Commercial Fire and Burglary

Commercial Fire and Burglary

Commercial Fire and Burglary

Commercial Fire and Burglary    

Partitioned Security System

Partitioned Security System

Partitioned Security System

Partitioned Security System    

 with Scheduling

 with Scheduling

 with Scheduling

 with Scheduling

    

 
 

Programming Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K3840V5  10/09  Rev. A  

 

Содержание Ademco VISTA-32FB

Страница 1: ... B B Commercial Fire and Burglary Commercial Fire and Burglary Commercial Fire and Burglary Commercial Fire and Burglary Partitioned Security System Partitioned Security System Partitioned Security System Partitioned Security System with Scheduling with Scheduling with Scheduling with Scheduling Programming Guide K3840V5 10 09 Rev A ...

Страница 2: ... KEYPAD SOUNDING N 0 disable 1 enable Must be set to 1 enabled 20 VIP MODULE PHONE CODE N Enter 01 09 for the first digit enter 11 for or 12 for for the second digit Not used Must be set to 00 22 KEYPAD PANIC ENABLES PARTITION SPECIFIC N 0 disable 1 enable Must be set to 000 for partition 1 in fire systems 23 MULTIPLE ALARMS PARTITION SPECIFIC N 0 disable 1 enable Must be set to 1 enabled 26 INTEL...

Страница 3: ... to 0 1 44 WIRELESS KEYPAD TAMPER DETECTION N 0 disable 1 enable Not used Must be set to 0 1 45 EXIT DELAY SOUNDING PARTITION SPECIFIC N 0 disable 1 enable Must be set to 0 disable for partition 1 1 48 WIRELESS KEYPAD ASSIGNMENT N 0 none 1 2 partition number Not used Must be set to 0 1 49 SUPPRESS TX SUPERVISION SOUND N 0 disable 1 enable Must be set to 0 disable 1 53 DISABLE DOWNLOAD CALLBACK N 0...

Страница 4: ...extended delay 3 19 AUXILIARY INPUT ALTERNATE FUNCTION ENABLE N 0 disable 1 enable Must be set to 0 disable 3 20 TRIGGER OUTPUTS FUNCTION SELECTION N 0 remote keypad sounder 1 keyswitch LEDs Must be set to 0 remote keypad sounder 3 21 MAXIMUM NUMBER OF DIALER ATEMPTS Y 1 8 Must be set at 3 4 or 5 3 50 ZONE TYPE RESTORE ENABLES FOR TYPES 16 18 N 0 disable 1 enable Must be set to 1 enable 3 55 RESET...

Страница 5: ...utlined in RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure Multiple Partition System You must enter the number of partitions you are using in data field 2 00 to set the system for multiple partitions Use the VISTA 32FB SINGLE PARTITION and the PARTITION SPECIFIC PROGRAM FORMS when programming the system for multiple partitions Follow the steps outlined in RECOMM...

Страница 6: ... keypad sounding options Also use this mode to assign RF receivers relay modules and Communicators 7845i ent 6 Use 93 Menu Mode for zone programming Refer to Zone Programming in this guide to program zone response types assign right loop zones and wireless zones assign zones to partitions and to program alarm report codes 7 Use 93 Menu Mode for programming outputs Refer to Output Programming in th...

Страница 7: ...ecific 85 Partition Specific 87 Partition Specific 88 Partition Specific 89 Communications 90 Partition Specific 1 12 System Wide 1 13 System Wide 1 17 System Wide 1 18 Partition Specific 1 19 Partition Specific 1 20 System Wide 1 21 System Wide 1 22 System Wide 1 23 System Wide 1 24 System Wide 1 25 System Wide 1 26 Partition Specific 1 28 System Wide 1 29 System Wide 1 30 System Wide 1 31 System...

Страница 8: ...mmercial Fire installations 19 RANDOMIZE AC LOSS REPORT 2 0 within 2 minutes 1 10 40 min 2 1 3 hours 3 6 12 hours without Type 13 1 3 hours with Type 13 20 VIP MODULE PHONE CODE Not used Enter 01 09 for the first digit enter 00 11 11 for or 12 for for the second digit Must be set to 00 for Commercial Burglary and Commercial Fire installations 22 KEYPAD PANIC ENABLES 001 1 enable 0 disable 995 996 ...

