![Honeywell 854 ATG Series Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/honeywell/854-atg-series/854-atg-series_instruction-manual_151778034.webp)
Operation
Page 32
4.8 Servo Auto Test
The Servo Auto Test (SAT hereafter) is an automatic safety related function meant to reduce the small risk of
tank overfill caused by a failing servo gauge. Immediate after the gauge detects that tank loading has finished
a SAT is executed to rule out (or detect) that the gauge is unable to measure the product level due to some
failure (e.g. blockage of displacer).
The gauge will raise the displacer over a programmable distance (item
SH
). If the movement is not completed within the expected time, the gauge will retry. If this second try also
fails, a third and final attempt is made. Should even the third try fail, the gauge will update the display by
removing the measurement unit and display the fill mode. After that the gauge will go into General Fail mode
and item
ES
is set to the value 607 (SAT failed for three consecutive attempts). From this moment on the
gauge will respond only to status requests and the reset command (item
RS
).
The SAT will not only be executed immediately after tank loading has apparently stopped, but also at regular
intervals configurable through item
SI
.
The SAT can also be performed manually by entering the command
PQ
.
The default behaviour of the SAT can be influenced by means of a number of configuration items.
Item
Name
Description
SE
SAT enable
When set to 'E' (enabled) a SAT will be started roughly 1 minute after
tank loading has apparently stopped. Furthermore SATs will be
executed at regular intervals. When set to ‘D’ (disabled) there will be
no automatic SAT at all. The operator can however start a SAT by
manually entering the
PQ
command.
SH
SAT raise height
With this item the operator can configure the height over which the
displacer is raised during the SAT.
SI
SAT interval time
With this item the operator can configure the time between two
consecutive SATs.
SY
SAT invalidate display and level
When set to '
N
' (NO), during SAT
- An asterisk ('*') will be shown on the same position where
normally the arrow up/down symbols are displayed.
When set to '
Y
' (YES), during SAT
- An asterisk ('*') will be shown on the same position where
normally the arrow up/down symbols are displayed.
- Both the measurement unit and the measurement type will be
set to exclamation marks.
- All level related GPU records will be invalidated.
- Items like
QS
,
LQ
,
UQ
and
CQ
are unaffected.
Содержание 854 ATG Series
Страница 1: ...Instruction manual Series 854 ATG level gauge ...
Страница 2: ......
Страница 53: ...Appendix Instruction manual 854 ATG Page 51 ...
Страница 55: ...Appendix Instruction manual 854 ATG Page 53 ...
Страница 56: ...Appendix Page 54 Appendix C ASCII table ...
Страница 57: ...Appendix Instruction manual 854 ATG Page 55 Appendix D Display formats Level and Temperature display format A ...
Страница 58: ...Appendix Page 56 Level display format B Average gas temperature display format C ...
Страница 60: ...Appendix Page 58 HIMS pressure displays format F and H Servo density display format I ...
Страница 61: ...Appendix Instruction manual 854 ATG Page 59 Analog level output display format J Water level display format K ...
Страница 62: ...Appendix Page 60 Appendix E PCB layout XPU 2 HCU HCU SPU II GFC ...
Страница 67: ......