IGSMV
/
IGSMVCN Installation and Setup Guide
3-14
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
18
Supervision
(24 Hours)_
30 Day
24 Hrs
None
Additional
options for CN
only
1 Hr
CN UL Line
Lvl 3
(3 Min)
CN UL Line
Lvl 4
(90 Sec)
CN UL
Line Lvl 5
(75 Sec)
The AlarmNet network must hear at least one
supervisory message from the module during
this supervision period; otherwise, AlarmNet
notifies the central station that a communica-
tion failure has occurred. (If the supervision
period is changed after registration, you must
re-register the module.)
Press the [space] key to scroll through choices.
UL
: A loss of communications is treated as an
Alarm condition.
ULC
: Must be set to" CN UL Line Lvl 3" for
ULC-S304 Active Level 3 or ULC-S559 Active
Fire installations. All other commercial
applications must be set to "24 Hrs".
19
GSM Rollover
Y/N (N)_
[Y], [N]
If enabled, all messages (including AlarmNet
network supervisory messages) are sent over
the GSM network in the event of an Internet
failure.
If disabled, all messages (except AlarmNet
network supervisory messages) are sent
automatically over the GSM network in the
event of an Internet failure.
UL/ULC
: Must be set to "Y" if 24 hours is
selected in Prompt: 23: Supervision. Must be
set to "N" for ULC-S304 Active Level 3 or ULC-
S559 Active Fire installations where CN UL
Line Lvl 3 is selected.
IMPORTANT WARNING:
If set to "Y", AND
Prompt 23: Supervision is set to occur less than
every 24 hours, this can result in data overage
charges on your monthly bill.
20
GSM 24Hr Tst
Y/N (N)_
[Y], [N]
If enabled a message is sent every 24 hrs over
GSM to verify proper operation. If it fails, a
Periodic Comm Test Failure message will be
sent over Ethernet.
UL/ULC:
Must be set to "Y".
21
Old Alarm Time
10 Minutes_
10 Min
15 Min
30 Min
1 Hr
2 Hrs
4 Hrs
8 Hrs
12 Hrs
24 Hrs
Sets how long an undeliverable alarm is retried
for delivery to the central station. If the
message is not validated, it is retried until the
old alarm time is reached or the message is
validated.
Press the [space] key to scroll through choices.
UL/ULC:
Must be set to 10 minutes.
22
IP Flt Time
(60 mins)_
[01-99]
In the event there is a loss of contact with the
network over the Ethernet connection, enter the
time delay (in minutes) before the IGSMV
notifies the central station. IP failure will
always be sent to the central station as Primary
Communication Path Failure.
UL/ULC:
Must be one (01) minute.
Содержание AlarmNet IGSMV
Страница 2: ......
Страница 20: ...IGSMV IGSMVCN Installation and Setup Guide 2 10 ...
Страница 46: ...IGSMV IGSMVCN Installation and Setup Guide 4 4 ...
Страница 54: ...IGSMV IGSMVCN Installation and Setup Guide A 2 ...
Страница 56: ...IGSMV IGSMVCN Installation and Setup Guide B 2 ...
Страница 58: ...IGSMV IGSMVCN Installation and Setup Guide C 2 ...
Страница 60: ...IGSMV IGSMVCN Installation and Setup Guide D 2 ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...