Страница 9: ...g 1 option 1 34 alarms and alarm restores go to both primary and secondary numbers while all other reports go to secondary only If used with Split Reporting 2 option alarms and alarm restores go to both open close and test messages go to secondary only while all other reports go to primary If used with Split Reporting 3 option fire alarms and fire restores signals go to both all other reports go t...

Страница 10: ...C ENABLE 0 0 No 1 Bypass E E and Interior zones faulted after exit delay Must be 0 for Commercial Burglary installations 1 21 EXIT DELAY RESET 0 0 No 1 Resets Exit Delay to programmed value after zone is closed and then faulted prior to end of exit delay Must be 0 for Commercial Burglary installations FIELDS 1 22 1 25 Allow four sets of two zones each to be linked so that both must fault within a ...

Страница 11: ...ot Used Must Be Set To 0 0 0 disable 1 enable 1 73 PRINTER BAUD RATE Not Used Must Be Set To 0 0 1 300 0 1200 1 74 RELAY TIMEOUT XXX MINUTES 000 Enter relay timeout 0 127 in multiples of 2 minutes desired for 80 Menu Mode time driven event relay command numbers 04 09 and 93 Menu Mode Output Programming output command 56 1 75 RELAY TIMEOUT YYY SECONDS 000 Enter relay timeout 0 127 seconds desired f...

Страница 12: ...AD OF CHECK 0 0 CHECK 1 TRBL 3 01 EVENTS DISPLAY LOCK 1 0 scroll all alarms 1 lock display of first fire alarm NOTE Must be set to 1 for Commercial Fire Installations 3 12 ZN TYPE 18 DELAY USE 1 0 disable 1 enable NOTE Must be set to 0 for Commercial Fire Installations 3 13 FIRE SUPERVISORY RESPONSE TO OPEN SHORT Applies to Zone Type 18 0 0 Trouble on open Supervisory on short 1 Supervisory on ope...

Страница 13: ...minutes 00 no timeout 00 00 Minimum 16 minutes for Commercial Burglary installations 3 61 AUX RELAY FUNCTION 1 0 trouble supervisory 1 alarm silenced by code off 2 smoke detector reset 3 battery save 4 alarm silenced by code 67 NOTE See Data Field Descriptions in the Installation and Setup Guide for specific information 3 82 ENABLE BURG FEATURES ON PART 1 1 0 disable disables AWAY STAY MAX TEST IN...

Страница 14: ...burglary panic types only Do not use in partition 1 in Fire systems 23 MULTIPLE ALARMS 1 1 enable 0 disable Must be 1 for Commercial Burglary installations 29 QUICK ARM 1 1 enable 0 disable 32 PRIM SUBS ACCT Enter 00 09 B F 11 15 15 15 15 15 38 PREVENT ZONE XXX BYPASS 000 001 032 000 if all zones can be bypassed 39 ENABLE OPEN CLOSE REPORT 1 FOR INSTALLER CODE 1 enable 0 disable 84 SWINGER SUPPRES...

Страница 15: ...G WINDOWS See system wide field 2 11 if enabling field 2 10 This feature adds high security to the installation 0 disable 1 enable 2 18 ENABLE GOTO FOR THIS PARTITION 0 1 Allow log on from other partitions 0 disable NOTE Must be disabled 0 for partition 1 in Commercial Fire installations 2 20 ENABLE J2 TRIGGERS BY PARTITION 1 0 disable for displayed partition 1 enable for displayed partition 2 22 ...

Страница 16: ... Zone Dialer report code for zone Input Device Type for zone whether RF polling loop etc Enrolling serial numbers of 5800 Series transmitters serial polling loop devices into the system Zone Attributes e g Arm w Fault Silent etc EXPERT MODE 1 YES 0 NO 0 Same as Zone Programming except Done with a minimum number of keystrokes Can program wireless keys using pre defined templates NOTE Be aware some ...

