Section 5 – Data Field Descriptions
5-3
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*24
Ignore Expansion Zone Tamper
0
= disable (tamper detection)
1
= enable (no tamper detection)
If disabled, the system monitors the tampers on expansion zones.
NOTE:
Only applicable to certain polling loop sensors with tamper
switches or 5800 Series transmitters.
Must be
0
for UL installations.
*25
Burglary Trigger for Response
Type 8
0
= disable
1
= enable
If enabled, allows triggering of Output 3 (pin 7) of the J7 header to
include zone response type 8 (24-hr. auxiliary).
*26
Intelligent Test Report
0
= disable
1
= enable
If enabled, no test report is sent if any other type of report was sent since
the last test report.
If disabled, test reports are sent at the set intervals, regardless of
whether or not any other report has been sent.
Must be
0
for UL applications.
*27
Test Report Interval
Enter
001-999
for the test report interval in
hours.
Enter
000
for test reporting.
If a test report is desired, enter a test code in
Report Code Programming
in
#93 Menu Mode
. Set first test report time in field *83.
Maximum Test report interval is 0024 for UL installations.
*28
Power-Up in Previous State
0
= disable
1
= enable
If enabled, the system, upon power-up, reverts to its status prior to a
complete power loss.
If disabled, the system always powers up in a disarmed state.
NOTE:
Neither authority level 0 nor 5 can be used to disarm the system
if the control powers up armed.
Must be
1
for UL applications.
*29
Quick Arm (partition-specific)
0
= disable
1
= enable
If enabled, allows arming of the burglary system in AWAY, STAY,
INSTANT, or MAXIMUM mode by using the [#] key instead of the user
code.
NOTES:
When armed, the system reports closing as User 0 if Open/Close reporting
for User #2 (typically a Master level user) was enabled for a given
partition.
If Quick Arm is used, the Installer Code and Authority Level 5 codes
cannot disarm the system.
TouchTone or Rotary Dial
0
= disable
1
= enable
Select the dialing method for the system
If you select TouchTone, make sure the subscriber has requested and is paying for TouchTone service. Note that
whether or not TouchTone dialing for call placement is permitted, communication by the use of DTMF signaling
(ADEMCO High Speed) will still take place. See field 1*33 for TouchTone w/Rotary backup
*30
*31
PABX Access Code
Enter
00-09; B-F (11-15)
This field is used to enter up to four 2-digit numbers representing the
prefix needed to obtain an outside telco line. If not required, enter
nothing and proceed to next field.
*32
Primary Subscriber’s Account
Number (partition-specific)
Enter
00-09; B-F (11-15)
Enter a 3- or 4-digit (depending on report format) primary subscriber
account number. Each number requires a 2-digit entry so as to allow
entry of hexadecimal digits (B-F). If a 3-digit account number is to be
used, enter data only in the first 3 locations, and enter * in the fourth
location.
WWW.DIYALARMFORUM.COM
Содержание Ademco VISTA-50P
Страница 2: ...ii WWW DIYALARMFORUM COM ...
Страница 12: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 2 4 WWW DIYALARMFORUM COM ...
Страница 40: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 3 28 WWW DIYALARMFORUM COM ...
Страница 48: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 4 8 WWW DIYALARMFORUM COM ...
Страница 64: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 5 16 WWW DIYALARMFORUM COM ...
Страница 78: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 6 14 WWW DIYALARMFORUM COM ...
Страница 82: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 7 4 WWW DIYALARMFORUM COM ...
Страница 84: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 8 2 WWW DIYALARMFORUM COM ...
Страница 98: ...VISTA 50P VISTA 50PUL Installation and Setup Guide B 2 WWW DIYALARMFORUM COM ...
Страница 100: ...VISTA 50P VISTA 50PUL Installation and Setup Guide C 2 WWW DIYALARMFORUM COM ...
Страница 102: ...VISTA 50P VISTA 50PUL Installation and Setup Guide D 2 WWW DIYALARMFORUM COM ...
Страница 110: ...WWW DIYALARMFORUM COM ...
Страница 111: ...WWW DIYALARMFORUM COM ...