6.2 XPU error code (item EP)
The XPU error code is a three-digit number. When the XPU detects an error about a certain item, that item
follows the error code, separated by a space.
For instance:
067 LL :
invalid level format in item
LL
.
Some XPU error codes of item
EP
are listed below, with suggestions for solving the problem. For a complete
overview, refer to “Item documentation for Honeywell Enraf series 854 ATG” and in the item help of the
service tool Engauge.
000
No error
011
NOVRAM version error
New software is installed; requires NOVRAM initialization
014
NOVRAM operation error
Set item
03
to ‘@’; check all settings, there may be an error
017
NOVRAM init failed
NOVRAM seize too small. Use XPU-1 board with larger NOVRAM seize
021
SPU start-up failure
SPU board not well connected in backplane, or defective.
033
SPU fatal error
SPU board not well connected in backplane, or defective.
036
Jumper setting changed
Jumper setting changed while power was on. Give reset (
RS
) command.
040
Missing SPU board
Missing SPU board or board not well connected in backplane, or defective.
051
Unknown item
Item not known to 854 ATG, check for correct item.
053
Invalid item length
Wrong data field length, check for correct item setting.
056
Wrong protection level
First enter protection level 1 or 2.
067
Invalid level format
Check item
LD
, then give the setting in the correct level format.
071
Invalid decimal separator
Check item
DP
, then give the setting with the correct decimal separator.
076
Invalid floating point format
Give the setting in the correct floating point format (refer to section 3.3.3).
081
Command disabled by
HC
Command is currently disabled by the host command (
HC
)
082
Invalid password
Give the correct password for
W1
and
W2
.
096
Password read not allowed
Password read access not allowed
101
Watchdog error
The watchdog reset is a sign that there is a serious fault, caused by interference,
or a faulty XPU board.
136
SPU board not responding
Missing SPU board, or SPU board not well connected in backplane, or SPU
board defective.
137
Optional board not responding
Missing optional board, or optional board not well connected in backplane, or
optional board defective.
999
Fatal XPU error
Serious internal XPU software error; check contents of item
00
and report to
Honeywell Enraf Delft.
6.3 SPU error code (item ES)
The SPU error code is a four-digit number. Some SPU error codes of item
ES
are listed below, with
suggestions for solving the problem. For a complete overview, refer to “Item documentation for Honeywell
Enraf series 854 ATG” and in the item help of the service tool Engauge.
0000
No error
0104
F0
range error
Frequency constant 0 value is out of range (probably after NOVRAM init). Give
correct setting in item
F0
, or calibrate force transducer (refer to section 5.5).
0407
Force transducer initialisation error
The force transducer does not start-up correctly, or the motor unit has not been
unlocked.
0553
Reference encoder error 1 A minimum correlation between the reference encoder table and the values read
0554
Reference encoder error 2
from the actual reference encoder is not achieved. Either stepper motor or the
reference encoder is defective or filthy. Check motor and reference encoder
(excessive oil?).
0555
Reference encoder error 3
Motor slack of more than ¼ revolution appeared. Recalibrate the gauge.
0601
Force transducer error 1
Frequency of the force transducer is too low
0602
Force transducer error 2
Frequency of the force transducer is too high
0605
No wire tension
A wire rupture was detected or the motor unit has not been unlocked, or the
force transducer is defective.
0607
Servo Auto Test failed for
Make sure that the mechanical moving parts of the gauge can move as
3 consecutive attempts
intended.
0610
Wire tension too low
The wire tension has been too low for a while. Solve the problem or adjust item
ML
.
0611
Wire tension too high
The wire tension gas been too high for a while. Solve the problem; clean the
displacer.
Содержание 854 ATG Series
Страница 1: ...Instruction manual Series 854 ATG level gauge ...
Страница 2: ......
Страница 53: ...Appendix Instruction manual 854 ATG Page 51 ...
Страница 55: ...Appendix Instruction manual 854 ATG Page 53 ...
Страница 56: ...Appendix Page 54 Appendix C ASCII table ...
Страница 57: ...Appendix Instruction manual 854 ATG Page 55 Appendix D Display formats Level and Temperature display format A ...
Страница 58: ...Appendix Page 56 Level display format B Average gas temperature display format C ...
Страница 60: ...Appendix Page 58 HIMS pressure displays format F and H Servo density display format I ...
Страница 61: ...Appendix Instruction manual 854 ATG Page 59 Analog level output display format J Water level display format K ...
Страница 62: ...Appendix Page 60 Appendix E PCB layout XPU 2 HCU HCU SPU II GFC ...
Страница 67: ......