AQS 51/61 CO2 / TEMPERATURE SENSOR WITH BUILT-IN CONTROLLER

EN1B-0189GE51 R0102

6

FUNCTIONAL TEST OF THE AQS51/61 CO2 AND TEMPERATURE SENSOR

Functional Test

The unit has two LED’s - yellow and red - on the front panel

(found under the front lid). These LED’s indicate the

controller's status.

Yellow LED 

- ”Call for maintenance” is lit if an error flag has

been set or the measurement is out of range. In the case of

the AQS61, this information is also shown on the display by

the wrench icon. Any push button press, or executed main-

tenance function, is acknowledged by this LED lighting up.

Red LED

 - ”Relay active” is lit when the relay has been

activated (contact closed).

A simple and visual functional test can easily be performed.

Take a breath and blow the air from a distance of a few

centimeters onto the sensor. The sensor will detect a rapid

increase in the carbon dioxide concentration. As a result, the

red LED will light up as the CO

2

 level exceeds 1000 ppm

(sensor default setting). If the sensor is connected to a

controller, the flow of the ventilation system will eventually

increase by change of the fan speed or opening of a damper

actuator (depending on the installation/application).

In the case of the AQS61, the present output values of the

outputs OUT1, OUT2 and OUT4 can be viewed on the LCD

by pressing MENU four to six times. The displayed values are

in %FS (percent full scale) and can be compared with the

actual output value measured with a multimeter.

Test Gas Verification

Insert 4 mm plastic tubing in the test gas inlet at the bottom

of the wall plate. The plastic tubing should be inserted as far

as possible into the inlet. Flow test gas at a rate of about 0.5

liter/minute. Check the display (or OUT1 with a multimeter) to

read the CO

2

-value when it has stabilized.

NOTE:

The sensor accuracy is defined at continuous

operation (at least 3 weeks after installation).

Self Diagnostics

The system contains complete self diagnostic procedures. A

full system test is executed automatically every time the

power is turned on. In addition, the sensor probes are con-

stantly checked against failure during operation by checking

the valid dynamic measurement ranges. All EEPROM

updates (initiated by the sensor itself or by external connec-

tions) are checked by subsequent memory read back and

data comparisons.

 

These different system checks return

error bytes to the system RAM. If any error is detected, the

yellow LED will light up

 

until the error has vanished and the

error flag is reset. “Warm up” and “Out of Range” are the only

bits that are reset automatically after return to normal state.

All other error bits have to be reset manually after return to

normal state – either by pushing the MENU and ESC buttons

simultaneously for ENTER (AQS61 only) or by power off and

restart.

The error code 

number Exxx 

can be made to appear on the

LCD (AQS61) by pressing the ”MENU” push button.

Descriptions of the different codes are listed below.

上海君琼空调科技有限公司,021-60341366,www.shjqkt.com

Содержание AQS51

Страница 1: ...near control of e g mixed air dampers and fans The wall mounting housing has been designed with snap in features to minimize installation time The units can be directly connected to common VAV Variable Air Volume controllers Direct Digital Control DDC devices or standalone control systems The linear output functions are pre programmed as CO2 and temperature transmitters In addition the AQS51 and A...

Страница 2: ...ert dowel into the holes 3 Position the wall plate over the holes and pull the wires through the wiring opening 4 Loosely insert the mounting screws into the holes and tighten them see Fig 2 Fig 2 Mounting of the wall plate Mounting System Unit onto Wall Plate 1 Bend the wires to the top to allow wiring connections to the terminals 2 Engage first the top tabs of the sensor controller pro tection c...

Страница 3: ...ary use separate floating transformers for sensor and controller DDC system 1 Connect the correct wires to the terminals and securely tighten each terminal screw Follow the actual job wiring diagrams if available or refer to Table 2 for terminal designations A sticker is located on the inside of the terminal cover that identifies the terminals see Fig 5 All wiring must comply with local electrical...

Страница 4: ...or OUT4 when it is used as an open collector output see Table 1 If different outputs are needed for the application these have to be configured before the unit is powered up To select alternative output ranges position the four jumpers as required for the application Each jumper selection is independent from the others except in the case of the Start point selection jumper which affects both linea...

Страница 5: ...uipment Provides access to a sub menu in which output selection XX 1 4 is done by pressing MENU The selected output FOXX OUT1 4 is fixed via ENTER 2 For XX 1 2 LO always provides 2 V 4 mA regardless of the position of the start point selection jumper but voltage or current according to the position of the jumper OFF ON is true for the relay and open collector outputs FO 1 2 LO selected output is f...

Страница 6: ...d can be compared with the actual output value measured with a multimeter Test Gas Verification Insert 4 mm plastic tubing in the test gas inlet at the bottom of the wall plate The plastic tubing should be inserted as far as possible into the inlet Flow test gas at a rate of about 0 5 liter minute Check the display or OUT1 with a multimeter to read the CO2 value when it has stabilized NOTE The sen...

Страница 7: ... speaking the AQS51 61 is maintenance free An internal self adjusting calibration function takes care of normal long term drift associated with the CO2 sensor To ensure the highest accuracy a time interval of max five years is recommended between CO2 calibrations unless some special situations have occurred A zero point calibration can be performed using the push button functions for AQS61 or for ...

Страница 8: ...ker Road Böblinger Straβe 17 manufacturing P O Box 524 North York Ontario D 71101 Schönaich location certified to Minneapolis MN 55408 0524 M2H 3N7 Germany USA Canada http www honeywell com http www honeywell ca http europe hbc honeywell com EN1B 0189GE51 R0102 printed in Germany Subject to change without notice Fig 8 Positioning the temperature sensor the black dot enlargement at right 上海君琼空调科技有限...

Отзывы: