393691 LP GAS AND 394588 NATURAL GAS CONVERSION KITS

Automation and Control Solutions

Honeywell International Inc.

1985 Douglas Drive North

Golden Valley, MN  55422

customer.honeywell.com

® U.S. Registered Trademark
© 2016 Honeywell International Inc.
69-0244EF—01    M.S.  11-16
Printed in U.S.A.

8.

Turn gas supply back on to other appliances 
and relight all pilot flames according to 
appliance manufacturer instructions.

9.

Proceed to Checkout section.

Table 1. Converting Gas Flow Rate.*

CHECKOUT

1.

Make certain the primary air supply to the main 
burner is properly adjusted for complete 
combustion at final pressure regulator setting. 
Main burner must light reliably under all 
conditions.

2.

Place system in operation and observe through 
at least one complete cycle to assure all con-
trols are operating properly.

3.

If manometer (pressure gauge) method is used, 
perform Gas Leak Test at outlet pressure tap plug.

4.

Apply the conversion label in the conversion kit 
to the gas control, heating appliance, and any 
other controls to show conversion to a new type 
of gas.

Time (sec)

Flow (cfh)

Flow (m

3

/hr)

40

90

2.55

41

88

2.50

42

86

2.44

43

84

2.38

44

82

2.32

45

80

2.27

46

78

2.21

47

77

2.18

48

75

2.12

49

73

2.07

50

72

2.04

51

71

2.01

52

69

1.95

53

68

1.93

54

67

1.90

55

65

1.84

56

64

1.81

57

63

1.78

58

62

1.76

59

61

1.73

60

60

1.70

62

58

1.64

64

56

1.59

66

54

1.53

68

53

1.50

70

51

1.44

72

50

1.42

74

49

1.39

76

47

1.33

78

46

1.30

80

45

1.27

84

43

1.22

88

41

1.16

92

39

1.10

96

38

1.08

100

36

1.02

105

34

0.96

110

33

0.93

115

31

0.88

120

30

0.85

125

29

0.82

130

28

0.79

135

27

0.76

140

26

0.74

150

24

0.68

160

23

0.65

170

21

0.59

180

20

0.57

Time (sec)

Flow (cfh)

Flow (m

3

/hr)

Содержание 393691

Страница 1: ...RNING Fire or Explosion Hazard Can cause severe injury death or property damage Follow these warnings exactly 1 Disconnect power supply before wiring to prevent electrical shock or equipment damage 2 To avoid dangerous accumulation of fuel gas turn off gas supply at appliance service valve before starting installation and perform Gas Leak Test after completion of installation 3 Use only your hand ...

Страница 2: ...connec tions 3 Stand clear of main burner while lighting to pre vent injury caused from hidden leaks that could cause flashback in the appliance vestibule Light main burner 4 With main burner operating paint pipe joints including adapters and control inlet and outlet with rich soap and water solution 5 If another gas leak is detected tighten adapter screws joints and pipe connections 6 Replace par...

Страница 3: ...e pressure regulator adjustment cap screw b Using a screwdriver turn inner adjustment screw clockwise to increase or counterclockwise to decrease gas pressure to main burner c Always replace cap screw and tighten firmly to prevent gas leakage 7 Turn gas control knob to PILOT standing pilot system or OFF intermittent and direct ignition systems 8 Remove pressure gauge and replace outlet pressure ta...

Страница 4: ...at least one complete cycle to assure all con trols are operating properly 3 If manometer pressure gauge method is used perform Gas Leak Test at outlet pressure tap plug 4 Apply the conversion label in the conversion kit to the gas control heating appliance and any other controls to show conversion to a new type of gas Time sec Flow cfh Flow m3 hr 40 90 2 55 41 88 2 50 42 86 2 44 43 84 2 38 44 82 ...

Страница 5: ... AVERTISSEMENT Risque d incendie ou d explosion Peut causer des blessures graves le décès ou des dommages matériels Suivez exactement ces avertissements 1 Débranchez l alimentation électrique avant d effectuer le câblage afin de prévenir les décharges électriques ou l endommagement de l équipement 2 Pour éviter l accumulation dangereuse de gaz combustible fermez la vanne d alimentation en gaz de l...

Страница 6: ...st de fuite de gaz 1 Recouvrez les raccords de conduit au dessus de l appareil de contrôle du gaz avec une solution riche de savon et d eau Les bulles indiquent une fuite de gaz 2 Si une fuite de gaz est détectée serrez tous les raccords de conduit 3 Tenez vous à l écart du brûleur principal lors de l allumage pour prévenir des blessures causées par des fuites cachées qui pourraient entraîner un r...

Страница 7: ...ion de la pression du gaz à l aide d un manomètre indicateur de pression 1 Tournez la molette de contrôle du gaz vers la position PILOT veilleuse systèmes à veilleuse permanente ou vers la position OFF arrêt systèmes à allumage intermittent et direct 2 Retirez le bouchon de prise de pression de sortie de l appareil de contrôle du gaz et branchez l indicateur de pression Consultez la Fig 1 3 Tourne...

Страница 8: ...toujours la vis d assemblage et serrez la fermement pour prévenir les fuites de gaz 8 Rétablissez l alimentation en gaz vers les autres appareils en marche et rallumez toutes les flammes de veilleuse conformément aux instructions du fabricant 9 Passez à la section Vérification Tableau 1 Conversion du taux d écoulement du gaz VÉRIFICATION 1 Assurez vous que l alimentation en air vers le brûleur pri...

Отзывы: