Honeywell Ademco VISTA-50P Скачать руководство пользователя страница 50

VISTA-50P/VISTA-50PUL Installation and Setup Guide 

5-2 

FIELD 

TITLE and DATA ENTRIES

 

EXPLANATION

 

 

 

*12 

Exit Delay #2 (partition-specific) 

Enter 

03-15

 multiplied by 15 seconds.  

00

 = no delay. 

Exit Delay #2 is used for a secondary door requiring a longer delay than 
those assigned to Exit Delay #1. 

NOTE: 

The delay may not exceed 60 seconds for UL installations.   

 

*13 

Alarm Sounder Duration 
(partition-specific) 

Enter 

01-15

 multiplied by 2 minutes.  

00

 = no timeout. 

Defines the length of time the Bell Output and the keypad’s sounder will 
sound for all audible alarms.  

Must be minimum 16 minutes for UL Commercial Burglary installations.  

 

*14 

Zone 9 Fast/Slow Response 

0

 = slow 350ms 

1

 = fast 10ms 

Select the response time for devices connected to zone 9. 

 

*15 

Keyswitch Assignment 

Enter 

1-8

 partition keyswitch is being used. 

Enter 

0

 if the keyswitch is not used. 

The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer 
available as protection zone).  The fire and panic alarm voltage triggers 
(J7) automatically become ARMING and READY status outputs for the 
Keyswitch LEDs. 

Openings/closing report as user “0” if enabled in field *40. 

 

*16 

Confirmation of Arming Ding 
(partition-specific) 

0

 = disable 

1

 = enable 

If enabled, produces ½-second external alarm sounding (“ding”) at the end 
of exit delay (or after kissoff from the central station, if sending closing 
reports). 

Must be 1 for UL installations. 

 

*17 

AC Loss Keypad Sounding 

0

 = disable 

1

 = enable 

If enabled, sounding at the keypad (rapid beeping) occurs when AC power 
is lost (sounding occurs about 2 minutes after actual AC loss).  

 

*19 

Randomize AC Loss Report 

0

 = disable 

1

 = enable 

If enabled, randomizes AC loss reporting between 10 and 40 min. after an 
actual AC loss.  

If disabled, AC loss reporting about 2 minutes after actual AC loss. 

Selecting this option helps prevent an overload of AC loss messages at the 
central station during a community blackout. 

 

*20 

VIP Module Phone Code 

1-9

 = first digit of access code 

 or 

#

 = second digit of access code (enter # 

+11 for “

”, or # +12 for “#”) 

To disable enter 

00

 for the 1

st

 digit 

If a 4285/4286 Voice Module is being used, enter the 2-digit phone code 
used to access the system. 

Must be disabled for UL installations. 

 

*21 

Prevent Fire Timeout 

0

 = disable (timeout) 

1

 = enable (no timeout) 

If enabled, there is no timeout of the alarm sounder duration for all fire 
zones, regardless of partition, so that fire sounding continues until the 
system is reset. 

If disabled, (timeout) the normal burglary sounder duration (field 

13) 

applies to fire alarms. 

 

*22 

Keypad Panic Enables (partition-
specific) 

0

 = disable 

1

 = enable 

If enabled, the keypad panics (zones 995, 996, and 999) may be used in 
this partition.  There are 3 entries in this field, one for each panic. 

 

*23 

Multiple Alarms (partition-
specific) 

0

 = disable 

1

 = enable 

If enabled, allows more than one alarm sounding for a given zone during 
an armed period.  

NOTE:

 that multiple alarm soundings will not occur more frequently 

than allowed by the programmed alarm sounder duration. This has no 
impact on the number of communication messages transmitted.  

Must be 1 for UL installations. 

 

WWW.DIYALARMFORUM.COM

Содержание Ademco VISTA-50P

Страница 1: ...N5944 6V2 5 04 Rev A 0 0 2 2 9 9 6 67 7 6 6 5 5 6 6 9 9 6 67 7 3 3 9 9 6 67 7 3 38 8 RPPHUFLDO XUJODU 3DUWLWLRQHG 6HFXULW 6 VWHP LWK 6FKHGXOLQJ QVWDOODWLRQ DQG 6HWXS XLGH WWW DIYALARMFORUM COM ...

Страница 2: ...ii WWW DIYALARMFORUM COM ...

Страница 3: ...17 Installing the Ground Start Module 3 18 Installing a Remote Keyswitch 3 18 Remote Keypad Sounder 3 19 Long Range Radio Connected to the J7 Triggers 3 20 Installing a 4100SM 3 20 Installing the 4285 4286 VIP Module 3 20 Installing the Audio Alarm Verification Module 3 22 Connecting the Transformer 3 24 Panel Earth Ground Connections 3 25 Determining the Control s Power Supply Load 3 25 Determini...

Страница 4: ...ser 9 4 Deleting a Master Manager or Operator Code 9 4 Exiting the User Edit Mode 9 4 SECTION 10 Testing the System 10 1 Battery Test 10 1 Dialer Test 10 1 Burglary Walk Test Code 5 TEST 10 1 Armed Burglary System Test 10 1 Testing Wireless Transmitters 10 2 Trouble Conditions 10 3 To the Installer 10 3 APPENDIX A Regulatory Agency Statements A 1 UL Installation Requirements A 1 UL609 Grade A Loca...

Страница 5: ...0 Figure 3 15 Wiring Latching Glassbreaks to Zone 8 3 10 Figure 3 16 Polling Loop Connections to the VISTA 50P VISTA 50PUL 3 12 Figure 3 17 Polling Loop Connections Using One 4297 Extender Module 3 12 Figure 3 18 Polling Loop Connections Using Multiple Extender Modules 3 13 Figure 3 19 Installing the 5881ENHC with Tamper Protection 3 14 Figure 3 20 5881 RF Receiver cover removed 3 15 Figure 3 21 4...

Страница 6: ...ymbol indicates a critical note that could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol also denotes warnings about physical harm to the user ZONE PROG 1 YES 0 NO 0 Many system options are programmed in an interactive mode by responding to alpha keypad display prompts These prompts are shown in a single line box 00 ...

Страница 7: ...cial Burglary applications Provides three keypad panic keys 1 A B and 3 C Peripherals Devices Supports up to 16 addressable devices keypads RF receivers relay modules etc Provides 16 outputs using 4204 and X 10 devices The system can activate outputs in response to system events alarm condition at a specific time of day and manually using the 70 Relay Command Mode Supports the 4285 4286 VIP Module...

Страница 8: ...update your 685 receiver contact your distributor Provides an Audio Alarm Verification AAV option that permits voice dialog between an operator at the central station and a person at the premises An AAV unit such as ADEMCO UVS is required Downloading Supports upload and download capability of program and user information Event Log Provides an event log history log that can store up to 224 events C...

Страница 9: ...ble GOTO is enabled for each partition he she wants to log on to from another A partition can be selected as a common lobby partition and other partitions can affect this partition by causing arming disarming of this partition to be automated see Common Lobby Logic later in this section Setting Up a Partitioned System The basic steps to setting up a partitioned system are described below If you ne...

Страница 10: ...ct the Common Lobby but not arm it Office 2 is set up to affect and arm the Common Lobby NOTE In the tables below the notations in parentheses indicate the current status of the other partition when the user takes action Sequence 1 Office 1 Office 2 Lobby Action User 1 Disarms Armed Disarms User 2 Disarmed Disarms No Change User 1 Arms Disarmed No change User 2 Armed Arms Arms Sequence 2 Office 1 ...

Страница 11: ...R N N A 7 B Possible status indications include A Armed Away S Armed Stay M Armed Maximum I Armed Instant R Ready N Not Ready B Bypassed Ready Alarm Trouble To obtain more information regarding a particular partition enter Partition No e g 4 This allows viewing only of that partition In order to affect that partition the user must use a code that has access to that partition Also in order for a us...

Страница 12: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 2 4 WWW DIYALARMFORUM COM ...

Страница 13: ...ld securely by its snap tabs Use a Part Number K4445 Lock supplied CABINET DOOR BOTTOM LOCKED UNLOCKED cab_lock_snap 001 V0 ADEMCO ADEMCO PUSH SNAP TAB SNAP TAB PUSH ON LOCK UNTIL IT IS SEATED SECURELY STEP 2 STEP 1 CHECK POSITION Figure 3 1 Installing the Lock Grade A Mercantile Premises Listing Guidelines The panel door must be supervised Mount the clip on tamper switch supplied to the cabinet s...

Страница 14: ...nsor also must be wired to a hardwire zone Installing the Control s Circuit Board To install the circuit board in the cabinet perform the following steps Step Action 1 Hang the three mounting clips on the raised cabinet tabs Refer to Figure 3 3 Detail B Make sure the clip orientation is exactly as shown in the diagram to avoid damage This will also avoid problems with insertion and removal of the ...

Страница 15: ...d Connections to Control Panel Addressing the Keypads The keypads will not operate until they are physically addressed and enabled in the system s Device Programming in the 93 Menu Mode Set each keypad for an individual address 00 30 according to the keypad s instructions Set an alpha keypad for address 00 and other keypads for higher addresses Each keypad must be set for a different address Do no...

Страница 16: ...utput must not exceed 1 7A A battery must be installed as the battery supplies current from the combined auxiliary power polling loop and alarm output in excess of 750mA Non UL Installations For non UL installations the total current drawn from this output can be up to 1 7 amps A battery must be installed as the battery supplies current in excess of 750mA Up to two 719 sirens can be used wired in ...

Страница 17: ... alarm by night The minimum load on the alarm output must exceed 5mA at 12V for proper supervision operation Using a Siren Driver To install a siren driver perform the following steps Step Action 1 Mount the siren driver in the panel s cabinet 2 Wire the siren driver to the control and to the speaker s See the driver s instructions 3 Cut the blue jumper on the upper left hand corner of the panel s...

Страница 18: ...mmunication failure if power is lost Reporting Formats The system supports the following formats ADEMCO Low Speed 3 1 4 1 4 2 Sescoa Radionics 3 1 4 1 4 2 ADEMCO 4 2 Express ADEMCO High Speed ADEMCO Contact ID TERMINALS ON CONTROL EARTH GROUND INCOMING TELCO LINE Handset TIP RING RJ31X JACK PLUG DIRECT CONNECT CORD TIP RING GROUND PREMISES PHONES BROWN TIP GREY RING GREEN TIP RED RING 26 27 28 29 ...

Страница 19: ...Sensor 2451TH Ionization direct wire System Sensor 1400 Ionization w B401B base System Sensor 1451 Photoelectric duct detect DH400 base System Sensor 2451 Photoelectric duct detect DH400 base System Sensor 2451 Ionization duct detector DH400 base System Sensor 1451DH Ionization direct wire System Sensor 1100 Ionization w B110LP base System Sensor 1151 Photoelectric direct wire System Sensor 2100 P...

Страница 20: ...t the EOLR across the loop wires at the last detector _ _ _ _ _ HEAT DETECTOR 4 WIRE SMOKE DETECTORS V128BP 002 V0 NO CONNECTION C NC NO RESET RELAY 1 2 3 OR 4 4204 RELAY MODULE NOTES PROGRAM THE RELAY TO TRANSFER ON FIRE ZONE RESET ACTIVATION CODE 54 SEE 4204 RELAY MODULE SECTION FOR DETAILS SECOND CODE AND OFF ENTERED AT CONSOLE MOMENTARILY INTERRUPTS DETECTOR POWER SHOWN POWERED RELAY OPENS WHE...

Страница 21: ... MODULE MUST BE IN B POSITION FOUR WIRE DETECTOR CIRCUIT CONTROL PANEL 7 4 6 Figure 3 12 Wiring a 333PRM to the Control EOL POWER SUPERVISION RELAY MODULE A77 761B 4 WIRE SMOKE DETECTORS 2000 OHM EOLR TO FIRE ZONE TERMINALS HEAT DETECTOR SHOWN POWERED RELAY OPENS WHEN POWER IS LOST 333PRM 002 V0 333 PRM 7 6 5 4 3 2 1 8 JUMPER NC C NO P1 JUMPER P1 ON 333 MODULE MUST BE IN B POSITION FOUR WIRE DETEC...

Страница 22: ...ance Less than 1 1k ohms see note below Alarm Current 2mA 10mA Reset Time Less than 6 seconds NOTES You can use detectors that exceed 1 1k ohms in alarm provided they maintain a voltage drop of less than 3 8 volts in alarm The ASC SS1 detector has been tested and found to be compatible with these ratings 21 22 GLASSBREAK DETECTOR ZONE 8 LATCHING TYPE GLASS BREAK DETECTOR LOOP 2000 OHMS EOLR Figure...

Страница 23: ... a UL Listed supplementary power supply The 7500 and 9500 detectors are not UL Listed For new polling loop installations always use twisted pair wiring In many cases existing non twisted pair wiring may be used but it is more susceptible to interference from other sources and may be problematic in installations with long wire runs or in high noise environments Always locate polling loop wiring at ...

Страница 24: ... a burglary zone the will go into alarm A trouble on zone 97 prevents a partition from being armed unless all polling loop zones on that partition are bypassed Using the 4297 Polling Loop Extender The 4297 Polling Loop Extender may be used to provide additional polling loop current to extend the polling loop wire run length and or to provide individual electrically isolated polling loops Refer to ...

Страница 25: ...s applies as well to the 5882 Receivers Both receivers use the same transmitters RF System Operation and Supervision The 5800 RF system operation has the following characteristics The receiver responds to a frequency of 345MHz The receiver has a nominal range of 200 feet Supervised transmitters send a supervisory signal every 70 90 minutes Zones 88 and 90 are used to supervise the RF reception of ...

Страница 26: ...er as this address must be enabled in the system s Device Programming in the 93 Menu Mode 5881ENHC 001 V0 SCREW Figure 3 19 Installing the 5881ENHC with Tamper Protection To install the 5881 RF receiver perform the following steps Step Action 1 Mount the receiver following the advisories stated previously 2 Set the DIP switches in the receiver for the address 01 07 See Figure 3 20 Make sure the ad...

Страница 27: ... control s Device Programming in the 93 Menu Mode as a keypad and then assigned to a partition To install the 5800TM perform the following steps Step Action 1 Mount the unit using its accompanying mounting bracket near the RF receiver The 5800TM must not be installed within the control cabinet It must be between one and two feet from the receiver s antennas 2 Set the module for the appropriate add...

Страница 28: ...r programmed for Fire it reports in Contact ID as a Fire Trouble 373 not Loss of Supervision 381 to the central station Transmitter Battery Life Batteries in the wireless transmitters may last from 4 to 7 years depending on the environment usage and the specific wireless device being used Factors such as humidity high or low temperatures as well as large swings in temperature may all reduce the ac...

Страница 29: ...ngth 22 125 feet 20 200 feet 18 300 feet 16 500 feet 3 SWITCH 4 2 0 4 A D D R E S S S E T T I N G S POSITION means OFF 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 ON ON ON ON ON ON ON ON 3 ON ON ON ON ON ON ON ON 4 ON ON ON ON ON ON ON ON 5 ON ON ON ON ON ON ON ON ON 1 2 3 4 5 13 14 15 16 C NC NO OFF ON DIP SWITCH FOR SETTING DEVICE ADDRESS AND ENABLING DISABLING TAMPER COVER TAMPER REED SWITCH TB1 42...

Страница 30: ...OUT 4 WHITE GROUND J7 CONNECTOR N U IF USED 1 OUT 1 IS NO LONGER USABLE FOR SMOKE DETECTOR RESET SEE FIELD 1 46 2 OUT 2 3 4 CAN STILL BE USED TO PROVIDE ALARM STATUS INDICATIONS OR TO OPERATE A KEYSWITCH SEE FIELD 15 3 THE 675 IS NOT UL LISTED BROWN GROUND START TRIGGER BLUE GREEN BLACK VIOLET TO AUX POWER TERM 7 TO AUX POWER TERM 6 50mA CURRENT DRAW 675 GROUND START MODULE CUT ORANGE JUMPER TO TE...

Страница 31: ...h Figure 3 23 Remote Keyswitch Wiring Remote Keypad Sounder An optional Amseco PAL 328N Piezo Sounder can be used to duplicate the sounds produced by the keypad s built in sounder The panel will remote all sounds e g alarm trouble chime entry exit etc produced by the keypad s built in sounder except for the short beeps associated with keypad key depression One application of this feature might be ...

Страница 32: ... 4100SM Interface Module The 4100SM Module is supplied with a 10 foot RS232 cable A longer cable can be used if the VISTA 50P VISTA 50PUL is separated from the serial printer by more than 10 feet but the total cable length should be less than 50 feet 1 2 3 4 5 6 7 8 9 NU J8 CONNECTOR VIOLET GREY YELLOW RED GREEN BROWN BLUE BLACK I N 2 I N 3 G R O U N D O U T 5 O U T 6 G R O U N D G R O U N D P R I...

Страница 33: ...of the cabinet or adjacent to it If you mount the VIP Module inside the control cabinet attach it to the cabinet s interior surface with 2 faced adhesive tape You may leave the module s cover off if it is mounted within the cabinet If you mount the module outside the cabinet use the screw holes at the rear to mount horizontally or vertically 2 faced adhesive tape may be used if preferred 2 Affix t...

Страница 34: ...ontact ID is the only reporting format that will send a Listen in to Follow If you are also using a 4285 4286 VIP Module be sure to follow Figure 3 29 when making connections The UVS consists of a UVCM and at least one UVST The UVCM board has a DC power jack and a 34 position terminal block for making connections to a DC power source UVSTs telephone lines music source or to the 4286 VIP Module and...

Страница 35: ...CHINE AND PHONE S ANSWERING MACHINE P3 UVST VOLUME CONTROL DIAL TIP RING TIP RING 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NOTE 1 CONNECT TO PROPER EARTH GROUND NOTE 2 POWER MAY ALSO BE SUPPLIED BY A LISTED CLASS 2 POWER SUPPLY RATED 12VDC MIN 600mA CONNECTED TO THE UVCM 12VDC IN AND GND TERMINALS NOTE 3 SOME CONTROL PANELS USE BUILT IN TRIGGER AND SOME USE 4204 RELAY MODULE REFER TO AAV SECTION OF CONTROL...

Страница 36: ...unction Failure to observe the auxiliary power current rating will result in a battery that does not charge properly or possibly a tripped circuit breaker To connect the transformer to the control perform the following steps Step Action 1 Connect all installed devices to the control 2 Wire the 1361 Transformer 1361CN in Canada to the panel before connecting the battery as shown in Figure 3 28 or w...

Страница 37: ...requires the earth ground connection for its lightning transient protection devices Determining the Control s Power Supply Load Use the tables that follow to calculate the total current for the Auxiliary Power the Alarm Output and the Polling Loop In each table multiply each device s standby and or alarm current by the number of units used 1 In Table 1 enter devices used on the polling loop Calcul...

Страница 38: ...oop outputs combined must be limited to 270mA when 14AH batteries are used and to 390mA when 17 2AH batteries are used DO NOT use Gates batteries sealed lead acid type These batteries require a different charging voltage than is supplied by the panel UL Household Fire or Combination Household Fire Burglary installations require the use of a backup battery that is capable of providing 24 hours of s...

Страница 39: ...sa NP7 12 12AH Yuasa NP12 12 Fits in large mercantile cabinet only 14AH Yuasa NP7 12 Connect two in parallel 17 2AH Yuasa NPG18 12 Fits in large mercantile cabinet only 7 Connect the battery referring to Figure 3 28 The standby battery is automatically tested for 10 minutes every 4 hours beginning 4 hours after exiting Programming mode In addition entry into the Test mode initiates a battery test ...

Страница 40: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 3 28 WWW DIYALARMFORUM COM ...

Страница 41: ...rmation in a field press the field number 03 To read the information in a field press the field number 03 When the entries for a field are completed the keypad beeps three times and advances to the next field Summary of Data Field Programming Commands 91 Select partition for programming partition specific fields 92 Display the software revision level of the control panel 93 Enter Menu mode program...

Страница 42: ...lds To program partition specific data fields once in Program Mode do the following Step Action 1 Enter Program Mode Installer Code 8 0 0 2 Press 91 which will prompt you for the partition number desired 3 Enter a partition specific field number e g 09 to begin programming When the first field s entry is completed the next partition specific field is automatically displayed When all partition spec...

Страница 43: ...lay Descriptors DEVICE PROG 1 YES 0 NO 0 For defining the following device characteristics for addressable devices including keypads RF receivers 5881 output relay modules 4204 and 4285 4286 VIP Module Device Address Device Type Keypad Options including Partition assignment RF House ID RELAY PROG 1 YES 0 NO 0 For defining output device functions RLY VOICE DESCR 1 YES 0 NO 0 For entering voice desc...

Страница 44: ...eport code programming Zone Index The zones are designated as follows ZONE RANGE ZONE FUNCTION ACTUAL ZONE 01 86 Protection zones As indicated 87 88 89 90 91 97 98 System Supervisory Zones 87 VIP Module Supervision 88 2nd Wireless Receiver not receiving signals 89 2nd Wireless Receiver not talking to control 90 1st Wireless Receiver not receiving signals 91 1st Wireless Receiver not talking to con...

Страница 45: ... each partition a polling loop supervision zone and four RF supervisory zones two for each RF receiver installed Zone types are defined below Type 00 Zone Not Used Program with this zone type if the zone is not used Type 01 Entry Exit 1 Burglary Provides entry delay whenever the zone is faulted and the system is armed in the AWAY or STAY mode When the panel is armed in the INSTANT or MAXIMUM mode ...

Страница 46: ...f this type is always active and cannot be bypassed Type 10 Interior with Delay Provides entry and exit delays using the programmed entry and exit delay times when armed in the AWAY mode Provides only exit delay when armed in the MAXIMUM mode no entry delay Interior with Delay zones are automatically bypassed when the panel is armed in the STAY or INSTANT mode Delay begins whenever sensors in this...

Страница 47: ...he second loop of two zone polling loop devices e g 4190WH 4278 Programming for 4100SM 1 70 Event Log Types 1 enable 0 disable 1 71 12 24 Hour Time Stamp 0 12 hr 1 24 hr 1 72 Printer On line 0 disable 1 enable 1 73 Printer Baud Rate 0 1200 1 300 Programming for Access Control The VISTA 50P VISTA 50PUL can be used to trigger an access point i e door strike for 2 seconds by entering User Code 0 To p...

Страница 48: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 4 8 WWW DIYALARMFORUM COM ...

Страница 49: ...response types Refer to the Programming Guide for details 03 Response Types for Zones 09 16 Skip this field Use 93 Menu Mode Zone Programming to program the response types Refer to the Programming Guide for details 04 Response Types for Zones 17 24 Skip this field Use 93 Menu Mode Zone Programming to program the response types Refer to the Programming Guide for details 05 Response Types for Zones ...

Страница 50: ...unding at the keypad rapid beeping occurs when AC power is lost sounding occurs about 2 minutes after actual AC loss 19 Randomize AC Loss Report 0 disable 1 enable If enabled randomizes AC loss reporting between 10 and 40 min after an actual AC loss If disabled AC loss reporting about 2 minutes after actual AC loss Selecting this option helps prevent an overload of AC loss messages at the central ...

Страница 51: ...thority level 0 nor 5 can be used to disarm the system if the control powers up armed Must be 1 for UL applications 29 Quick Arm partition specific 0 disable 1 enable If enabled allows arming of the burglary system in AWAY STAY INSTANT or MAXIMUM mode by using the key instead of the user code NOTES When armed the system reports closing as User 0 if Open Close reporting for User 2 typically a Maste...

Страница 52: ... enable Enabling a function means that you are able to perform that function via the Compass Downloading software Functions are as follows Dialer Shutdown System Shutdown Not Used Remote Bypass Remote Disarm Remote Arm Upload Program Download Program For UL installations all entries must be 0 38 Prevent Zone XX Bypass partition specific Enter a zone number 01 86 Enter 00 if all zones except fire z...

Страница 53: ...lephone number 47 Secondary Format 0 Low Speed 1 Contact ID 2 ADEMCO High Speed 3 ADEMCO Express Enter the reporting format for the secondary telephone number 48 Low Speed Format Secondary 0 ADEMCO Low Speed 1 Sescoa Radionics Enter the low speed format for the secondary telephone number 49 Checksum Verification Enter 2 digits one for the primary and one for the secondary 0 disable 1 enable If ena...

Страница 54: ...u Mode Zone Programming to program the response types Refer to the Programming Guide for details 61 Alarm Code for Zones 25 32 Skip this field Use 93 Menu Mode Zone Programming to program the response types Refer to the Programming Guide for details 62 ID Digit for Zones 25 32 Skip this field Use 93 Menu Mode Zone Programming to program the response types Refer to the Programming Guide for details...

Страница 55: ...Code for Zones 89 99 Skip this field Use 93 Menu Mode Zone Programming to program the response types Refer to the Programming Guide for details 77 ID Digit for Zones 89 99 Skip this field Use 93 Menu Mode Zone Programming to program the response types Refer to the Programming Guide for details 78 Supervisory and Restore Codes for Zones 81 99 Enter 00 15 This field has five two digit entries as fol...

Страница 56: ...store reports are sent after an alarm Must be 2 for UL installations 90 Secondary Subscriber Account Number partition specific Enter 00 09 B F 11 15 Enter a 3 or 4 digit depending on report format primary subscriber account number Each number requires a 2 digit entry so as to allow entry of hexadecimal digits B F If a 3 digit account number is to be used enter data only in the first 3 locations an...

Страница 57: ...le 1 enable Exit Error Logic functions as follows the system at the end of the exit delay if a door is left open or an interior zone is faulted starts the entry delay period and sounds the bell s siren s and keypad sounders for the duration of entry delay This gives the user time to re enter the premises and disarm the system before exit error occurs If the user does not re enter the premises and ...

Страница 58: ... an interior follower zone be sure to enter the entry exit zone as the first zone of the pair This ensures that the entry delay time is started before the follower zone is processed If a relay is programmed to activate on a fault of one of the zones the relay activates without the other zone being faulted If a relay is programmed to activate on either an alarm or trouble both zones must trip befor...

Страница 59: ...communicator is not successful in dialing using TouchTone DTMF on first attempt 1 34 Communicator Split Reporting 0 Split Reporting disabled 1 Alarm Alarm Restore and Cancel reports to primary all others to secondary 2 Open Close and Test reports to secondary all other reports to primary Select the type of split reporting for system communication NOTE See 51 for split dual reporting combinations 1...

Страница 60: ...s removed once a valid key sequence is received from a wired keypad 1 45 Exit Delay Sounding partition specific 0 disable 1 enable If enabled the system produces slow beeping from the keypads during exit delay and reverts to rapid beeping during the last 10 seconds of the exit delay NOTE The duration of the beeping is the programmed value of field 10 regardless of which entry exit zone is used to ...

Страница 61: ...Event Log Printer On Line Mode 0 disable 1 enable If enabled the system prints the events as they occur If disabled the system prints the log only upon request 1 73 Printer Baud Rate 0 1200 1 300 Select the baud rate for the serial printer 1 74 Relay Timeout XXX Minutes Enter 000 127 times 2 minutes 000 254 This is used for 80 Menu Mode Time Driven event relay command numbers 04 09 and Output Prog...

Страница 62: ...by Exception partition specific 0 disable 1 enable If enabled Open Close reports are sent only if the openings closings occur outside the arm and disarm windows NOTES Open reports are also suppressed during the closing window in order to prevent false alarms if the user arms the system then re enters the premises for example to retrieve a forgotten item Openings and closings are still recorded in ...

Страница 63: ...e accessed from another partition s keypad using the GOTO command 2 19 Use Partition Descriptor 0 disable 1 enable If enabled the normal keypad display will include a partition number and four digit descriptor 2 20 Enable J7 Triggers for Partition partition specific 0 disable 1 enable If enabled the J7 triggers function for this partition 2 21 Supervision Pulses for LRR 0 disable 1 enable There ar...

Страница 64: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 5 16 WWW DIYALARMFORUM COM ...

Страница 65: ...r to the arming in partition specific program field 2 06 During this period the keypad beeps every 15 seconds and displays AUTO ARM ALERT During the last 60 seconds the keypads beep every 5 seconds The panel arms at the conclusion of the Auto Arm Warning period Extend Closing Window A user can manually delay the arm closing time window by 1 or 2 hours This is done by entering a keypad command User...

Страница 66: ...8 00 PM The system also provides up to 20 programmable timers available to the end user for the purpose of activating output devices at preset times and days Time Window Definitions Scheduled events are based on time windows periods of time during which an event may take place The system supports up to 20 time windows each defined by a Start time and a Stop time The windows are shared by all 8 par...

Страница 67: ...ccurs outside the assigned time window The system keeps a record of all openings closings in its event log If a disarming occurs during a closing window for example a person who arms the system forgets something and has to re enter the Opening report although outside of the opening window will not be sent as long as that disarming occurs within the closing window This option is programmed in parti...

Страница 68: ...on and Setup Guide In order to use 80 Scheduling Menu Mode use the worksheets to do the following 1 Define time windows up to 20 2 Define the daily open close schedules one schedule per day per partition 3 Define the holidays to be used by the system up to 16 4 Define limitation of access times up to 8 schedules 5 Define the Time Driven events up to 20 NOTE Temporary schedules are programmed using...

Страница 69: ... to 1 AM Time Window Number Start Time HH MM Stop Time HH MM 1 2 3 20 A time window must have a start and a stop time Time Windows Programming Enter Scheduling Mode by entering Installer Code 80 The keypad displays the Time Window Programming prompt PROMPT EXPLANATION Time Window 1 YES 0 NO 0 Enter 1 at this main menu prompt to program time windows Time Window 01 20 00 Quit 01 Enter the 2 digit ti...

Страница 70: ...is desired for a particular day As the number is keyed in the actual time that has been stored for that window number is displayed as a programming aid Press to accept the entry Mon P1 CL WIND 00 00 00 00 00 Enter the time window number for the displayed day s closing schedule As the number is keyed in the actual time that has been stored for the window number is displayed Press the key to accept ...

Страница 71: ...partitions on or off or use keys 1 8 to toggle the letter x under the partition to which this holiday will apply Press the key when all desired partitions have been assigned The Holiday Number prompt is displayed again Repeat the procedure for each holiday to be programmed Quit 1 YES 0 NO 0 Enter 0 at the Quit prompt to return to the main menu choices and continue programming Enter 1 to quit Sched...

Страница 72: ... warning field 2 06 applies when using Time Driven events to auto arm Temporary schedules do not override an auto arming or auto disarming programmed in Time Driven events The auto arming window cannot be extended using the Installer Code 82 Mode Bypass Commands Action Code Action Action Specifier 30 Auto bypass Zone list Zone list 31 Auto unbypass Zone list Zone list Open Close Windows Action Cod...

Страница 73: ...oup Close for 2 seconds 09 Relay Group Close XX minutes 10 Relay Group Close YY seconds Actions 06 10 If you selected actions 06 10 the prompt at the right appears Enter the relay group number Press to accept entry The Time Window prompt appears 01 RELAY GRP 00 20 Arm STAY 21 Arm AWAY 22 Disarm 23 Force Arm STAY 24 Force Arm AWAY 40 Enable Open Window by Part 41 Enable Close Window by Part Actions...

Страница 74: ...ain menu choices and continue programming Enter 1 to quit Scheduling Menu Mode Limitation of Access Schedules Limitation of Access is a means by which a user s access code is limited to working during a certain period of time The system provides 8 Access Schedules each of which consists of two time windows for each day of the week and two time windows for holidays typically one for an opening time...

Страница 75: ...indow is displayed Press to continue Hol A1 Window 2 00 00 00 00 00 Enter the second time window number for holidays for this access schedule As the number is keyed in the actual time that has been stored for the window is displayed Press to continue Quit 1 YES 0 NO 0 Enter 0 at the Quit prompt to return to the main menu choices and continue programming Enter 1 to quit Scheduling Menu Mode Tempora...

Страница 76: ...0AM Repeat the procedure described above for all days of the week When all the windows for all the days have been completed the system prompts for which days of the schedule are to be activated Days MTWTFSS Hit 0 7 x x This is the prompt that actually activates the temporary schedule To select the days to be activated enter 1 7 Monday 1 An X appears under that day indicating the temporary schedule...

Страница 77: ... The cursor positioned on the tens of hours digit of the OFF time Enter the desired hour Press to move to the minutes field The minutes are entered in the same manner The AM PM indication is toggled by hitting any key in the 0 9 range while the cursor is under the AM PM position Press to continue 06 DAYS MTWTFSS HIT 0 7 x x To select the days to be activated enter 1 7 Monday 1 An x appears under t...

Страница 78: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 6 14 WWW DIYALARMFORUM COM ...

Страница 79: ...control against compromise while it is being accessed from a remote location 1 Security code handshake The subscriber s account number as well as an 8 digit ID number known only to the office must be matched between the control and computer 2 Hang up and callback The control panel hangs up and calls the computer back at the pre programmed number only if the security codes match 3 Data encryption A...

Страница 80: ... line with the computer Alarms and Trouble responses and reports are disabled during actual uploading or downloading sessions If you are on line but not actively uploading or downloading all alarms report immediately All other reports are delayed until you complete the session The keypads remain active when on line with a control but are inactive during actual uploading or downloading sessions To ...

Страница 81: ... of the IN CASE OF DIFFICULTY section of the 4100SM Instructions use the violet wire instead Connector J8 on the main PC board see the Summary of Connections diagram on the inside back cover of this manual is intended to be interfaced to either a local serial printer see SECTION 3 Installing the Control or a computer Make connections to a computer as shown below Note that the violet wire connectio...

Страница 82: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 7 4 WWW DIYALARMFORUM COM ...

Страница 83: ...y of the week is automatically calculated based on the date entered Time and date entries are made by simply entering the appropriate hour minute month day and year Press to move the cursor to the right of the display to the next position Press to move the cursor to the left of the display to the previous position 2 Enter the correct hour Then press to move to the minutes field 3 Enter the correct...

Страница 84: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 8 2 WWW DIYALARMFORUM COM ...

Страница 85: ...Close reports for any user Is the only code that can be used to enter program mode The Installer Code can be prevented from re entering the Program Mode by exiting using 98 Must program at least one Master Code during initial installation Master Codes are codes intended for use by the primary user s of the system Level 1 Master Codes Can perform all normal system functions Can be used to assign up...

Страница 86: ...r adds a new user the new user s Open Close reporting is the same as that of the Master or Manager who is adding the user If Open Close reports are required to be selectable by the Master or Manager the Installer should assign two Master or Manager user codes one with Open Close reporting enabled and one without Note that Open Close reporting of Quick Arm is enabled if User 02 is enabled for Open ...

Страница 87: ...he button transmitter as AWAY STAY or DISARM The system then assigns all buttons of the transmitter to this user number Multi Access 0 NO 1 YES Press 0 NO if the user is to have access to this partition only Press 1 YES if the user is to have access to more than one partition If NO the program exits this mode If YES the keypad prompts for the Global Arm option for this user Global Arm 0 NO 1 YES P...

Страница 88: ...ator Code paragraph Deleting a Master Manager or Operator Code Enter your code 8 new user no 02 75 your code again Or Master or Manager Code but the code must be a higher level of authority than the code being changed e g a Manager Code can add an Operator level Code but cannot add a Master or another Manager Code PROMPT EXPLANATION OK TO DELETE 03 0 NO 1 YES The system prompts to confirm that you...

Страница 89: ...ed the system activates the alarm output for 3 seconds The system sends a Start of Walk Test message to the central station The keypad displays Burg Walk Test in Progress and sounds a single beep every 15 seconds while the test remains active Open and close each protected door and window in turn Each action should produce 3 beeps from the keypad Walk in front of any motion detectors Listen for thr...

Страница 90: ...to transmit As the system receives a signal from each of the transmitters the zone number of that transmitter disappears from the display 3 Enter Installer Code OFF to exit the Sniffer Mode Go No Go Test Mode Checking the transmitters in this mode assists in determining good mounting locations and verifies that the RF transmission has sufficient signal amplitude margin for the installed system All...

Страница 91: ...ists in the wireless transmitter displayed Pressing any key silences the audible warning sound SYSTEM LO BAT This indicates that a low battery condition exists with the system s backup battery RCVR SETUP ERROR This indicates that the system has more wireless zones programmed than the wireless receiver can support If this is not corrected none of the zones in the system will be protected If additio...

Страница 92: ...y documentation that came with the product Note your customer number and or company name Having this information handy will make it easier for us to serve you quickly and effectively You may contact Technical Support via Toll Free Fax Please include your return fax number You will receive a reply within 24 hours You may also contact Technical Support via modem to ATLIS BBS Tech Support s Electroni...

Страница 93: ...ay not be used If 4190WH RPMs are used set field 24 to 0 to enable tamper detection Attach a door tamper switch supplied to the VISTA 50P VISTA 50PUL cabinet backbox For safe and vault installations a shock sensor not supplied must also be attached to the backbox Also see SECTION 3 Installing the Control Wire an AB12 Grade A Bell Box to the bell output Bell wires must be run in conduit Program the...

Страница 94: ... Marshal CSFM and UL Residential Fire Battery Backup Requirements The California State Fire Marshal and UL have regulations that require all residential fire alarm control panels to have backup battery with sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition followed by at least 4 minutes in the intended fire alarm signaling c...

Страница 95: ...s On the front cover of this equipment is a label that contains among other information the FCC registration number and ringer equivalence number REN for this equipment If requested this information must be provided to the telephone company This equipment uses the following jacks An RJ31X is used to connect this equipment to the telephone network The REN is used to determine the quantity of device...

Страница 96: ...valence Numbers of all the devices does not exceed 5 AVIS L étiquette d Industrie Canada identifie le matériel homologué Cette étiquette certifie que le matériel est conforme aux normes de protection d exploitation et de sécurité des réseaux de télécommunications comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal Le Ministère n assure toutefois pa...

Страница 97: ...Sniffer Mode Code 2 Installer Only Transmitter ID Test Code 3 Installer Only Go No Go Test Code 5 Test Key Partition GOTO User Code Partition Number 0 8 GOTO Home Partition User Code 0 Panics 1 or A Key Zone 995 or B Key Zone 999 3 or C Key Zone 996 View Downloaded Messages Press 0 for 5 Seconds Display All Zone Descriptors Press for 5 Seconds Additional Commands Display User Self Help Hold Any Ke...

Страница 98: ...VISTA 50P VISTA 50PUL Installation and Setup Guide B 2 WWW DIYALARMFORUM COM ...

Страница 99: ... against reverse battery connections and on alarm sounder output to protect against wiring faults shorts A solid state circuit breaker is used on auxiliary power output to protect against wiring faults shorts Digital Communicator Formats Supported ADEMCO High Speed ADEMCO 4 2 Express ADEMCO Low Speed ADEMCO Contact ID Sescoa and Radionics Low Speed Line Seize Double Pole Ringer Equivalence 0 7B FC...

Страница 100: ...VISTA 50P VISTA 50PUL Installation and Setup Guide C 2 WWW DIYALARMFORUM COM ...

Страница 101: ...80 Trouble global 381 Loss of Supervision RF 382 Loss of RPM Supervision 383 RPM Sensor Tamper 384 RF Transmitter Low Battery 401 O C by User Code Definition 403 Power Up Armed Auto Arm 406 Cancel by User 407 Remote Arm Disarm Download 408 Quick Arm 409 Keyswitch O C 411 Callback Requested 441 Armed STAY 451 Early Open Close 452 Late Open Close 453 Fail to Open 454 Fail to Close 455 Auto Arm Fail ...

Страница 102: ...VISTA 50P VISTA 50PUL Installation and Setup Guide D 2 WWW DIYALARMFORUM COM ...

Страница 103: ...ESS C 1 ADEMCO CONTACT ID C 1 ADEMCO HIGH SPEED C 1 ADEMCO Low Speed 3 6 ADEMCO LOW SPEED C 1 Affects Lobby 2 2 5 9 Agency Statements A 1 Alarm Code for Zones 01 08 5 6 Alarm Code for Zones 09 16 5 6 Alarm Code for Zones 17 24 5 6 Alarm Code for Zones 25 32 5 6 Alarm Code for Zones 33 40 5 6 Alarm Code for Zones 41 48 5 6 Alarm Code for Zones 49 56 5 7 Alarm Code for Zones 65 72 5 11 Alarm Code fo...

Страница 104: ...pe 07 4 7 Direct Wire Downloading 7 3 Disable Download Callback 5 12 Disarm Delay 6 1 Disarm Type 22 4 6 Download Command Enables 5 4 Download ID Number 5 4 Download Phone Number 5 4 Downloading 7 1 Downloading Access Security 7 1 Downloading Requirements 7 1 Dual Reporting 5 5 Duress Codes Level 6 9 2 Duress Reporting 9 2 E Earth Ground 3 26 Enable 5800 RF Button Force Arm 5 13 Enable 5800 RF But...

Страница 105: ...ow Speed Format Primary 5 5 Low Speed Format Secondary 5 5 M Manager Codes Level 2 9 1 Master Codes Level 1 9 1 Master Keypad 2 3 MODEM COMM 7 1 10 3 modems 7 1 Mounting the Control Cabinet 3 1 Multi Access 9 3 Multiple Alarms 5 2 Multiple Partition Access 9 2 N No Alarm Response Type 23 4 6 Non Alarm Report Codes First Digit 5 7 5 11 Non Alarm Report Codes Second Digit 5 7 Non Alarm Report Codes ...

Страница 106: ... 5 11 RF Transmitter Low Battery Sound 5 11 Ring Count 7 2 Ring Detection Count 5 5 RINGER EQUIVALENCE C 1 RJ31X 3 6 RJ31X jack 3 21 RLY VOICE DESCR 4 3 S Scheduling 1 2 6 1 Scheduling Commands B 1 Scheduling Menu Mode 6 4 Scheduling Menu Structure 6 4 Scheduling Report Codes First Digit 5 14 Scheduling Report Codes Report Codes Second Digit 5 15 Secondary Format 5 5 Secondary Phone Number 5 4 Sec...

Страница 107: ...ire or Household Fire Burglary Installations 3 4 UNABLE TO ARM LOBBY PARTITION 2 2 Unsupervised RF 3 16 Unsupervised RF UR Type 04 4 6 Use Partition Descriptor 5 15 User Access Codes 9 1 User Code Authority Levels 9 1 User Code Commands B 1 User Code Rules 9 2 User Scheduling Menu Mode 6 12 Users 2 1 V View Capabilities 9 1 VIP Module 3 20 VIP Module Phone Code 5 2 VISTA 50P VISTA 50PUL Current Lo...

Страница 108: ...etect motion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperature of the protected area appr...

Страница 109: ...NSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the product s it sells may not be compromised or circumvented that the product s will prevent any personal injury or property loss by burglary robbery...

Страница 110: ...WWW DIYALARMFORUM COM ...

Страница 111: ...WWW DIYALARMFORUM COM ...

Страница 112: ... 1 9 l N5944 6V2 5 04 Rev A 165 Eileen Way Syosset New York 11791 Copyright 2004 Honeywell International Inc www honeywell com security WWW DIYALARMFORUM COM ...

Отзывы: