, if required). If the CO

2

 readings are normal but the error

code remains, the temperature sensor might be broken.

REMARK:

If several errors are detected at the same time, the different error code numbers will be added together into one single

error code.

Maintenance

Basically speaking, the AQS51/61 is maintenance-free. An

internal self-adjusting calibration function takes care of

normal long-term drift associated with the CO

2

 sensor. To

ensure the highest accuracy, a time interval of max. five

years is recommended between CO

2

 calibrations unless

some special situations have occurred. A zero-point

calibration can be performed using the push button functions

(for AQS61), or for a complete overview, by using a PC

together with the  

AQS-USPxx software version 4.0

 (or

higher). This software and a special RS232-cable are

included in the 

AQS-F0005

 service kit

.

 The cable is to be

connected to the UART port slide connector (see Fig.9). For

changing control parameters and re-calibration (CO

2

 and

temperature), this PC tool must to be used. The check can

be done on site without interfering with the ventilation system.

If, for some reason, the printed circuit board (PCB) needs to

be removed, special precautions must be taken in order to

avoid damaging the temperature probe. When putting the

PCB back into the protective housing, the temperature probe

must be gently positioned in the small probe compartment

(see Fig. 8)!

Limited Warranty

This product has been accurately tested and examined for

proper operation. Please operate this product only in

accordance with the instructions.

The warranty period of the product against defects in work-

manship and material is one year from date of purchase by

the original owner. If the product should become defective

within this warranty period, the customer owns the right for

repair or exchange the product free of charge. Please contact

your retailer for further information.

The retailer is not responsible for any consequential loss or

damages, which may occur by reason of purchase and use

of this product. The warranty is, in any event, strictly limited

to the replacement/repair of the product.

This product is in accordance with the EMC Directive

89/336/EEC and the Low-Voltage Directive 73/23/EEC,

including amendments by the CE-marking Directive

93/68/EEC.

This product fulfills the following requirements:

 EN50081-1

 EN55011(B)

 EN50082-2

 

EN61000-4-2.-3.-4.-5. Level 3

上海君琼空调科技有限公司,021-60341366,www.shjqkt.com

Содержание AQS51

Страница 1: ...near control of e g mixed air dampers and fans The wall mounting housing has been designed with snap in features to minimize installation time The units can be directly connected to common VAV Variable Air Volume controllers Direct Digital Control DDC devices or standalone control systems The linear output functions are pre programmed as CO2 and temperature transmitters In addition the AQS51 and A...

Страница 2: ...ert dowel into the holes 3 Position the wall plate over the holes and pull the wires through the wiring opening 4 Loosely insert the mounting screws into the holes and tighten them see Fig 2 Fig 2 Mounting of the wall plate Mounting System Unit onto Wall Plate 1 Bend the wires to the top to allow wiring connections to the terminals 2 Engage first the top tabs of the sensor controller pro tection c...

Страница 3: ...ary use separate floating transformers for sensor and controller DDC system 1 Connect the correct wires to the terminals and securely tighten each terminal screw Follow the actual job wiring diagrams if available or refer to Table 2 for terminal designations A sticker is located on the inside of the terminal cover that identifies the terminals see Fig 5 All wiring must comply with local electrical...

Страница 4: ...or OUT4 when it is used as an open collector output see Table 1 If different outputs are needed for the application these have to be configured before the unit is powered up To select alternative output ranges position the four jumpers as required for the application Each jumper selection is independent from the others except in the case of the Start point selection jumper which affects both linea...

Страница 5: ...uipment Provides access to a sub menu in which output selection XX 1 4 is done by pressing MENU The selected output FOXX OUT1 4 is fixed via ENTER 2 For XX 1 2 LO always provides 2 V 4 mA regardless of the position of the start point selection jumper but voltage or current according to the position of the jumper OFF ON is true for the relay and open collector outputs FO 1 2 LO selected output is f...

Страница 6: ...d can be compared with the actual output value measured with a multimeter Test Gas Verification Insert 4 mm plastic tubing in the test gas inlet at the bottom of the wall plate The plastic tubing should be inserted as far as possible into the inlet Flow test gas at a rate of about 0 5 liter minute Check the display or OUT1 with a multimeter to read the CO2 value when it has stabilized NOTE The sen...

Страница 7: ... speaking the AQS51 61 is maintenance free An internal self adjusting calibration function takes care of normal long term drift associated with the CO2 sensor To ensure the highest accuracy a time interval of max five years is recommended between CO2 calibrations unless some special situations have occurred A zero point calibration can be performed using the push button functions for AQS61 or for ...

Страница 8: ...ker Road Böblinger Straβe 17 manufacturing P O Box 524 North York Ontario D 71101 Schönaich location certified to Minneapolis MN 55408 0524 M2H 3N7 Germany USA Canada http www honeywell com http www honeywell ca http europe hbc honeywell com EN1B 0189GE51 R0102 printed in Germany Subject to change without notice Fig 8 Positioning the temperature sensor the black dot enlargement at right 上海君琼空调科技有限...

Отзывы: