34
Mounting and Connection Instructions Door controller module for MB
8.4
Detector group inputs, contacts, GBS
Detector group inputs that are not required, are not allocated to detector groups (DG00)
when programming the control panel.
3.3 V DC detector group inputs:
- Open: 3.3 V
- Terminated with 12k1: Approx. 1.65 V
input with 3.3 V
12k1±40% and is suitable for a Z-wiring connection.
(ST5)
DG input with 12 V
(ST3)
DG input with 12 V, active LOW (pull-up)
A bolt switching contact can be connected here. The input can be allocated to a bolt switching group
when programming the control panel. This input only affects the positive drive condition.
(ST9)
DG input with 3.3 V
Tamper monitoring of external readers. The input is monitored at 12k1±40%.
-
(ST4)
DG
For monitoring the opening of the door, e.g. a magnetic contact is connected to this input. The input is
monitored at
Differential detector group with clear function for connecting passive glass breakage sensors. The
input is monitored at 12k1±30% and is suitable for a Z-wiring connection.
Opening contact
-
-
-
The input must be terminated with 12k1 even if it is not used.
Glass breakage sensor
Bolt switching contact
Cover contact - external reader