AQS 51/61 CO2 / TEMPERATURE SENSOR WITH BUILT-IN CONTROLLER

EN1B-0189GE51 R0102

4

Table 2. Electrical terminal connections for AQS51/61

Connection

terminal

Function

Electrical data

Remarks

G+

power (+)

24 Vac/dc+ (

±

20%), 3 W

2 W without output load

1

G0

power ground (-)

24 Vac/dc-

OUT1

analog output 1 (+) 0...10 Vdc or 0...20 mA

2...10 Vdc or 4...20 mA

According to positions of OUT1 and start

point of jumpers

2

OUT2

analog output 2 (+) same as output 1

According to positions of OUT2 and start

point of jumpers

2

M

signal ground (-)

connected to G0 via PTC fuse

See note 1!

Relay

normally open

contact-free relay; min. load: 1 mA / 5 V;

rated load: 0.5 A / 125 Vac, 1 A / 24 Vdc

Triggered by register OUT3

OUT4

analog output 4 (+)

or open collector

0...10 Vdc; max. 0.5 A, 60 Vdc / 40 Vac

(half-wave rectifier protection)

According to positions of OUT4. See also

notes 2 and 3!

DI1

digital input 1

closed contact current: 1 mA, open

voltage contact: max. 5 V

Do not apply any voltage to this input!

NOTE 1:

The ground terminal is used as negative power supply DC input or AC phase ground G0 (half-wave rectifier). The

signal ground M, protected by a PTC resistor, is the same as power ground G0 (permitting a ”3-wire” configuration). A

single transformer may be used for the entire system.

NOTE 2:

AQS51/61 can deliver both a voltage or a current loop for OUT1/OUT2. For OUT4 a voltage output or an open

collector output is selected with jumper OUT4. To change between voltage and current output mode the hardware

jumpers are used. There is one jumper for OUT1 and one for OUT2, so that one output can be a voltage output and

the other a current output. Both voltage output and current output can have start points 0 % (0-10 VDC or 0-20mA) or

20% (2-10 VDC or 4-20mA). The same start point is used for both outputs. See Table 1.

NOTE 3:

The open collector's current is internally returned to the G0 terminal.

Output Configurations

The sensors/controllers are supplied from the factory (unless

otherwise ordered) with 0...10 Vdc linear outputs for OUT1

and OUT2 and for OUT4 when it is used as an open collector

output (see Table 1). If different outputs are needed for the

application, these have to be configured before the unit is

powered up. To select alternative output ranges, position the

four jumpers as required for the application. Each jumper

selection is independent from the others, except in the case

of the “Start point selection” jumper, which affects both linear

outputs (i.e. OUT1 and OUT2).

Table 3. Configuration jumpers for AQS51/61

Jumper

Position

Function

0%

Jumper top position provides a 0 Vdc or 0 mA start point for OUT1 and OUT2 (0...20 mA or 0...10 V).

OUT4 has a 0 V output start point when jumper OUT4 is in the “voltage” position (0...10 V).

start point

of the

selection

jumper

20%

Jumper bottom position provides a 2 Vdc or 4 mA start point for OUT1 and OUT2 (4...20 mA or

2...10 V). OUT4 has a 0 V output start point when jumper OUT4 is in the “voltage” position (0...10 V).

current

Connection in the "current" position provides a 0/4...20 mA output range for OUT1.

OUT1

voltage

Connection in the "voltage" position provides a 0/2...10 Vdc output range for OUT1.

current

Connection in the "current" position provides a 0/4...20 mA output range for OUT2.

OUT2

voltage

Connection in the "voltage" position provides a 0/2...10 Vdc output range for OUT2.

current

Connection in the "open collector" position provides an open collector output. Max. 0.5 A, 60 Vdc /

40 Vac (half-wave rectifier).

OUT4

voltage

Connection in the "voltage" position provides a 0...10 Vdc output range for OUT4.

Push Button Operation for AQS61

This sensor has two push buttons, MENU and ESC, located

on the front panel behind the flip-down lid. The YELLOW

LED will acknowledge a successful push by a short flash.

The push button MENU is available for selection of display

value or maintenance commands, whereas ESC is available

to escape back from a selected level.

Display Modes

In the DISPLAY MODE, the push button MENU is used to

select the value to be indicated on the display: CO

2

 con-

centration and temperature (alternating), error code, CO

2

,

temperature, output 1, output 2, or output 4. After the device

is powered up, the display will always return to the default

display mode

上海君琼空调科技有限公司,021-60341366,www.shjqkt.com

Содержание AQS51

Страница 1: ...near control of e g mixed air dampers and fans The wall mounting housing has been designed with snap in features to minimize installation time The units can be directly connected to common VAV Variable Air Volume controllers Direct Digital Control DDC devices or standalone control systems The linear output functions are pre programmed as CO2 and temperature transmitters In addition the AQS51 and A...

Страница 2: ...ert dowel into the holes 3 Position the wall plate over the holes and pull the wires through the wiring opening 4 Loosely insert the mounting screws into the holes and tighten them see Fig 2 Fig 2 Mounting of the wall plate Mounting System Unit onto Wall Plate 1 Bend the wires to the top to allow wiring connections to the terminals 2 Engage first the top tabs of the sensor controller pro tection c...

Страница 3: ...ary use separate floating transformers for sensor and controller DDC system 1 Connect the correct wires to the terminals and securely tighten each terminal screw Follow the actual job wiring diagrams if available or refer to Table 2 for terminal designations A sticker is located on the inside of the terminal cover that identifies the terminals see Fig 5 All wiring must comply with local electrical...

Страница 4: ...or OUT4 when it is used as an open collector output see Table 1 If different outputs are needed for the application these have to be configured before the unit is powered up To select alternative output ranges position the four jumpers as required for the application Each jumper selection is independent from the others except in the case of the Start point selection jumper which affects both linea...

Страница 5: ...uipment Provides access to a sub menu in which output selection XX 1 4 is done by pressing MENU The selected output FOXX OUT1 4 is fixed via ENTER 2 For XX 1 2 LO always provides 2 V 4 mA regardless of the position of the start point selection jumper but voltage or current according to the position of the jumper OFF ON is true for the relay and open collector outputs FO 1 2 LO selected output is f...

Страница 6: ...d can be compared with the actual output value measured with a multimeter Test Gas Verification Insert 4 mm plastic tubing in the test gas inlet at the bottom of the wall plate The plastic tubing should be inserted as far as possible into the inlet Flow test gas at a rate of about 0 5 liter minute Check the display or OUT1 with a multimeter to read the CO2 value when it has stabilized NOTE The sen...

Страница 7: ... speaking the AQS51 61 is maintenance free An internal self adjusting calibration function takes care of normal long term drift associated with the CO2 sensor To ensure the highest accuracy a time interval of max five years is recommended between CO2 calibrations unless some special situations have occurred A zero point calibration can be performed using the push button functions for AQS61 or for ...

Страница 8: ...ker Road Böblinger Straβe 17 manufacturing P O Box 524 North York Ontario D 71101 Schönaich location certified to Minneapolis MN 55408 0524 M2H 3N7 Germany USA Canada http www honeywell com http www honeywell ca http europe hbc honeywell com EN1B 0189GE51 R0102 printed in Germany Subject to change without notice Fig 8 Positioning the temperature sensor the black dot enlargement at right 上海君琼空调科技有限...

Отзывы: