28
Mounting and Connection Instructions Door controller module for MB
5.
Programming
BUS-2 address
The DIP switches located in the Door controller module
(address switch S1) are for setting the BUS-2 user
address. The individual codes can be found in the
programming protocol of the intrusion detection control
panel.
The address of the users (IK3 operating units) is
allocated automatically by the corresponding function in
the programming of the control panel.
Indicated switch position =
set!
Address 5
32
16
8
4
2
1
Address switch S1
Switch position
OFF
ON
Address value
12
3
4
5
6
ON
6.
LED indicators
7.
Installation guidelines
The BUS connection lead
be a shielded cable stranded in pairs and the cores laid according to
the diagram below.
The corresponding line cross-sections can be found in the
of the intrusion
detection control panel (Chapter on lines). The shield terminal should also be kept as short as
possible to avoid the risk of an unintentional short circuit.
must
Installation Manual
Data
0 V
+12 V DC
0 V
Data
Control panel
Module
BUS-2
0 V
0 V
U_b +12 V DC
BUS-2
Shield
Shield
12
3
4
5
6
ON
JP22
LD1 LD2
Address
switch
BUS-2
Yellow
Green
Normal operation:
Boot loader active
-
RAM is initialized when started
-
When in operation, module is
initialized by the central control
unit.
Firmware downloaded
Testing firmware after update
Faulty firmware
LD1
LD2
LD1
LD2
blinkt 50ms / 2s
aus
aus
blinkt 1x
LD1
LD2
immer aus
LD1
LD2
LD1
LD2
LD1
LD2
LD1
LD2
blinkt 50ms / 2s
aus
aus
blinkt 1x
LD1
LD2
immer aus
LD1
LD2
LD1
LD2