Страница 17: ...n prompts will be displayed after the device s Serial and Loop numbers have been entered later ENTER ZONE NO 000 QUIT 010 Zone 010 entered Enter the 3 digit zone number to be programmed as follows Protection Zones 001 032 Relay Zones 601 632 use for relays on 4204CF modules only ECP Device Supervisory Zones 800 830 System Supervisory Zones 988 990 992 duress 997 Keypad Panic Zones 995 Do not use i...

Страница 18: ...Enter the report code The report code consists of 2 hexadecimal digits each in turn consisting of 2 numerical digits For example for a report code of 3C enter 03 for 3 and 12 for C Refer to the System Communication section in the Installation and Setup Guide for more information about report codes and reporting formats Press to continue 010 BELL RLY SEL 0 Each zone can be assigned to activate eith...

Страница 19: ...on type transmitter press and release the button wait approximately 4 seconds then press and release the button a second time OR b Manually enter the 7 digit serial number printed on a label on the transmitter using the Alpha keypad Then press the key the cursor moves to the L position You can edit the loop number if necessary When the loop number is acceptable press OR c Press key C to copy the l...

Страница 20: ...nsmit the correct serial number 010 ZT P RC In L 03 1 3C RF 1s If the serial number transmitted does match the serial number entered the system beeps 3 times and a summary display appears showing that zone s programming Note that an s indicates that a transmitter s serial number has been enrolled Press to accept the zone information ENTER ZONE NO 000 QUIT 011 The system now returns to the ENTER ZO...

Страница 21: ...licate wireless keys see Entering Wireless Keys later Zn ZT P RC In L 010 03 1 10 RF Enter all zone information except for Loop number or press C to copy the zone information on this screen from the last saved zone including Loop ZT Zone Type P Partition RC Report Code In Input Device Type L Loop number to which the sensor is connected NOTE Pressing the C copies the zone information from the last ...

Страница 22: ...l Number enter 0 in the loop number field The serial number will change to 0 s If 0 was entered in error simply re enter the loop number or press and the serial number will return to the display XMIT TO CONFIRM PRESS TO SKIP The prompt to confirm appears This prompt only appears if you answered Yes at the SET TO CONFIRM prompt The system enters a confirmation mode so that the operation of the actu...

Страница 23: ...e system at one time In actuality you may skip from one main menu option to another by pressing 0 N at each main menu option Main menu options are highlighted in bold text To enter report codes do the following Enter Program Mode Installer Code 8 0 0 Then press 93 Enter 0 N at each main menu option until the Report Code Programming option is displayed PROMPT EXPLANATION REPORT CODE PROG 1 YES 0 NO...

Страница 24: ...SS GRP 001 016 00 Enter the first digit of the Bypass Report Code double digit entry and press The second digit for two digit reporting formats is automatically the ID second digit of the Alarm Report Code for each zone if programmed Press to continue BYPASS RESTORE GRP 001 016 00 Enter the first digit of the Bypass Restore Report Code double digit entry and press The second digit for two digit re...

Страница 25: ... Press Enter the second digit of the report If the user number is desired as the second digit enter 01 not necessary for Contact ID or High Speed formats Press to continue Enter the rest of the codes in the same manner Other codes in System Group 2 are Time Set Log Reset Dialer Queue Overflow Exit Error by Zone Exit Error by User Recent Close Once you have entered these report codes the system pro...

Страница 26: ...enter other system report codes enter 0 N Press to continue System Group 4 Codes PROMPT EXPLANATION SYSTEM GROUP 4 1 YES 0 NO 0 To enter System Group 4 codes press 1 YES WALK TEST START 1st 00 2nd 00 Enter the first digit of the Fire Walk Test Start Report Code Press Enter the second digit of the report code Press to continue Enter the rest of the codes in the same manner Other codes in System Gro...

Страница 27: ...Descriptors 1 Select ZONE DESCRIPTOR mode The keypad keys perform the following functions 3 Scrolls both alphabet and actual words in ascending alphabetical order 1 Scrolls both alphabet and actual words in descending alphabetical order 2 Adds or removes an s or s to a vocabulary word 6 Switches between alphabet and actual word list used to accept entries 8 Saves the zone description in the system...

Страница 28: ...e message For example to replace READY TO ARM with the message SERVICE 424 0177 proceed as follows Press 6 to move the cursor to the right and continue until the cursor is positioned over the first location on the second line Press 3 to advance through the alphabet to the first desired character in this case S Press 1 to go backward when necessary When the desired character is reached press 6 The ...

Страница 29: ...rd or word string cannot exceed 10 characters 5 Save the word by pressing 8 This returns you to the CUSTOM WORD display The custom word or string of words is automatically added to the built in vocabulary at the end of the group of words beginning with the same letter Custom words are retrieved as word numbers 255 to 314 for words 1 to 60 respectively when using method 3a to enter alpha descriptor...

Страница 30: ...VING 122 LOADING 123 LOCK 124 LOOP 125 LORRA 126 LOW 127 LOWER 128 MACHINE 129 MAGNETIC 130 MAIDS 131 MAIN 132 MASTER 133 MAT 134 MEDICAL 135 MEDICINE 136 MICROWAVE 137 MONEY 138 MONITOR 139 MOTHERS 140 MOTION 141 MOTOR 142 MUD 143 NORTH 144 NURSERY 145 OFFICE 146 OIL 147 OPEN 148 OPENING 149 OUTSIDE 150 OVERFLOW 151 OVERHEAD 152 PAINTING 153 PANIC 154 PASSIVE 155 PATIO 156 PERIMETER 157 PHONE 158...

Страница 31: ...number of partitions programmed for system in field 2 00 This is the primary partition for the device Enter 3 to make this keypad a Master keypad for the system Press to accept entry 01 SOUND OPTION 00 If you entered device type 01 alpha keypad this prompt appears Keypads can be individually programmed to suppress arm disarm beeps entry exit beeps and chime mode beeps This helps prevent unwanted s...

Страница 32: ...HIFT key function press SHIFT key then press desired function key Normal and SHIFT key Functions Key Normal Key Function SHIFT Key Function BS ESC BS Press to delete entry ESC Press to quit Program Mode Also can reset EEPROM defaults Scroll down programming Scroll up programming N Y N Press for NO answer Y Press SHIFT Y for YES answer SHIF T Press before pressing a SHIFT key function Will light RE...

Страница 33: ...ges using the control panel s customer number If these numbers are different you will be billed for two AlarmNet Communicator accounts PROMPT EXPLANATION ODD Y N N Enter Y for odd system flag N for even system flag Alarmnet Y N Y Enter Y if this is an AlarmNet installation Enter N if this is a private system and skip to Question 7 CS ID 11 Enter the primary central station s system ID number 1 7F ...

Страница 34: ...e that must occur to a zone or group of zones zone list in order to activate the device These conditions apply only when a zone list is used The different choices for EVENT are listed below and in Programming Relays later in this section ALARM Action begins upon any alarm in an assigned zone in the zone list FAULT Action begins upon any opening of an assigned zone in the zone list TROUBLE Action b...

Страница 35: ...1 96 This is a reference number only used for identification purposes The actual module address and relay number on the module are programmed in the last two prompts Press to continue 02 A EV ZL ZT P STT 0 0 00 00 0 Press to continue 02 A ZL ZT P STOP 0 00 00 0 The keypad displays a summary STOP screen Press to continue 02 RELAY ACTION NO RESPONSE 0 The Relay Action is the way in which the relay w...

Страница 36: ...or alarm as the START option If you are using options 56 and or 57 usually as the STOP Zone Type you must program data fields 1 74 and 1 75 for the respective relay timeouts for minutes and seconds Do not use a zone programmed with an RF Button Input Type BR to STOP a relay The system will not de activate the relay PROMPT EXPLANATION 02 STOP ZN LIST 00 If a zone list is being used to stop this rel...

Страница 37: ...t s corresponding supervisory zone This is equal to 600 Relay ID No For example if you are programming Relay ID No 1 the relay s supervisory zone 601 Program this zone with response type 05 Day Night in Zone Programming Zone List Programming After all relays have been programmed upon entering 00 at the ENTER RELAY NO prompt you are asked to enter a zone list If a zone list number was used to start...

Страница 38: ...ogram voice descriptors for relays ENTER RELAY NO 00 QUIT 01 Enter the 2 digit relay number 01 32 for the relay desired or enter 00 to quit Relay Voice Descriptor Programming Mode Press 01 ENTER DESC d1 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list enter the 3 digit index number for the first word of the relay descriptor phrase Press to accept entry 01 ENTER DESC d2 ...

Страница 39: ...r 029 Four 073 Fourth 217 Foyer 137 Front 087 Garage 023 Word Index Gas 138 Glass 139 Hall 050 Heat 010 Inside 209 Kitchen 022 Laundry 140 Left 027 Library 141 Light 019 Living 030 Loading 142 Lower 094 Machine 143 Master 144 Medical 014 Motion 145 Nine 078 Ninth 222 No 165 North 146 Not 012 Word Index Off 011 Office 147 On 058 One 070 Open 148 Outside 210 Panic 013 Partition 090 Patio 149 Phone 0...

Страница 40: ... no Option Part 1 Part 2 Entry Delay 1 00 30 225 seconds Exit Delay 1 00 45 225 seconds Entry Delay 2 00 30 225 seconds Exit Delay 2 00 45 225 seconds Quick Arming Multiple Alarms per Arming Console Panic for Zone 995 1 Console Panic for Zone 996 3 Console Panic for Zone 999 Allow Sign on GOTO function Non Bypassable Zone 001 032 Bell 1 Sounder Duration 2 min increments Bell 2 Aux Relay Sounder Du...

Страница 41: ...it and Chime Mode Beeps Defaults Addresses 00 Alpha Keypad No Suppression ACCESS CODES and USER DEFINITIONS FOR PARTITIONS 1 and 2 Partition 1 Partition 2 4 digit Security Code Access Group 0 1 8 3 Digit User Auth Level Open Close Group Bypass RF Key Global Arm 3 Digit User Auth Level Open Close Group Bypass RF Key Global Arm Authority Levels 1 Master arm disarm bypass and or modify lower level us...

Страница 42: ... Bell Relay Activation Serial Loop Tamper Panel ID Access Point Bypass Group Silent Auto STAY STAY Mode Vent Zone Arm w Fault Input Type Part 1 2 Zone Type ZONE DEFINTION FOR ZONES 01 25 Zone No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 ...

Страница 43: ...r 3 words max Rpt Code Bell Relay Activation Serial Loop Tamper Panel ID Access Point Bypass Group Silent Auto STAY STAY Mode Vent Zone Arm w Fault Input Type Part 1 2 Zone Type ZONE DEFINTION FOR ZONES 26 32 Zone No 26 27 28 29 30 31 32 ...

Страница 44: ... Report Code Zone Information and Alpha Descriptor 3 words max 995 see note below 996 999 NOTE Do Not Use Zone No 995 in a Fire Alarm application ZONE DEFINITIONS FOR SYSTEM ZONES 970 975 988 990 and 997 Zone No Zone Type Bell Relay Activation Report Code Zone Information and Alpha Descriptor three words max 970 971 972 973 974 975 988 990 997 ...

Страница 45: ...ne Type Report Code Zone Information and Alpha Descriptor 3 words max 601 617 602 618 603 619 604 620 605 621 606 622 607 623 608 624 609 625 610 626 611 627 612 628 613 629 614 630 615 631 616 632 NOTE Only the relays on 4204CF modules may be supervised If supervision is programmed for other types of Output Devices unpredictable results may occur ...

Страница 46: ... fire 18 supervisory 27 Not Used 03 perimeter 10 interior delay 19 24 hour trouble 28 Not Used 04 interior follower 12 Not Used 20 arm stay 29 Not Used 05 day night burglary 13 remote P S 21 arm away 06 24 hour silent 14 CO detector alarm Input Types Bells Auxiliary Relay Activation 00 not used 07 DIP switch type polling loop 0 none 4 auxiliary relay 01 hardwired 08 right loop dip switch poll loop...

Страница 47: ...device address Set the DIP switches on the device for that address 2 For V Plex devices must be programmed in the Zone Programming section 3 If you are using outputs on V Plex e g 4101SN no more than 20 of the V Plex outputs may be programmed for the same START or STOP condition Also if you are using ZONE for the START of a V Plex output and want that output to stop when the same zone restores the...

Страница 48: ...t d S T A R T S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Relay Group Restrict 0 V Plex 1 4204 4204CF V Plex Zone or Dev Add 4204 4204CF Relay for 4204 4204CF 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 ...

Страница 49: ...t d S T A R T S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Relay Group Restrict 0 V Plex 1 4204 4204CF V Plex Zone or Dev Add 4204 4204CF Relay for 4204 4204CF 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 ...

Страница 50: ...d S T A R T S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Relay Group Restrict 0 V Plex 1 4204 4204CF V Plex Zone or Dev Add 4204 4204CF Relay for 4204 4204CF 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 ...

Страница 51: ... Not Used 33 Any Burglary Alarm 57 YY Seconds enter YY in field 1 75 13 Remote P S 34 Code 71 58 Duress 14 CO Detector Alarm 35 Code 72 16 Fire With Verification 36 At Bell Timeout 17 Waterflow 37 2 Times Bell Timeout 60 Audio Alarm Verification must be selected for both START and STOP operation 18 Fire Supervisory 38 Chime 61 Code 67 19 24 Hour Trouble 39 Fire Alarm 62 Bell 2 Timeout 20 Arming ST...

Страница 52: ...t 9 Started or stopped by zone numbers enter 000 to end entries Zone List 10 Started or stopped by zone numbers enter 000 to end entries Zone List 11 Started or stopped by zone numbers enter 000 to end entries Zone List 12 Started or stopped by zone numbers enter 000 to end entries Zone List 13 Started or stopped by zone numbers enter 000 to end entries Zone List 14 Started or stopped by zone numb...

Страница 53: ...ing and closing window for each day of the week and holidays Holidays 1 YES 0 NO 0 For defining up to 16 holidays for which partitions they apply Timed Events 1 YES 0 NO 0 For defining up to 20 time driven events with the following parameters Time window Action desired Action specifier Activation time Days of the week Access Sched 1 YES 0 NO 0 For defining the limitation of access schedules for th...

Страница 54: ...15 16 17 18 19 20 Keep this worksheet handy as you will be asked for a given time window number later in this section Because the time windows are shared among both partitions it is important to make sure that changing a time window does not adversely affect desired actions in the other partition Daily Open Close Schedule Worksheet Using the time windows previously defined fill in the required dat...

Страница 55: ...hat appear in sequence HOL Partition Month Day 1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Time Driven Event Worksheet The system provides up to 20 time driven events that can be programmed for the system Fill in the required data on the worksheet below and follow the procedure in the installation and setup guide as you enter the data during the displays and prompts that appear in sequence Sched Ti...

Страница 56: ...lay Close for 2 seconds 04 Relay Close XX minutes field 1 74 05 Relay Close YY seconds field 1 75 06 Relay Group On 07 Relay Group Off 08 Relay Group Close for 2 seconds 09 Relay Group Close XX minutes field 1 74 10 Relay Group Close YY seconds field 1 75 Arm Disarm commands Action Specifier for commands 20 24 is Partition s Activation times 1 Beginning 2 End 3 During 5 Random Start 6 Random End 7...

Страница 57: ...pear in sequence Acc Mon Tues Wed Thurs Fri Sat Sun Hol Sch W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 1 2 3 4 5 6 7 8 Temporary Schedule 81 Menu Mode The system provides a Temporary Schedule for each partition Enter the temporary scheduling mode by pressing Installer Code 81 Fill in the required data on the worksheet below and follow the procedure in the installation and setup guide as you e...

Страница 58: ... 58 NOTES ...

Страница 59: ... 59 NOTES ...

Страница 60: ... 60 NOTES ...

Страница 61: ... 61 NOTES ...

Страница 62: ... 62 NOTES ...

Страница 63: ... 63 NOTES ...

Страница 64: ...ÊK3840V5Š K3840V5 10 09 Rev A 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 Copyright 2009 Honeywell International Inc www honeywell com security ...